Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
DCSD
Site Name Priority Building Name System Name Deficiency Description Deficiency Note DCSD Category Notes
Category
Adams Stadium 1 Building 8010 Fire and Life Safety Security Alarm Replacement Beyond Useful Life - Stadium A Deficiency has been corrected or addressed
Adams Stadium 1 Building 8010 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life - Stadium A Deficiency has been corrected or addressed
Broken Windows, West And At Roof. 30 Sf
Administrative and Instructional Complex (AIC) 2 Building 9010 Exterior Storefront/Curtain Wall Replacement (Bldg SF) A Deficiency has been corrected or addressed
Broken Windows
Administrative and Instructional Complex (AIC) 3 Building 9030 Exterior Metal Exterior Door Repair A Deficiency has been corrected or addressed
Administrative and Instructional Complex (AIC) 2 Building 9020 Exterior Metal Exterior Door Replacement A Deficiency has been corrected or addressed
Damaged And Need Of Replacement In Office
Administrative and Instructional Complex (AIC) 1 Building 9020 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Service Office
Administrative and Instructional Complex (AIC) 1 Building 9030 Fire and Life Safety Security Alarm Camera Replacement Outside Entrance A Deficiency has been corrected or addressed
Administrative and Instructional Complex (AIC) 2 Building 9040 Fire and Life Safety Emergency Exit Signage Is Missing Good Shape Inside Bay A Deficiency has been corrected or addressed
Administrative and Instructional Complex (AIC) 3 Building 9040 Roofing Debris In Gutter Removal Located Beneath Trees A Deficiency has been corrected or addressed
Allgood Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Allgood Elementary School 3 Building 2011 Electrical Electrical Receptacle Replacement Exposed Wiring At Receptacle, Cr 111 A Deficiency has been corrected or addressed
Allgood Elementary School 3 Building 2013 Roofing Gutter Replacement A Deficiency has been corrected or addressed
Teacher's Work Room 131.1 - Exposed Wiring
Allgood Elementary School 3 Building 2013 Electrical Electrical Receptacle Replacement At Receptacle, Cr 125 - Replace Receptacle A Deficiency has been corrected or addressed
Near Sink With Gf1 Device
Allgood Elementary School 1 Building 2010 Fire and Life Safety Wall Pack Lighting Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Allgood Elementary School 1 Building 2010 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Allgood Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Allgood Elementary School 1 Building 2011 Fire and Life Safety Wall Pack Lighting Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Allgood Elementary School 1 Building 2011 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Allgood Elementary School 1 Building 2011 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Allgood Elementary School 1 Building 2012 Fire and Life Safety Wall Pack Lighting Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Allgood Elementary School 1 Building 2012 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Allgood Elementary School 1 Building 2012 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Allgood Elementary School 1 Building 2013 Fire and Life Safety Wall Pack Lighting Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Allgood Elementary School 1 Building 2013 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Allgood Elementary School 1 Building 2013 Fire and Life Safety Fire Alarm Replacement Old And Damaged A Deficiency has been corrected or addressed
Allgood Elementary School 1 Building 2014 Fire and Life Safety Wall Pack Lighting Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Allgood Elementary School 1 Building 2014 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Allgood Elementary School 1 Building 2014 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Allgood Elementary School 1 Building 2020 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Evidence Of Structural Deficiency At 400 Sf
Allgood Elementary School 1 Building 2012 Structural Evidence of Structural Deficiency A Deficiency has been corrected or addressed
Exterior Brick
Allgood Elementary School 1 Building 2013 Structural Evidence of Structural Deficiency Columns Show Signs Of Structure Failure A Deficiency has been corrected or addressed
At Expansion Joint - Holes. Roof Leak At
Arabia Mountain High School 3 Building 5010 Roofing Membrane Flashing At Parapet (>2') Repair Media Center And South Class Rooms With A Deficiency has been corrected or addressed
Wind Driven Rain.
Arabia Mountain High School 2 Building 5010 Roofing Modified Membrane Has Holes That Should Be Repaired Separated Joints A Deficiency has been corrected or addressed
Ashford Park Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Ashford Park Elementary School 2 Building 2010 Roofing Modified Roof Covering Replacement A Deficiency has been corrected or addressed
Ashford Park Elementary School 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing A Deficiency has been corrected or addressed
Ashford Park Elementary School 2 Building 2011 Roofing Modified Roof Covering Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Ashford Park Elementary School 1 Building 2010 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Ashford Park Elementary School 1 Building 2010 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Ashford Park Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Ashford Park Elementary School 1 Building 2011 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Ashford Park Elementary School 1 Building 2011 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Ashford Park Elementary School 1 Building 2011 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Ashford Park Elementary School 1 Building 2020 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Ashford Park Elementary School 1 Building 2020 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Ashford Park Elementary School 1 Building 2020 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Ashford Park Elementary School 3 Building 2010 Roofing Debris In Gutter Removal A Deficiency has been corrected or addressed
Ashford Park Elementary School 2 Building 2010 Roofing Gutter Joint Repair A Deficiency has been corrected or addressed
Ashford Park Elementary School 3 Building 2011 Roofing Debris In Gutter Removal Clogged A Deficiency has been corrected or addressed
Ashford Park Elementary School 2 Building 2011 Roofing Gutter Joint Repair A Deficiency has been corrected or addressed
Ashford Park Elementary School 3 Building 2011 Roofing Gutter Replacement A Deficiency has been corrected or addressed
1 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Ashford Park Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Clogged A Deficiency has been corrected or addressed
Ashford Park Elementary School 2 Building 2020 Roofing Gutter Joint Repair A Deficiency has been corrected or addressed
Austin Elementary School 3 Building 2010 Plumbing Condensate Drain Repair Broken And Roof Above Office - Rtu-6 A Deficiency has been corrected or addressed
Austin Elementary School 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility
Plan South By Entrance A Deficiency has been corrected or addressed
Avondale Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Beyond Useful Life - Top Surface Peeling Up
At Joints And Roof Drains, A Study Is Needed
Avondale Elementary School 2 Building 2010 Roofing Single-Ply Membrane Roof Covering Replacement A Deficiency has been corrected or addressed
To Determine If More Roof Scuppers Are
Needed For Adequate Drainage
Top Surface Peeling Up At Joints And Roof
Drains, A Study Is Needed To Determine If
Avondale Elementary School 2 Building 2011 Roofing Single-Ply Membrane Roof Covering Replacement A Deficiency has been corrected or addressed
More Roof Scuppers Are Needed For
Adequate Drainage
Top Surface Peeling Up At Joints And Roof
Drains, A Study Is Needed To Determine If
Avondale Elementary School 2 Building 2012 Roofing Single-Ply Membrane Roof Covering Replacement A Deficiency has been corrected or addressed
More Roof Scuppers Are Needed For
Adequate Drainage
Avondale Elementary School 3 Building 2013 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Standing Water Near Drains A Deficiency has been corrected or addressed
Avondale Elementary School 3 Building 2010 Roofing Roof Drain Cleaning Clogged Drains A Deficiency has been corrected or addressed
Avondale Elementary School 3 Building 2011 Roofing Roof Drain Cleaning Clogged Drains A Deficiency has been corrected or addressed
Avondale Elementary School 3 Building 2012 Roofing Roof Drain Cleaning All Roof Drains Are Clogged With Leaf Debris A Deficiency has been corrected or addressed
Leaf Debris Clogging Drains Causing Roof
Avondale Elementary School 3 Building 2014 Roofing Roof Drain Cleaning A Deficiency has been corrected or addressed
Leaks
Avondale Elementary School 3 Building 2010 Plumbing Sanitary Sewer Piping Replacement A Deficiency has been corrected or addressed
Avondale Elementary School 2 Building 2010 Mechanical Radiant Heater (Ceiling Panel) Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Avondale High DSA 3 Building 5022 Roofing Roof Drain Cleaning A Deficiency has been corrected or addressed
Avondale High DSA 3 Building 5022 Roofing Built Up Roofing (Bur) Covering Has Blisters That Should Be Repaired A Deficiency has been corrected or addressed
Avondale High DSA 3 Building 5023 Exterior Exterior Metal Door Repainting A Deficiency has been corrected or addressed
Avondale High DSA 3 Building 5020 Exterior Exterior Metal Door Repainting All Doors A Deficiency has been corrected or addressed
Avondale High DSA 3 Building 5010 Exterior Exterior Metal Door Repainting Paint Is Pealing A Deficiency has been corrected or addressed
Avondale High DSA 3 Building 5011 Exterior Exterior Metal Door Repainting Paint Is Pealing A Deficiency has been corrected or addressed
Avondale Stadium 1 Building 8010 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Avondale Stadium 2 Building 8010 Mechanical Gas Piping Replacement (SF Basis) Throughout A Deficiency has been corrected or addressed
Cracked Driveway, South And West Egress
Barack H. Obama Elementary 3 Site Asphalt Driveway Replacement A Deficiency has been corrected or addressed
Road. Repair And Replace.
Barack H. Obama Elementary 3 Building 2010 Electrical Electrical Receptacle Replacement Multiple Locations A Deficiency has been corrected or addressed
1206 Kindergarten - Replace Four Hinge -
Barack H. Obama Elementary 3 Building 2010 Interior Interior Door Hardware Replacement A Deficiency has been corrected or addressed
Deficient.
Install Camera Outside Cafeteria Loading
Bob Mathis Elementary School 1 Building 2010 Fire and Life Safety Security Alarm Camera Is Missing A Deficiency has been corrected or addressed
Dock.
Vegetation And Debris In Gutters. Clean And
Bob Mathis Elementary School 3 Building 2020 Roofing Debris In Gutter Removal A Deficiency has been corrected or addressed
Remove.
Flooding Occurring At East Entry Of Building
2020 (Gym). Problem Seems To Be Related
Bob Mathis Elementary School 3 Site Site Requires Civil/Drainage Study A Deficiency has been corrected or addressed
To Rainwater Runoff Into "Courtyard".
Conduct Civil Survey For Further Assessment.
Pole Lights At North-West Parking Area Are
Bob Mathis Elementary School 3 Electrical Pole Lighting Repair A Deficiency has been corrected or addressed
Failing (Flickering Or Off Completely) Repair.
Briar Vista Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Debris Observed A Deficiency has been corrected or addressed
Briar Vista Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement Old A Deficiency has been corrected or addressed
Briar Vista Elementary School 1 Building 2011 Fire and Life Safety Fire Alarm Replacement Old A Deficiency has been corrected or addressed
Briar Vista Elementary School 1 Building 2012 Fire and Life Safety Fire Alarm Replacement Old A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Building 2010 Roofing Debris In Gutter Removal Various Areas A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2020 Plumbing Water Heater Replacement Storage A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Building 2010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life
Throughout A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Building 2010 Plumbing Sanitary Sewer Piping Replacement Throughout A Deficiency has been corrected or addressed
2 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Briar Vista Elementary School 2 Building 2011 Mechanical Gas Piping Replacement (SF Basis) Throughout A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Building 2011 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life
Throughout A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Building 2011 Plumbing Sanitary Sewer Piping Replacement Throughout A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2012 Mechanical Gas Piping Replacement (SF Basis) Throughout A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Building 2012 Plumbing Gas Water Heater Replacement Mech Room A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Building 2012 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life
Throughout A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Building 2012 Plumbing Sanitary Sewer Piping Replacement Throughout A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2012 Mechanical Ductwork Replacement (SF Basis) Throughout A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2012 Electrical Panelboard Replacement Old, Elec And Mech A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2010 Mechanical Gas Piping Replacement (SF Basis) Throughout A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement Old A Deficiency has been corrected or addressed
Main Entry Front Of School, Others Around
Briar Vista Elementary School 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility A Deficiency has been corrected or addressed
School
Briar Vista Elementary School 2 Building 2010 Mechanical Heat Exchanger Replacement Storage 28 A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Building 2010 Plumbing Gas Water Heater Replacement Mech Room A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Building 2010 Plumbing Gas Water Heater Replacement Mech Room A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2010 Plumbing Water Heater Replacement Media Office A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2010 Plumbing Water Heater Replacement Custodial A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Building 2012 Electrical Interior Power Wiring Replacement Old A Deficiency has been corrected or addressed
There Is No ADA Ramp Down To The Play
Field. Grade Difference Is 20'. Length Of
Briar Vista Elementary School 3 Building 2010 Site Exterior Ramp Replacement A Deficiency has been corrected or addressed
Ramp Required Would Be Roughly 120' With
Handrails.
Briar Vista Elementary School 3 Building 2010 Interior Entry Door Does Not Have Power Assist Device Main Entrance A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Building 2010 Plumbing Restroom Is Not ADA Compliant No ADA In Building 2010 A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsMain (Modify Full)
Office A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Building 2010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
No Ramp Present A Deficiency has been corrected or addressed
None Of The Restrooms Has ADA-Compliant
Briar Vista Elementary School 3 Building 2011 Plumbing Restroom Is Not ADA Compliant A Deficiency has been corrected or addressed
Toilets.
No ADA Compliant Entry Exists Stairs To
Door. Furthermore There Is No ADA
Briar Vista Elementary School 3 Building 2012 Site Exterior Ramp Replacement A Deficiency has been corrected or addressed
Compliant Path Of Travel Between Building
2012 And The Rest Of The Buildings. On Site.
Briar Vista Elementary School 3 Building 2012 Interior Entry Door Does Not Have Power Assist Device Main 2012 Entry A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Building 2020 Interior Entry Door Does Not Have Power Assist Device No Power Assist To Gym Building 2020 A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Site Curb Ramp Does Not Meet Minimum ADA Compliance Requirements Along Drop-Off A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Site Sidewalk Longitudinal Or Cross Slope Exceeds Maximum Slope NoCriteria
ADA Compliant Entry A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Site Car Accessible Parking Spaces Restiriping Side Of Building A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2010 Exterior Concrete Pre-Cast Panel Replacement (Bldg SF) Sections Of Entire Areas A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2010 Electrical Distribution Panel Replacement Old, Main Elec A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Old, Main Elec A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Old, Main Elec A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2010 Electrical Panelboard Replacement Old, Main Elec A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2010 Electrical Panelboard Replacement Old, Kitchen A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2010 Electrical Panelboard Replacement Old, Stage, Corridors A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2012 Electrical Panelboard Replacement Old, Hallway A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2010 Electrical Switchgear Replacement Old, Main Elec A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2010 Mechanical Air Cooled Condenser Replacement Roof A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2010 Mechanical Boiler Replacement Mech Room A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2010 Mechanical Ductless Split System AC Replacement Av Work Room A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2020 Mechanical Gas Unit Heater Replacement Gym A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2010 Mechanical Infrared Electric Radiant Heater Replacement Kitchen Restroom A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Building 2010 Mechanical Large Diameter Exhausts/Hoods Replacement Roof A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Building 2012 Mechanical Large Diameter Exhausts/Hoods Replacement Roof A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Throughout A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2011 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Throughout A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2012 Mechanical Package DX Unit Replacement Throughout A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2012 Mechanical Package Roof Top Unit Replacement Roof A Deficiency has been corrected or addressed
Briar Vista Elementary School 2 Building 2010 Mechanical Steam/HW Unit Heater Replacement Storage 28 A Deficiency has been corrected or addressed
Briar Vista Elementary School 3 Building 2012 Mechanical Testing And Balancing Throughout A Deficiency has been corrected or addressed
3 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Briar Vista Elementary School 2 Building 2020 Mechanical Thru Wall AC Replacement Coach Office A Deficiency has been corrected or addressed
Briarlake Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Briarlake Elementary School 3 Building 2010 Roofing Debris In Gutter Removal Clogged With Leaf Debris A Deficiency has been corrected or addressed
Briarlake Elementary School 3 Building 2011 Roofing Debris In Gutter Removal Clogged With Leaf Debris A Deficiency has been corrected or addressed
Briarlake Elementary School 3 Building 2012 Roofing Roof Drain Cleaning Clogged With Leaves A Deficiency has been corrected or addressed
Briarlake Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Clogged With Leaf Debris A Deficiency has been corrected or addressed
Briarlake Elementary School 3 Building 2010 Exterior Exterior Metal Door Repainting Rusting Through Paint A Deficiency has been corrected or addressed
Briarlake Elementary School 3 Site Asphalt Driveway Replacement Potholes And Cracking A Deficiency has been corrected or addressed
Briarlake Elementary School 3 Site Concrete Walks Replacement Cracked A Deficiency has been corrected or addressed
Briarlake Elementary School 3 Building 2012 Exterior Exterior Metal Door Repainting Rusting Through Paint A Deficiency has been corrected or addressed
Water Damage. Due To Roof Water
Mismanagement Several Concrete Overhangs
And Columns, Footing, And CMU Walls Have
Brockett Elementary School 3 Site Site Requires Civil/Drainage Study A Deficiency has been corrected or addressed
Been Affected. Civil Study Recommended To
Understand Extent Of Damage To Under Slab
Components.
Beyond Useful Life. Bur Roofing Over Original
Mod Blt. Both Assemblies Need To Be
Brockett Elementary School 2 Building 2010 Roofing Built-up Roofing Replacement Replaced. At Roof Step Down Concrete Beam A Deficiency has been corrected or addressed
Is Exposed And Water Infiltrates Building
Through There.
Brockett Elementary School 2 Building 2011 Roofing Built-up Roofing Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Brockett Elementary School 3 Building 2011 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
No Slope A Deficiency has been corrected or addressed
Brockett Elementary School 2 Building 2012 Roofing Built-up Roofing Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Brockett Elementary School 3 Building 2012 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
No Slope A Deficiency has been corrected or addressed
Cracked And Spalling. Rain Water Flowing
From Concrete Overhangs Are Damaging
Brockett Elementary School 2 Building 2010 Exterior Concrete Pre-Cast Panel Replacement (Bldg SF) A Deficiency has been corrected or addressed
Overhangs, Exterior Concrete Columns And
Exposing Exterior Water Footings.
Brockett Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Debris A Deficiency has been corrected or addressed
Brockett Elementary School 1 Building 2020 Fire and Life Safety Wall Pack Lighting Replacement Old, Gym A Deficiency has been corrected or addressed
Brockett Elementary School 1 Building 2020 Fire and Life Safety Emergency Exit Signage Replacement Old, Gym A Deficiency has been corrected or addressed
Brockett Elementary School 1 Building 2010 Fire and Life Safety Install New Kitchen Fire Suppression Hood A Deficiency has been corrected or addressed
Browns Mill Elementary School 3 Site Playground Equipment Replacement Damaged A Deficiency has been corrected or addressed
Browns Mill Elementary School 1 Building 2010 Fire and Life Safety Security Alarm Camera Replacement Outside Front Door A Deficiency has been corrected or addressed
Browns Mill Elementary School 3 Building 2010 Fire and Life Safety Wall Pack Lighting Repair A Deficiency has been corrected or addressed
Browns Mill Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement Not Working A Deficiency has been corrected or addressed
Canby Lane Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Canby Lane Elementary School 2 Building 2010 Mechanical Ductwork Replacement (SF Basis) A Deficiency has been corrected or addressed
Canby Lane Elementary School 3 Building 2030 Roofing Debris In Gutter Removal Debris A Deficiency has been corrected or addressed
Cedar Grove Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement Old, No Fan In Classrooms Or Restrooms A Deficiency has been corrected or addressed
Cedar Grove Elementary School 1 Building 2011 Fire and Life Safety Fire Alarm Replacement Old, No Fan In The Classrooms Or Restrooms A Deficiency has been corrected or addressed
Lobby Slab Shows Differential Settlement
Cedar Grove Elementary School 1 Building 2012 Structural Evidence of Structural Deficiency Along Boys Restroom Wall- Engineering Study A Deficiency has been corrected or addressed
Recommended
Cedar Grove Elementary School 3 Building 2012 Roofing Debris In Gutter Removal Debris And Tree Growing A Deficiency has been corrected or addressed
Cedar Grove Elementary School 2 Building 2012 Roofing Gutter Joint Repair Water Leaking A Deficiency has been corrected or addressed
Roof Is Not Accessible But Staff Noted The
Cedar Grove Elementary School 2 Building 2012 Roofing Modified Roof Covering Replacement A Deficiency has been corrected or addressed
Roof Leaks And Is Original
Differential Settlement Present Between
Exterior And Interior Walls At The
Cedar Grove High School 1 Building 5010 Structural Evidence of Structural Deficiency A Deficiency has been corrected or addressed
Administration Offices. Engineering Study Is
Recommended
Debris And Granules In Gutter. Remove And
Cedar Grove High School 3 Building 5010 Roofing Debris In Gutter Removal A Deficiency has been corrected or addressed
Clean Gutters
Cedar Grove High School 3 Building 5011 Roofing Debris In Gutter Removal A Deficiency has been corrected or addressed
4 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Cedar Grove High School 3 Building 5010 Roofing Roof Drain Cleaning Clean Debris From Roof Drains A Deficiency has been corrected or addressed
Cedar Grove High School 3 Building 5012 Plumbing Urinal Repair A Deficiency has been corrected or addressed
Cedar Grove Middle School 3 Building 4010 Roofing Roof Drain Cleaning Debris A Deficiency has been corrected or addressed
Cedar Grove Middle School 1 Building 4010 Fire and Life Safety Emergency Exit Signage Replacement Old A Deficiency has been corrected or addressed
Chamblee High School 2 Building 5010 Exterior Storefront/Curtain Wall Replacement (Bldg SF) Broken Glass Pane A Deficiency has been corrected or addressed
Chamblee Middle School 1 Building 4010 Fire and Life Safety Fire Alarm Panel Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Chamblee Middle School 1 Building 4010 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Champion Middle Theme 1 Building 4010 Fire and Life Safety Emergency Exit Signage Replacement Old A Deficiency has been corrected or addressed
Champion Middle Theme 1 Building 4010 Fire and Life Safety Security Alarm Replacement Old A Deficiency has been corrected or addressed
Champion Middle Theme 1 Building 4010 Fire and Life Safety Fire Alarm Panel Replacement Old A Deficiency has been corrected or addressed
Champion Middle Theme 1 Building 4010 Fire and Life Safety Fire Alarm Replacement Old A Deficiency has been corrected or addressed
Champion Middle Theme 1 Building 4011 Fire and Life Safety Emergency Exit Signage Replacement Old A Deficiency has been corrected or addressed
Champion Middle Theme 1 Building 4011 Fire and Life Safety Security Alarm Replacement Old A Deficiency has been corrected or addressed
Champion Middle Theme 1 Building 4011 Fire and Life Safety Fire Alarm Replacement Old A Deficiency has been corrected or addressed
Champion Middle Theme 1 Building 4012 Fire and Life Safety Emergency Exit Signage Replacement Old And Damaged A Deficiency has been corrected or addressed
Champion Middle Theme 1 Building 4012 Fire and Life Safety Security Alarm Replacement Old A Deficiency has been corrected or addressed
Champion Middle Theme 1 Building 4012 Fire and Life Safety Fire Alarm Replacement Old A Deficiency has been corrected or addressed
Champion Middle Theme 1 Building 4013 Fire and Life Safety Emergency Exit Signage Replacement Old A Deficiency has been corrected or addressed
Champion Middle Theme 1 Building 4013 Fire and Life Safety Security Alarm Replacement Old A Deficiency has been corrected or addressed
Champion Middle Theme 1 Building 4013 Fire and Life Safety Fire Alarm Panel Replacement Old A Deficiency has been corrected or addressed
Champion Middle Theme 1 Building 4013 Fire and Life Safety Fire Alarm Replacement Old A Deficiency has been corrected or addressed
Chapel Hill Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement Old, Throughout Building A Deficiency has been corrected or addressed
Chapel Hill Elementary School 1 Building 2011 Fire and Life Safety Fire Alarm Replacement Old, Throughout Building A Deficiency has been corrected or addressed
Chapel Hill Elementary School 1 Building 2012 Fire and Life Safety Fire Alarm Replacement Old, Throughout Building A Deficiency has been corrected or addressed
Chapel Hill Elementary School 1 Building 2013 Fire and Life Safety Fire Alarm Replacement Old, Throughout Building A Deficiency has been corrected or addressed
Chapel Hill Elementary School 3 Building 2010 Mechanical Kitchen Exhaust Hood Replacement Kitchen A Deficiency has been corrected or addressed
Chapel Hill Elementary School 3 Building 2010 Mechanical Kitchen Exhaust Hood Replacement A Deficiency has been corrected or addressed
Chapel Hill Elementary School 3 Building 2010 Roofing Debris In Gutter Removal A Deficiency has been corrected or addressed
Chapel Hill Elementary School 3 Building 2020 Roofing Debris In Gutter Removal A Deficiency has been corrected or addressed
Chapel Hill Elementary School 3 Site Concrete Walks Replacement Cracked A Deficiency has been corrected or addressed
Chapel Hill Middle School 1 Building 4010 Fire and Life Safety Emergency Exit Signage Replacement Old, Throughout Building A Deficiency has been corrected or addressed
Chapel Hill Middle School 1 Building 4010 Fire and Life Safety Emergency Lighting System Replacement Old, Throughout Building A Deficiency has been corrected or addressed
Chapel Hill Middle School 2 Building 4010 Roofing Modified Roof Covering Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Chesnut Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Chesnut Elementary School 2 Electrical Pole Lighting Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Chesnut Elementary School 1 Building 2010 Fire and Life Safety Security Alarm Camera Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Chesnut Elementary School 3 Building 2010 Electrical Electrical Receptacle Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Chesnut Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant All Interior Door Hardware Not Compliant A Deficiency has been corrected or addressed
Chesnut Elementary School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsNot (Modify Full)
Compliant A Deficiency has been corrected or addressed
Chesnut Elementary School 3 Building 2010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
No Ramp Existing A Deficiency has been corrected or addressed
Install 2 Pole Lights At West End Of South
Chesnut Elementary School 3 Electrical Area Lighting Installation Parking Lot, 2 Pole Lights At Kitchen Staff A Deficiency has been corrected or addressed
Parking
Chesnut Elementary School 2 Building 2010 Electrical Distribution Panel Replacement Beyond Useful Life 75 Amps A Deficiency has been corrected or addressed
Chesnut Elementary School 2 Building 2010 Electrical Distribution Panel Replacement Beyond Useful Life 1000 Amps A Deficiency has been corrected or addressed
Chesnut Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Chesnut Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Chesnut Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Chesnut Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Chesnut Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Chesnut Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Clarkston High School 2 Building 5010 Electrical Public Address Repair Install 26 Speakers A Deficiency has been corrected or addressed
Clarkston High School 3 Building 5010 Electrical Canopy Lighting Replacement Broken A Deficiency has been corrected or addressed
Clarkston High School 3 Building 5013 Plumbing Condensate Drain Repair Damaged A Deficiency has been corrected or addressed
No Proper Drainage System For Inward-
Clarkston High School 3 Building 5012 Roofing Overflow Drain And Piping Installation Sloping Roof Segments, Major Ponding, A Deficiency has been corrected or addressed
Reported Roof Leaks At Gym
Columbia Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Columbia Elementary School 1 Building 2010 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Columbia Elementary School 1 Building 2010 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
5 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Columbia Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Columbia Elementary School 1 Building 2010 Fire and Life Safety Security Alarm Camera Replacement 9 Cctv Units Not Working A Deficiency has been corrected or addressed
Columbia Elementary School 1 Building 2011 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Columbia Elementary School 1 Building 2011 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Columbia Elementary School 1 Building 2011 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Columbia Elementary School 1 Building 2012 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Columbia Elementary School 1 Building 2012 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Columbia Elementary School 1 Building 2012 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2020 Fire and Life Safety Wall Pack Lighting Installation A Deficiency has been corrected or addressed
Columbia Elementary School 1 Building 2020 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Columbia Elementary School 1 Building 2020 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Columbia Elementary School 1 Building 2020 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2020 Fire and Life Safety Emergency Exit Signage Is Missing A Deficiency has been corrected or addressed
Cracked Column - Engineering Study To
Columbia Elementary School 1 Building 2010 Structural Evidence of Structural Deficiency A Deficiency has been corrected or addressed
Review Issue.
Columbia Elementary School 3 Site Aluminum Covered Walkways Replacement Clean Roof A Deficiency has been corrected or addressed
Columbia Elementary School 3 Building 2011 Roofing Debris In Gutter Removal Dirty A Deficiency has been corrected or addressed
Columbia Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Overgrown Vegetation A Deficiency has been corrected or addressed
Columbia Elementary School 3 Building 2010 Roofing Roof Drain Cleaning Clogged A Deficiency has been corrected or addressed
Columbia Elementary School 3 Building 2011 Roofing Roof Drain Cleaning Clogged A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2012 Exterior Aluminum Window Replacement Broken Glass At Room 101 A Deficiency has been corrected or addressed
Columbia Elementary School 3 Building 2010 Roofing Debris In Gutter Removal Clogged And Dirty A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Plumbing Water Heater Replacement Storage 141.4 A Deficiency has been corrected or addressed
Columbia Elementary School 3 Building 2010 Mechanical Air Compressor Replacement Mech Room 142.1 A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Mechanical Heat Exchanger Replacement Mech Yard At Ct A Deficiency has been corrected or addressed
Columbia Elementary School 3 Building 2010 Mechanical Circulation Pump Replacement Storage 142.2 A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Mechanical Electric Unit Heater Replacement Work Room, Asst. Principal 140.2 A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Mechanical Electric Unit Heater Replacement Entry Outside Gate 142 And Office Entry A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Mechanical Exterior Metal Cooling Tower Replacement Mech Yard A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Mechanical Air Cooled Condenser Replacement A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Mechanical Fan Coil Unit Replacement Storage A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement Above Ceiling A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement Above Ceiling A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement Above Ceiling A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement Above Ceiling A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement Cafeteria 142 A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement Above Ceiling A Deficiency has been corrected or addressed
Columbia Elementary School 3 Building 2010 Mechanical Testing And Balancing A Deficiency has been corrected or addressed
Columbia Elementary School 3 Building 2010 Mechanical Kitchen Exhaust Hood Replacement Kitchen 142 A Deficiency has been corrected or addressed
Columbia Elementary School 3 Building 2010 Mechanical Large Diameter Exhausts/Hoods Replacement Roof A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2011 Plumbing Water Heater Replacement A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2011 Mechanical Electric Unit Heater Replacement Girls Restroom, Boys Restroom, Office 123.1 A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2011 Mechanical Heat Pump HVAC Component Replacement Above Ceiling A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2011 Mechanical Heat Pump HVAC Component Replacement Above Ceiling A Deficiency has been corrected or addressed
Columbia Elementary School 3 Building 2011 Mechanical Testing And Balancing A Deficiency has been corrected or addressed
Columbia Elementary School 3 Building 2012 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding Water A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2020 Mechanical Electric Unit Heater Replacement Storage A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2020 Mechanical Electric Unit Heater Replacement Girls Restroom, Boys Restroom, Entry A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2020 Mechanical Thru Wall AC Replacement Office A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Storage 142.2 A Deficiency has been corrected or addressed
Columbia Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement Old Building Wiring A Deficiency has been corrected or addressed
Columbia Elementary School 3 Building 2011 Electrical Interior Power Wiring Replacement Old Wiring A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Electrical Panelboard Replacement Stage A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Electrical Panelboard Replacement Mech 142.1 A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Electrical Panelboard Replacement Hallway Storage 144.3 A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Electrical Panelboard Replacement Hallway At Music 140 A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Electrical Panelboard Replacement Hallway At Crk3 A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Electrical Panelboard Replacement Exposed Bus - Hallway At Cr10 A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Electrical Panelboard Replacement Hallway At Cr16 A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Electrical Panelboard Replacement Kitchen A Deficiency has been corrected or addressed
6 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Columbia Elementary School 2 Building 2010 Electrical Panelboard Replacement Mech 142.1 A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Electrical Panelboard Replacement Storage 142.2 A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Electrical Panelboard Replacement Storage 142.2 A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2011 Electrical Panelboard Replacement Hallway At Cr126 A Deficiency has been corrected or addressed
Columbia Elementary School 2 Building 2010 Electrical Switchgear Replacement A Deficiency has been corrected or addressed
Columbia High School 3 Building 5020 Exterior Exterior Metal Door Repainting A Deficiency has been corrected or addressed
Columbia High School 1 Building 5010 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Columbia High School 1 Building 5011 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Columbia High School 1 Building 5011 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Columbia High School 1 Building 5012 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Columbia High School 1 Building 5013 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Columbia High School 1 Building 5014 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Columbia High School 1 Building 5015 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Columbia High School 1 Building 5016 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Columbia High School 1 Building 5020 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Columbia High School 1 Building 5010 Electrical Exposed Wiring / Conduit Repair A Deficiency has been corrected or addressed
Columbia High School 3 Building 5010 Roofing Roof Drain Cleaning Clogged A Deficiency has been corrected or addressed
Columbia High School 3 Building 5016 Roofing Roof Drain Cleaning Clogged A Deficiency has been corrected or addressed
Columbia High School 3 Building 5015 Electrical Canopy Lighting Replacement Damaged A Deficiency has been corrected or addressed
Columbia High School 3 Building 5012 Roofing Roof Drain Cleaning Clogged A Deficiency has been corrected or addressed
Columbia High School 3 Building 5013 Roofing Roof Drain Cleaning Clogged A Deficiency has been corrected or addressed
Columbia High School 3 Building 5014 Roofing Roof Drain Cleaning Clogged A Deficiency has been corrected or addressed
Columbia Middle School 3 Building 4010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing A Deficiency has been corrected or addressed
Columbia Middle School 3 Building 4010 Plumbing Emergency Eyewash Replacement A Deficiency has been corrected or addressed
Columbia Middle School 1 Building 4010 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Columbia Middle School 2 Building 4010 Exterior Brick Exterior Replacement (Bldg SF) A Deficiency has been corrected or addressed
Columbia Middle School 2 Building 4010 Mechanical Air Cooled Condenser Replacement A Deficiency has been corrected or addressed
Columbia Middle School 2 Building 4010 Mechanical Ductless Split System AC Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Columbia Middle School 2 Building 4010 Electrical Generator Replacement 80KW A Deficiency has been corrected or addressed
Columbia Middle School 2 Building 4010 Electrical Electrical Receptacle Repair Exposed Wiring In Classroom A Deficiency has been corrected or addressed
Columbia Middle School 3 Building 4010 Roofing Modified Covering Has Blisters That Should Be Repaired A Deficiency has been corrected or addressed
Columbia Middle School 3 Building 4010 Roofing Roof Drain Cleaning A Deficiency has been corrected or addressed
Whole Roof Needs To Be Replace. Old With
Coralwood Education 2 Building 2010 Roofing Modified Roof Covering Replacement A Deficiency has been corrected or addressed
Many Bubbles And Some Holes. Leaking.
Whole Roof Needs To Be Replaced. Roof Is
Coralwood Education 2 Building 2011 Roofing Modified Roof Covering Replacement Old With Many Bubbles And Some Holes. A Deficiency has been corrected or addressed
Leaking.
Coralwood Education 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Coralwood Education 3 Building 2010 Roofing Debris In Gutter Removal Leaves And Courtyard A Deficiency has been corrected or addressed
Coralwood Education 3 Building 2011 Roofing Debris In Gutter Removal Leaves And Back Of Building A Deficiency has been corrected or addressed
Coralwood Education 1 Building 2010 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Coralwood Education 3 Building 2010 Plumbing Gas Water Heater Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Cross Keys High School 1 Building 5010 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Cross Keys High School 1 Building 5010 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Cross Keys High School 1 Building 5010 Fire and Life Safety Emergency Lighting System Replacement A Deficiency has been corrected or addressed
Cross Keys High School 1 Building 5011 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
DeKalb Elementary School of the Arts 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Metal Roof Is Leaking In Four Places Above
Classroom Halls Where Roof Bumps-Out.
DeKalb Elementary School of the Arts 2 Building 4010 Roofing Metal Roof Architectural Roof Covering Replacement A Deficiency has been corrected or addressed
Replace Metal Roof At 4 Bump-Outs That
Leak.
Roof Over Whole School Is Bad And Leaking.
Replace All Flat (R15) Roofs Over Whole
DeKalb Elementary School of the Arts 2 Building 4010 Roofing Modified Roof Covering Replacement A Deficiency has been corrected or addressed
School. 21 Years Old With Many Bubbles And
Leaks.
Repair Gutter At Front Entrance Canopy That
DeKalb Elementary School of the Arts 2 Building 4010 Roofing Gutter Joint Repair A Deficiency has been corrected or addressed
Is Leaking 2 Locations.
7 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Replace Gym Metal Roof Gutter On Both
DeKalb Elementary School of the Arts 3 Building 4010 Roofing Gutter Replacement Sides. Leaking And Bent, Joints Leaking, A Deficiency has been corrected or addressed
Rusting.
DeKalb Elementary School of the Arts 3 Building 4010 Roofing Metal Downspout Replacement Gym Gutter. A Deficiency has been corrected or addressed
Paint Peeling And Some Doors Rusting.
Courtyards And Back Of School. Interior
Courtyard Doors Leak When It Rains. The
DeKalb Elementary School of the Arts 3 Building 4010 Exterior Exterior Metal Door Repainting A Deficiency has been corrected or addressed
Windows Next To The Doors Also Leak. Add
Awnings Over Doors In Courtyards And
Windows Next To Doors.
DeKalb High of Technology, South Campus 1 Building 5010 Fire and Life Safety Fire Sprinkler System Replacement (SF Basis) Auto Labs A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 1 Building 5010 Fire and Life Safety Emergency Exit Signage Replacement Old A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 1 Building 5010 Fire and Life Safety Fire Alarm Replacement Old A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 3 Site Asphalt Driveway Replacement Beyond Useful Life - Cracked A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 3 Building 5010 Interior Entry Door Does Not Have Power Assist Device Missing At Main Entrance A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 3 Building 5010 Interior Existing Toilet Stall Does Not Meet Minimum ADA RequirementsBoys And Girls (One Each) A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 3 Building 5010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsMissing(Modify Full) A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Electrical Electrical Transformer Replacement Old, Elec Upper A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Electrical Electrical Transformer Replacement Old, Boiler A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Electrical Electrical Transformer Replacement Old, Elec A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 3 Building 5010 Electrical Interior Power Wiring Replacement Old A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Electrical Motor Control Center Replacement Old, Boiler A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Electrical Motor Control Center Replacement Old, Elec Lower A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Electrical Panelboard Replacement Old, Elec A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Electrical Panelboard Replacement Old A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Electrical Panelboard Replacement Old A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Electrical Panelboard Replacement Old A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Electrical Panelboard Replacement Old A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Electrical Panelboard Replacement Old A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Electrical Panelboard Replacement Old, Throughout A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Electrical Switchgear Replacement Old, Elec Lower A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Electrical Switchgear Replacement Old, Elec Upper A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Mechanical Air Handler HVAC Component Replacement Boiler Room A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Mechanical Ductwork Replacement (SF Basis) Throughout A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Mechanical Gas Piping Replacement (SF Basis) Throughout A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Mechanical Infrared Electric Radiant Heater Replacement Stairs A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 3 Building 5010 Mechanical Large Diameter Exhausts/Hoods Replacement Roof A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Throughout A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Mechanical Package DX Unit Replacement 115 Elec Lab, 116 Class A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Mechanical Package Roof Top Unit Replacement Roof A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Mechanical Package Roof Top Unit Replacement Roof A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Mechanical Steam/Hot Water Radiant Heater Replacement Throughout A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 2 Building 5010 Mechanical Steam/HW Unit Heater Replacement Mech Room A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 3 Building 5010 Mechanical Testing And Balancing Throughout A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 3 Building 5010 Exterior Brick Exterior Repair Cracks And Voids - Replace Expansion Joint A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 3 Building 5010 Roofing Membrane Flashing At Parapet (>2') Repair Cracked Sealant A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 3 Building 5010 Roofing Metal Downspout Replacement Reattach A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 3 Building 5010 Plumbing Gas Water Heater Replacement Mech Room A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 3 Building 5010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life
Throughout A Deficiency has been corrected or addressed
DeKalb High of Technology, South Campus 3 Building 5010 Plumbing Sanitary Sewer Piping Replacement Throughout A Deficiency has been corrected or addressed
Doraville Administrative 3 Building 8010 Roofing Awning Or Canopy Metal Roofing System Replacement Damaged A Deficiency has been corrected or addressed
Doraville Administrative 3 Site Storm Drain Cover Installation Clogged Storm Water Drain A Deficiency has been corrected or addressed
Doraville Administrative 3 Building 8010 Plumbing Toilet Plumbing Fixture Repair Leaking Toilets A Deficiency has been corrected or addressed
Doraville United Elementary School 3 Building 2010 Plumbing Condensate Drain Repair Broken Roof Above Office A Deficiency has been corrected or addressed
Dresden Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement Old, Entire Building A Deficiency has been corrected or addressed
Dresden Elementary School 1 Building 2011 Fire and Life Safety Fire Alarm Is Missing Old, Entire Building A Deficiency has been corrected or addressed
Dresden Elementary School 1 Building 2012 Fire and Life Safety Fire Alarm Is Missing Old, Entire Building A Deficiency has been corrected or addressed
Dresden Elementary School 1 Building 2013 Fire and Life Safety Fire Alarm Is Missing Old, Entire Building A Deficiency has been corrected or addressed
Druid Hills High School 1 Building 5030 Fire and Life Safety Emergency Exit Signage Replacement Old, Entire Building A Deficiency has been corrected or addressed
8 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Druid Hills High School 3 Building 5011 Exterior Brick Exterior Repointing Cracked A Deficiency has been corrected or addressed
Druid Hills High School 3 Building 5040 Roofing Membrane Flashing At Parapet (>2') Repair Cracked Sealant At Collector Box Openings. A Deficiency has been corrected or addressed
Druid Hills High School 3 Building 5020 Plumbing Sanitary Sewer Piping Replacement Throughout A Deficiency has been corrected or addressed
Druid Hills High School 3 Building 5020 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life
Throughout A Deficiency has been corrected or addressed
Druid Hills High School 2 Building 5021 Mechanical Gas Piping Replacement (SF Basis) Throughout A Deficiency has been corrected or addressed
Druid Hills High School 3 Building 5021 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life
Throughout A Deficiency has been corrected or addressed
Druid Hills High School 3 Building 5021 Plumbing Sanitary Sewer Piping Replacement Throughout A Deficiency has been corrected or addressed
Druid Hills High School 3 Building 5021 Electrical Interior Power Wiring Replacement Old, Throughout Building A Deficiency has been corrected or addressed
Druid Hills High School 3 Building 5030 Plumbing Sanitary Sewer Piping Replacement Throughout A Deficiency has been corrected or addressed
Druid Hills High School 2 Building 5030 Electrical Switchgear Replacement Old, Elec Room A Deficiency has been corrected or addressed
Druid Hills High School 3 Building 5030 Electrical Interior Power Wiring Replacement Old, Entire Building A Deficiency has been corrected or addressed
Druid Hills High School 2 Building 5030 Electrical Electrical Transformer Replacement Old, Elec Room A Deficiency has been corrected or addressed
Druid Hills High School 2 Building 5030 Electrical Panelboard Replacement Old, Elec Room A Deficiency has been corrected or addressed
Druid Hills High School 3 Building 5030 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life
Throughout A Deficiency has been corrected or addressed
Druid Hills High School 2 Building 5010 Mechanical Gas Piping Replacement (SF Basis) Throughout A Deficiency has been corrected or addressed
Druid Hills High School 3 Building 5010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life
Throughout A Deficiency has been corrected or addressed
Druid Hills High School 3 Building 5010 Plumbing Sanitary Sewer Piping Replacement Throughout A Deficiency has been corrected or addressed
Druid Hills High School 2 Building 5011 Mechanical Gas Piping Replacement (SF Basis) Throughout A Deficiency has been corrected or addressed
Druid Hills High School 3 Building 5011 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life
Throughout A Deficiency has been corrected or addressed
Druid Hills High School 3 Building 5011 Plumbing Sanitary Sewer Piping Replacement Throughout A Deficiency has been corrected or addressed
Druid Hills High School 2 Building 5020 Electrical Electrical Transformer Replacement Old, Elec Room A Deficiency has been corrected or addressed
Druid Hills High School 2 Building 5020 Electrical Distribution Panel Replacement Old, Elec Room A Deficiency has been corrected or addressed
Druid Hills High School 2 Building 5020 Electrical Panelboard Replacement Old, Elec Room A Deficiency has been corrected or addressed
Druid Hills High School 2 Building 5020 Electrical Panelboard Replacement Old, Elec Room A Deficiency has been corrected or addressed
Druid Hills Middle School 3 Building 4010 Plumbing Toilet Plumbing Fixture Repair Leaking A Deficiency has been corrected or addressed
Druid Hills Middle School 1 Building 4010 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 1 Building 4010 Fire and Life Safety Security Alarm Camera Replacement A Deficiency has been corrected or addressed
Druid Hills Middle School 1 Building 4011 Fire and Life Safety Wall Pack Lighting Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 1 Building 4011 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 1 Building 4011 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 1 Building 4011 Electrical Exposed Wiring / Conduit Repair Exposed Wiring A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4010 Electrical Electrical Transformer Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4010 Electrical Electrical Transformer Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4010 Electrical Electrical Transformer Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4010 Electrical Electrical Transformer Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4011 Electrical Switchgear Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 3 Building 4011 Electrical Interior Power Wiring Replacement A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4011 Electrical Electrical Transformer Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4011 Electrical Electrical Transformer Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4011 Electrical Electrical Transformer Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4011 Electrical Motor Control Center Replacement A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4011 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4011 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4011 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4011 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4011 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4011 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
9 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Druid Hills Middle School 2 Building 4011 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4011 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4011 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4011 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 3 Building 4010 Electrical Interior Power Wiring Replacement Old Wiring A Deficiency has been corrected or addressed
Druid Hills Middle School 3 Building 4010 Plumbing Condensate Drain Repair Insulate Condensate Drains A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4010 Roofing Skylight Replacement Leaking Skylights- Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4011 Roofing Skylight Replacement Leaking Skylights A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4010 Roofing Built-up Roofing Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4011 Roofing Built-up Roofing Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 3 Building 4011 Conveyances Platform Lift Needed for Access Missing A Deficiency has been corrected or addressed
Druid Hills Middle School 2 Building 4010 Electrical Generator Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 3 Building 4010 Plumbing Shower Replacement Shower Heads And Valves A Deficiency has been corrected or addressed
Druid Hills Middle School 3 Building 4010 Plumbing Toilet Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Druid Hills Middle School 3 Building 4010 Plumbing Urinal Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Dunaire Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Dunaire Elementary School 1 Building 2010 Fire and Life Safety Fire Sprinkler System Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Dunaire Elementary School 1 Building 2010 Fire and Life Safety Wall Pack Lighting Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Dunaire Elementary School 1 Building 2010 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Dunaire Elementary School 1 Building 2010 Fire and Life Safety Emergency Lighting System Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Dunaire Elementary School 1 Building 2010 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Dunaire Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Panel Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Dunaire Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Dunaire Elementary School 1 Building 2011 Fire and Life Safety Fire Sprinkler System Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Dunaire Elementary School 1 Building 2011 Fire and Life Safety Emergency Lighting System Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Dunaire Elementary School 1 Building 2011 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Dunaire Elementary School 1 Building 2011 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Dunaire Elementary School 1 Building 2012 Fire and Life Safety Fire Sprinkler System Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Dunaire Elementary School 1 Building 2012 Fire and Life Safety Emergency Lighting System Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Dunaire Elementary School 1 Building 2012 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Dunaire Elementary School 1 Building 2012 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Dunaire Elementary School 1 Building 2020 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Dunaire Elementary School 1 Building 2020 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Dunaire Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Debris And Trees Growing A Deficiency has been corrected or addressed
Dunaire Elementary School 3 Building 2010 Roofing Roof Drain Cleaning Clogged A Deficiency has been corrected or addressed
Dunaire Elementary School 3 Building 2011 Roofing Roof Drain Cleaning Clogged A Deficiency has been corrected or addressed
Dunaire Elementary School 3 Building 2012 Roofing Roof Drain Cleaning Clogged A Deficiency has been corrected or addressed
Dunwoody Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Storefront System At All Egress Stairwell
Curtain Walls Presents Paint Bubbling At Sills
Dunwoody Elementary School 2 Building 2010 Exterior Storefront / Curtain Wall Repair A Deficiency has been corrected or addressed
Above Exit Doors. Likely Water Damage And
Water Infiltration.
Dunwoody Elementary School 1 Building 2010 Fire and Life Safety Wall Pack Lighting Replacement 1148 Mech Room A Deficiency has been corrected or addressed
Dunwoody Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Actuator Repair Card Reader Repair Per Staff A Deficiency has been corrected or addressed
Dunwoody Elementary School 3 Building 2010 Roofing Debris In Gutter Removal Some Gutters On South Side A Deficiency has been corrected or addressed
Dunwoody Elementary School 3 Building 2010 Electrical Electrical Receptacle Replacement 1348 Room A Deficiency has been corrected or addressed
System Is Non-Functional. Pa Panel Gives
Dunwoody High School 1 Building 5010 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Constant Errors And Alarms
Dunwoody High School 1 Building 5011 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Fire Alarm System Is Not Operational.
Dunwoody High School 1 Building 5011 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Replace
Dunwoody High School 1 Building 5012 Fire and Life Safety Fire Alarm Replacement System Is Old And Barely Functional. Replace A Deficiency has been corrected or addressed
Dunwoody High School 1 Building 5013 Fire and Life Safety Fire Alarm Replacement Fire Alarm System In Not Functioning A Deficiency has been corrected or addressed
Dunwoody High School 1 Building 5011 Fire and Life Safety Security Alarm Camera Is Missing A Deficiency has been corrected or addressed
Dunwoody High School 3 Building 5011 Electrical Electrical Receptacle Replacement A Deficiency has been corrected or addressed
Dunwoody High School 3 Building 5013 Roofing Roof Drain Cleaning A Deficiency has been corrected or addressed
Dunwoody High School 1 Building 5012 Structural Evidence of Structural Deficiency A Deficiency has been corrected or addressed
10 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Structural Damage Present At Multiple
Locations. CMU Wall Outside Of 2404, Brick
Dunwoody High School 1 Building 5012 Structural Evidence of Structural Deficiency Column Outside Room 2304. Structural A Deficiency has been corrected or addressed
Damage Present To Exposed Metal Beam In
The Gym
Recurring Cracking Above The Entrance To
Dunwoody High School 1 Building 5013 Structural Evidence of Structural Deficiency The Auditorium. Structural Study A Deficiency has been corrected or addressed
Recommended
Eagle Woods Academy 1 Building 8010 Fire and Life Safety Wall Pack Lighting Replacement Multiple Locations A Deficiency has been corrected or addressed
Eagle Woods Academy 1 Building 8010 Fire and Life Safety Emergency Exit Signage Replacement Library, Old Sign A Deficiency has been corrected or addressed
Eagle Woods Academy 1 Building 8020 Fire and Life Safety Wall Pack Lighting Replacement All Lights A Deficiency has been corrected or addressed
Eagle Woods Academy 1 Building 8030 Fire and Life Safety Fire Alarm Is Missing A Deficiency has been corrected or addressed
Eagle Woods Academy 1 Building 8010 Fire and Life Safety Security Alarm Camera Is Missing Corridor A Deficiency has been corrected or addressed
Eagle Woods Academy 1 Building 8030 Fire and Life Safety Security Alarm Is Missing A Deficiency has been corrected or addressed
Early Learning Academy 3 Building 2010 Roofing Debris In Gutter Removal Debris A Deficiency has been corrected or addressed
Early Learning Academy 3 Building 2011 Roofing Debris In Gutter Removal Debris A Deficiency has been corrected or addressed
Early Learning Academy 3 Building 2020 Roofing Debris In Gutter Removal Debris And Plants A Deficiency has been corrected or addressed
Early Learning Academy 3 Building 2020 Roofing Roof Drain Cleaning Clogged A Deficiency has been corrected or addressed
Early Learning Academy 1 Building 2010 Fire and Life Safety Wall Pack Lighting Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 1 Building 2010 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 1 Building 2010 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 1 Building 2011 Fire and Life Safety Wall Pack Lighting Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 1 Building 2011 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Early Learning Academy 1 Building 2011 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 1 Building 2012 Fire and Life Safety Wall Pack Lighting Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 1 Building 2012 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 1 Building 2012 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 1 Building 2020 Fire and Life Safety Wall Pack Lighting Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 1 Building 2020 Fire and Life Safety Emergency Exit Signage Repair Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 1 Building 2020 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Stage Box Has Exposed Wiring Inside. Wires
Early Learning Academy 1 Building 2010 Electrical Exposed Wiring / Conduit Repair Are Not Supported On The Second Box Is Not A Deficiency has been corrected or addressed
Locked
Early Learning Academy 2 Building 2012 Electrical Electrical Receptacle Repair Missing Cover Plate A Deficiency has been corrected or addressed
Early Learning Academy 3 Building 2012 Roofing Debris In Gutter Removal Debris A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2010 Exterior Storefront/Curtain Wall Replacement (Bldg SF) Infill Panel Damaged A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2010 Mechanical Gas Piping Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2010 Mechanical Boiler Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2010 Mechanical Steam Condensate Receiver Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 3 Building 2010 Mechanical Circulation Pump Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2010 Mechanical Exterior Metal Cooling Tower Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2010 Mechanical Air Cooled Condenser Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2010 Mechanical Ductless Split System AC Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 3 Building 2010 Mechanical Testing And Balancing A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2010 Mechanical Ductwork Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2010 Mechanical Package Roof Top Unit Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2010 Mechanical Package Roof Top Unit Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 3 Building 2010 Mechanical Large Diameter Exhausts/Hoods Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2011 Mechanical Gas Piping Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2011 Mechanical Package DX Unit Replacement Beyond Useful Life 2 Ton(3) A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2011 Mechanical Package DX Unit Replacement Beyond Useful Life Actual Is 4Ton(12) A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2011 Mechanical Ductwork Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2011 Mechanical Package Roof Top Unit Replacement Beyond Useful Life 7.5 Tons (3Ea) A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2012 Mechanical Air Cooled Condenser Replacement Beyond Useful Life 1.5 Tons A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2012 Mechanical Ductless Split System AC Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2012 Mechanical Package DX Unit Replacement Beyond Useful Life 4 Tons (6Ea) A Deficiency has been corrected or addressed
Early Learning Academy 3 Building 2012 Mechanical Testing And Balancing Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2012 Mechanical Package Roof Top Unit Replacement Beyond Useful Life 7.5 Tons A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2011 Electrical Electrical Transformer Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 3 Building 2010 Electrical Interior Power Wiring Replacement Beyond Useful Life A Deficiency has been corrected or addressed
11 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Early Learning Academy 3 Building 2011 Electrical Interior Power Wiring Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2011 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2011 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2011 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2010 Electrical Switchgear Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2012 Roofing Modified Roof Covering Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 3 Building 2010 Plumbing Gas Water Heater Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 3 Building 2010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Useful Life
Beyond A Deficiency has been corrected or addressed
Early Learning Academy 3 Building 2011 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Useful Life
Beyond A Deficiency has been corrected or addressed
Early Learning Academy 3 Building 2010 Plumbing Sanitary Sewer Piping Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 3 Building 2011 Plumbing Sanitary Sewer Piping Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2011 Plumbing Water Heater Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2012 Plumbing Water Heater Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 2 Building 2020 Plumbing Water Heater Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 3 Building 2010 Electrical Lighting Fixtures Replacement Beyond Useful Life - Old T8 Lamps A Deficiency has been corrected or addressed
Early Learning Academy 3 Building 2011 Electrical Lighting Fixtures Replacement Beyond Useful Life- Old T8 Lamps A Deficiency has been corrected or addressed
Early Learning Academy 3 Building 2012 Electrical Lighting Fixtures Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Early Learning Academy 3 Building 2020 Electrical Lighting Fixtures Replacement Beyond Useful Life - Old T8 Lamps A Deficiency has been corrected or addressed
East Campus #1 DeKalb Alternative 2 Building 8010 Roofing Modified Roof Covering Replacement A Deficiency has been corrected or addressed
East Campus #1 DeKalb Alternative 2 Building 8020 Roofing Modified Roof Covering Replacement A Deficiency has been corrected or addressed
East Campus #1 DeKalb Alternative 3 Site Asphalt Driveway Replacement Majority Of Paving A Deficiency has been corrected or addressed
East Campus #1 DeKalb Alternative 3 Building 8010 Interior Interior Door Replacement Room 5831.21, Door Falling A Deficiency has been corrected or addressed
East Campus #1 DeKalb Alternative 2 Building 8010 Exterior Overhead Door Replacement South Side Of Building A Deficiency has been corrected or addressed
East Campus #1 DeKalb Alternative 3 Building 8010 Roofing Debris In Gutter Removal West Side Of Building A Deficiency has been corrected or addressed
East Campus #1 DeKalb Alternative 2 Building 8020 Roofing Gutter Joint Repair A Deficiency has been corrected or addressed
East Campus #1 DeKalb Alternative 3 Building 8020 Roofing Metal Downspout Replacement A Deficiency has been corrected or addressed
Edward L. Bouie, Sr. Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Edward L. Bouie, Sr. Elementary School 1 Building 2010 Fire and Life Safety Wall Pack Lighting Replacement Gym A Deficiency has been corrected or addressed
Edward L. Bouie, Sr. Elementary School 1 Building 2010 Fire and Life Safety Emergency Exit Signage Replacement Multiple Locations A Deficiency has been corrected or addressed
Edward L. Bouie, Sr. Elementary School 3 Building 2010 Roofing Debris In Gutter Removal East Side Of Room 504, Debris In Gutter A Deficiency has been corrected or addressed
Edward L. Bouie, Sr. Elementary School 2 Building 2010 Roofing Gutter Joint Repair Gutter At Room 504, Leaking. A Deficiency has been corrected or addressed
Broken Window Frames, Doors Dragging On
Edward L. Bouie, Sr. Elementary School 3 Building 2010 Interior Interior Door Replacement A Deficiency has been corrected or addressed
Floor. Rooms 169, 167, 175, 183, 254.2
Edward L. Bouie, Sr. Elementary School 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding Above Room 253 A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Mechanical Boiler Replacement Beyond Useful Life - 1355 Mbh A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Mechanical Heat Exchanger Replacement Beyond Useful Life - 184 GPM A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Mechanical Ductless Split System AC Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Mechanical Thru Wall AC Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Mechanical Ductwork Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Mechanical HVAC VAV Box Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2011 Mechanical Gas Piping Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2011 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2011 Mechanical Ductwork Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2011 Mechanical HVAC VAV Box Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2020 Mechanical Gas Unit Heater Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2020 Mechanical Thru Wall AC Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 1 Building 2010 Fire and Life Safety Fire Sprinkler System Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 1 Building 2010 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 1 Building 2011 Fire and Life Safety Fire Sprinkler System Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 1 Building 2011 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 1 Building 2011 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 1 Building 2020 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 1 Building 2020 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
12 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Clogged. Standing Water At Clogged Roof
Eldridge L. Miller Elementary School 3 Building 2010 Roofing Roof Drain Cleaning A Deficiency has been corrected or addressed
Drains.
Eldridge L. Miller Elementary School 3 Building 2011 Roofing Roof Drain Cleaning Clogged And Multi. 100 A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility A Deficiency has been corrected or addressed
Roofing Around Hvac Supports. Support
Eldridge L. Miller Elementary School 2 Building 2010 Roofing Membrane Flashings At Equipment Curb Repair Frame Rusting And Damaging Flashing And A Deficiency has been corrected or addressed
Causing Leaks (8 Locations)
Eldridge L. Miller Elementary School 3 Building 2010 Mechanical Circulation Pump Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 3 Building 2010 Mechanical Large Diameter Exhausts/Hoods Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 3 Building 2010 Mechanical Small Diameter Exhausts/Hoods Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 3 Building 2011 Mechanical Large Diameter Exhausts/Hoods Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 3 Building 2020 Plumbing Gas Water Heater Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 3 Building 2020 Plumbing Urinal Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 3 Building 2020 Mechanical Testing And Balancing A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 3 Building 2010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
No Ramp At Stage A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 3 Building 2011 Electrical Interior Power Wiring Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Electrical Motor Control Center Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2011 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 2 Building 2011 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 3 Building 2011 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Useful Life
Beyond A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 3 Building 2010 Plumbing Toilet Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 3 Building 2011 Plumbing Toilet Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 3 Building 2020 Plumbing Toilet Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 3 Building 2010 Plumbing Urinal Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 3 Building 2011 Plumbing Urinal Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 3 Site Asphalt Walks Replacement Old, Cracked A Deficiency has been corrected or addressed
Eldridge L. Miller Elementary School 3 Site Concrete Walks Replacement Cracked A Deficiency has been corrected or addressed
Evansdale Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Evansdale Elementary School 3 Building 2010 Roofing Roof Drain Cleaning Debris And Clogged A Deficiency has been corrected or addressed
Evansdale Elementary School 3 Building 2011 Roofing Roof Drain Cleaning Debris And Clogged A Deficiency has been corrected or addressed
Evansdale Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Debris A Deficiency has been corrected or addressed
Evansdale Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Evansdale Elementary School 1 Building 2011 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Evansdale Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Evansdale Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Evansdale Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Evansdale Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Evansdale Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Evansdale Elementary School 3 Building 2011 Electrical Interior Power Wiring Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Fairington Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
13 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Fernbank Elementary School 3 Building 2010 Roofing Roof Drain Cleaning Above Admin Area A Deficiency has been corrected or addressed
Fernbank Elementary School 1 Building 2010 Fire and Life Safety Security Alarm Camera Replacement Camera Not Working A Deficiency has been corrected or addressed
Fix Metal Flashing At Gable Roof Near The
Fernbank Elementary School 3 Building 2010 Roofing Membrane Flashing At Parapet (>2') Repair Main Office And Flashing Above Media A Deficiency has been corrected or addressed
Center And Library
Fernbank Science Center 3 Building 8010 Roofing Roof Drain Cleaning West Roof A Deficiency has been corrected or addressed
Fernbank Science Center 3 Building 8020 Roofing Debris In Gutter Removal Clogged A Deficiency has been corrected or addressed
Fernbank Science Center 3 Building 8010 Exterior Exterior Metal Door Repainting All Doors. A Deficiency has been corrected or addressed
Fernbank Science Center 3 Building 8010 Exterior Wood Exterior Door Repainting All Doors. A Deficiency has been corrected or addressed
Fernbank Science Center 2 Building 8020 Roofing Gutter Joint Repair Damaged A Deficiency has been corrected or addressed
Fernbank Science Center 3 Building 8010 Mechanical Large Diameter Exhausts/Hoods Replacement All Roof Exhaust Fans A Deficiency has been corrected or addressed
Flat Rock Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Flat Rock Elementary School 1 Building 2010 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Flat Rock Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Flat Rock Elementary School 1 Building 2010 Structural Evidence of Structural Deficiency Structure For Cooling Tower A Deficiency has been corrected or addressed
Flat Shoals Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Flat Shoals Elementary School 3 Building 2040 Roofing Debris In Gutter Removal Leaf Build-Up A Deficiency has been corrected or addressed
Flat Shoals Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Flat Shoals Elementary School 1 Building 2011 Fire and Life Safety Fire Sprinkler System Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Flat Shoals Elementary School 1 Building 2011 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Flat Shoals Elementary School 1 Building 2020 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Flat Shoals Elementary School 1 Building 2020 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Flat Shoals Elementary School 1 Building 2030 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Flat Shoals Elementary School 1 Building 2030 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Some Of The Parking Lots Have No Lighting.
Add 2 Light Poles In The Right Lot, 2 In The
Flat Shoals Elementary School 3 Electrical Area Lighting Installation A Deficiency has been corrected or addressed
Left Lot, 2 In The Back Lot And 1 Between
Buildings. 2020 And 2030
Flat Shoals Elementary School 3 Building 2010 Roofing Debris In Gutter Removal Leaf Build-Up A Deficiency has been corrected or addressed
Beyond Useful Life - Many Blisters. Replace
Freedom Middle School 2 Building 4010 Roofing Modified Roof Covering Replacement A Deficiency has been corrected or addressed
Roof
Freedom Middle School 3 Building 4010 Roofing Roof Drain Cleaning Back At Gym A Deficiency has been corrected or addressed
Green Forrest Drive 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Green Forrest Drive 1 Building 2010 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Green Forrest Drive 1 Building 2010 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Green Forrest Drive 1 Building 2010 Fire and Life Safety Security Alarm Replacement A Deficiency has been corrected or addressed
Green Forrest Drive 1 Building 2010 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Green Forrest Drive 1 Building 2011 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Green Forrest Drive 1 Building 2011 Fire and Life Safety Emergency Exit Signage Replacement Not Working A Deficiency has been corrected or addressed
Green Forrest Drive 1 Building 2011 Fire and Life Safety Security Alarm Replacement A Deficiency has been corrected or addressed
Green Forrest Drive 1 Building 2011 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Green Forrest Drive 1 Building 2012 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Green Forrest Drive 1 Building 2012 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Green Forrest Drive 1 Building 2012 Fire and Life Safety Security Alarm Replacement A Deficiency has been corrected or addressed
Green Forrest Drive 1 Building 2012 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Green Forrest Drive 1 Building 2020 Fire and Life Safety Security Alarm Replacement A Deficiency has been corrected or addressed
Green Forrest Drive 1 Building 2020 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Replace System. Not Working, Acc. To
Hallford, James R. Stadium 1 Building 8010 Fire and Life Safety Security Alarm Replacement A Deficiency has been corrected or addressed
Building Custodian.
Hallford, James R. Stadium 1 Building 8010 Fire and Life Safety Fire Alarm Is Missing A Deficiency has been corrected or addressed
Hallford, James R. Stadium 1 Building 8020 Fire and Life Safety Fire Alarm Is Missing A Deficiency has been corrected or addressed
Hallford, James R. Stadium 1 Building 8030 Fire and Life Safety Fire Alarm Is Missing A Deficiency has been corrected or addressed
Hallford, James R. Stadium 1 Building 8020 Fire and Life Safety Security Alarm Is Missing A Deficiency has been corrected or addressed
Hallford, James R. Stadium 1 Building 8020 Fire and Life Safety Security Alarm Camera Is Missing Field House, Need Camera A Deficiency has been corrected or addressed
Hallford, James R. Stadium 1 Building 8030 Fire and Life Safety Security Alarm Is Missing A Deficiency has been corrected or addressed
Replace Potholes And Damaged Asphalt,
Hambrick Elementary School 3 Site Asphalt Driveway Replacement A Deficiency has been corrected or addressed
Asphalt And Curb Near Fire Hydrant
Hambrick Elementary School 3 Building 2010 Roofing Debris In Gutter Removal Leaf Debris A Deficiency has been corrected or addressed
Hambrick Elementary School 3 Building 2011 Roofing Debris In Gutter Removal Leaf Debris A Deficiency has been corrected or addressed
14 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Hambrick Elementary School 3 Building 2012 Roofing Debris In Gutter Removal Leaf Debris A Deficiency has been corrected or addressed
Hambrick Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Leaf Debris A Deficiency has been corrected or addressed
Hatton Dr Warehouse 1 Building 8010 Fire and Life Safety Wall Pack Lighting Replacement Multiple Locations A Deficiency has been corrected or addressed
Hatton Dr Warehouse 1 Building 8010 Fire and Life Safety Emergency Exit Signage Replacement Multiple Locations A Deficiency has been corrected or addressed
Hatton Dr Warehouse 2 Building 8010 Electrical Distribution Panel Replacement 1000 Amps - Old A Deficiency has been corrected or addressed
Hawthorne Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Hawthorne Elementary School 3 Building 2020 Interior Athletic Sport Flooring Replacement Peeling And Bubbling A Deficiency has been corrected or addressed
Hawthorne Elementary School 1 Building 2010 Fire and Life Safety Wall Pack Lighting Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Hawthorne Elementary School 1 Building 2010 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Hawthorne Elementary School 1 Building 2010 Fire and Life Safety Security Alarm Camera Replacement Not Working A Deficiency has been corrected or addressed
Hawthorne Elementary School 1 Building 2011 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Hawthorne Elementary School 1 Building 2012 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Hawthorne Elementary School 1 Building 2020 Fire and Life Safety Wall Pack Lighting Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Hawthorne Elementary School 1 Building 2020 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Hawthorne Elementary School 2 Building 2012 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Hawthorne Elementary School 3 Building 2020 Exterior Exterior Metal Door Repainting Peeling A Deficiency has been corrected or addressed
Hawthorne Elementary School 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding A Deficiency has been corrected or addressed
Hawthorne Elementary School 3 Building 2010 Plumbing Sanitary Sewer Piping Replacement A Deficiency has been corrected or addressed
Hawthorne Elementary School 3 Building 2010 Mechanical Expansion Tank Replacement 55 Gallon A Deficiency has been corrected or addressed
Hawthorne Elementary School 2 Building 2010 Mechanical Boiler HVAC Component Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Hawthorne Elementary School 2 Building 2010 Mechanical Heat Exchanger Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Hawthorne Elementary School 3 Building 2010 Mechanical Circulation Pump Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Hawthorne Elementary School 2 Building 2010 Mechanical Exterior Metal Cooling Tower Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Hawthorne Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life - 1.5 Ton A Deficiency has been corrected or addressed
Hawthorne Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life - 2 Ton A Deficiency has been corrected or addressed
Hawthorne Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Hawthorne Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life - 4 Ton A Deficiency has been corrected or addressed
Hawthorne Elementary School 2 Building 2010 Mechanical Air Handler HVAC Component Replacement Beyond Useful Life - 6000 Cfm A Deficiency has been corrected or addressed
Hawthorne Elementary School 3 Building 2010 Mechanical Large Diameter Exhausts/Hoods Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Hawthorne Elementary School 3 Building 2010 Mechanical Small Diameter Exhausts/Hoods Replacement Box Fan Supported Overhead A Deficiency has been corrected or addressed
Hawthorne Elementary School 2 Building 2011 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Hawthorne Elementary School 3 Building 2012 Plumbing Sanitary Sewer Piping Replacement A Deficiency has been corrected or addressed
Hawthorne Elementary School 2 Building 2012 Mechanical Electric Unit Heater Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Hawthorne Elementary School 2 Building 2012 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Hawthorne Elementary School 2 Building 2012 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Hawthorne Elementary School 2 Building 2012 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Hawthorne Elementary School 3 Building 2012 Mechanical Large Diameter Exhausts/Hoods Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Replace Receptacle With Gfi Protector Device
Hawthorne Elementary School 3 Building 2012 Electrical Electrical Receptacle Replacement A Deficiency has been corrected or addressed
At Sink
Hawthorne Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Tree Debris A Deficiency has been corrected or addressed
Hawthorne Elementary School 2 Building 2020 Mechanical Electric Unit Heater Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Hawthorne Elementary School 2 Building 2020 Mechanical Thru Wall AC Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Middle School 3 Building 4010 Roofing Debris In Gutter Removal Clogged A Deficiency has been corrected or addressed
Roof Leaking When It Rains. Drains Above
Henderson Middle School 3 Building 4010 Roofing Roof Drain Cleaning This Area Are Blocked. Need To Clean Drains A Deficiency has been corrected or addressed
And Determine Cause Of Leaks.
Drains Clogged. Leaks Reported When It
Henderson Middle School 3 Building 4012 Roofing Roof Drain Cleaning Rains. Clean Drains And Investigate Roof Leak A Deficiency has been corrected or addressed
Sources.
Henderson Middle School 3 Building 4013 Roofing Debris In Gutter Removal Leaf Build Up A Deficiency has been corrected or addressed
Henderson Middle School 3 Building 4014 Roofing Debris In Gutter Removal Leaf Build-Up A Deficiency has been corrected or addressed
Henderson Middle School 3 Building 4011 Plumbing Emergency Eyewash Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Henderson Mill Elementary School 3 Building 2020 Roofing Debris In Gutter Removal A Deficiency has been corrected or addressed
Henderson Mill Elementary School 1 Building 2010 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 1 Building 2011 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 1 Building 2011 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 3 Building 2010 Exterior Brick Exterior Repointing Weathered A Deficiency has been corrected or addressed
15 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Concrete Spalling At Several Locations Down
Henderson Mill Elementary School 2 Building 2010 Exterior Concrete Pre-Cast Panel Replacement (Bldg SF) To The Rebar And Expansion Joint Sealant A Deficiency has been corrected or addressed
Needs Replacement
Built-Up Roofing Placed Over Existing
Henderson Mill Elementary School 2 Building 2010 Roofing Modified Roof Covering Replacement Modified Bitumen. Both Roofing Assemblies A Deficiency has been corrected or addressed
Needs Replacement.
Henderson Mill Elementary School 3 Building 2010 Roofing Gutter Replacement Beyond Useful Life Bent A Deficiency has been corrected or addressed
Henderson Mill Elementary School 3 Building 2010 Roofing Metal Downspout Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 2 Building 2010 Roofing Skylight Replacement Beyond Useful Life - Cracked A Deficiency has been corrected or addressed
Henderson Mill Elementary School 2 Building 2010 Mechanical Gas Piping Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 2 Building 2010 Plumbing Water Heater Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 2 Building 2010 Plumbing Water Heater Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 3 Building 2010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Useful Life
Beyond A Deficiency has been corrected or addressed
Henderson Mill Elementary School 3 Building 2010 Plumbing Sanitary Sewer Piping Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 3 Building 2010 Mechanical Circulation Pump Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 2 Building 2010 Mechanical Air Cooled Condenser Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 2 Building 2010 Mechanical Ductless Split System AC Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 3 Building 2010 Mechanical Testing And Balancing A Deficiency has been corrected or addressed
Henderson Mill Elementary School 3 Building 2010 Mechanical Kitchen Exhaust Hood Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 2 Building 2010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 2 Building 2010 Mechanical Ductwork Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 2 Building 2010 Mechanical Package Roof Top Unit Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 3 Building 2010 Mechanical Large Diameter Exhausts/Hoods Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 2 Building 2010 Electrical Switchgear Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 2 Building 2010 Electrical Motor Control Center Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 3 Building 2011 Exterior Brick Exterior Repointing Weathered A Deficiency has been corrected or addressed
Cracked Spalling At Several Locations Down
Henderson Mill Elementary School 2 Building 2011 Exterior Concrete Pre-Cast Panel Replacement (Bldg SF) A Deficiency has been corrected or addressed
To The Rebar
Henderson Mill Elementary School 2 Building 2011 Mechanical Gas Piping Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 3 Building 2011 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Useful Life
Beyond A Deficiency has been corrected or addressed
Henderson Mill Elementary School 3 Building 2011 Plumbing Sanitary Sewer Piping Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 2 Building 2011 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 3 Building 2011 Electrical Interior Power Wiring Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 2 Building 2011 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Gym Flooring Is Blistering And Delaminating
Henderson Mill Elementary School 3 Building 2020 Interior Athletic Sport Flooring Replacement A Deficiency has been corrected or addressed
Due To Underwater Water Infiltration.
Henderson Mill Elementary School 2 Building 2020 Plumbing Water Heater Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Gym Flooring Is Blistering And Delaminating
Due To Underwater Water Infiltration. The
Exterior CMU Wall Has Cracks Throughout
Henderson Mill Elementary School 3 Site Site Requires Civil/Drainage Study A Deficiency has been corrected or addressed
Due To Underground Water Infiltrations Part
Of The Study Needs To Determine Below Slab
Vapor Barrier Water Installed.
Henderson Mill Elementary School 3 Site Asphalt Driveway Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 3 Site Asphalt Walks Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Henderson Mill Elementary School 3 Site Concrete Walks Replacement Beyond Useful Life Cracked A Deficiency has been corrected or addressed
Henderson Mill Elementary School 3 Building 2010 Interior Access Is Not ADA Compliant Non-Compliant Hardware A Deficiency has been corrected or addressed
Henderson Mill Elementary School 3 Building 2010 Interior Entry Door Does Not Have Power Assist Device Main Door Exit A Deficiency has been corrected or addressed
Henderson Mill Elementary School 3 Building 2010 Conveyances Platform Lift Needed for Access Missing A Deficiency has been corrected or addressed
Henderson Mill Elementary School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsMissing
(ModifyLower
Full) Counter A Deficiency has been corrected or addressed
Henderson Mill Elementary School 3 Building 2020 Roofing Batt Insulation Under Metal Roof Deck Damaged, Mold And Ripped A Deficiency has been corrected or addressed
Hightower Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Need A Second Playground For Kindergarten
Hightower Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Students. Add One Playground.
Hightower Elementary School 2 Building 2010 Mechanical Electric Unit Heater Replacement Beyond Useful Life A Deficiency has been corrected or addressed
16 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Hightower Elementary School 3 Building 2010 Mechanical Testing And Balancing A Deficiency has been corrected or addressed
Hightower Elementary School 2 Building 2010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Beyond Useful Life A Deficiency has been corrected or addressed
Hightower Elementary School 3 Building 2010 Mechanical Large Diameter Exhausts/Hoods Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Hightower Elementary School 3 Building 2010 Mechanical Small Diameter Exhausts/Hoods Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Hightower Elementary School 3 Building 2011 Mechanical Testing And Balancing A Deficiency has been corrected or addressed
Hightower Elementary School 2 Building 2011 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Beyond Useful Life A Deficiency has been corrected or addressed
Hightower Elementary School 3 Building 2012 Mechanical Testing And Balancing A Deficiency has been corrected or addressed
Hightower Elementary School 2 Building 2012 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Beyond Useful Life A Deficiency has been corrected or addressed
Hightower Elementary School 3 Building 2013 Mechanical Testing And Balancing Beyond Useful Life A Deficiency has been corrected or addressed
Hightower Elementary School 3 Building 2020 Mechanical Testing And Balancing A Deficiency has been corrected or addressed
Hightower Elementary School 3 Building 2010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
No Ramp At Cafeteria Stage A Deficiency has been corrected or addressed
Huntley Hills Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Huntley Hills Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement Aged And Obsolete. A Deficiency has been corrected or addressed
Huntley Hills Elementary School 1 Building 2011 Fire and Life Safety Fire Alarm Replacement Aged And Obsolete. A Deficiency has been corrected or addressed
Huntley Hills Elementary School 1 Building 2012 Fire and Life Safety Security Alarm Replacement Aged And Obsolete. A Deficiency has been corrected or addressed
Idlewood Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Panel Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Idlewood Elementary School 1 Building 2011 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Idlewood Elementary School 1 Building 2012 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Idlewood Elementary School 1 Building 2020 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Idlewood Elementary School 1 Building 2020 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Idlewood Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Idlewood Elementary School 1 Building 2010 Fire and Life Safety Fire Sprinkler System Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Idlewood Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Idlewood Elementary School 1 Building 2011 Fire and Life Safety Fire Sprinkler System Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Idlewood Elementary School 1 Building 2011 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Idlewood Elementary School 1 Building 2012 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
International Student Center at Midway 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
International Student Center at Midway 2 Building 2012 Roofing Modified Roof Covering Replacement Beyond Useful Life A Deficiency has been corrected or addressed
International Student Center at Midway 1 Building 2010 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
International Student Center at Midway 1 Building 2010 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
International Student Center at Midway 1 Building 2012 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
International Student Center at Midway 1 Building 2020 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
International Student Center at Midway 1 Building 2011 Structural Evidence of Structural Deficiency A Deficiency has been corrected or addressed
International Student Center at Midway 3 Building 2010 Roofing Debris In Gutter Removal Leaf Build-Up A Deficiency has been corrected or addressed
International Student Center at Midway 3 Building 2010 Roofing Roof Drain Cleaning Leaf Build-Up A Deficiency has been corrected or addressed
International Student Center at Midway 3 Building 2011 Roofing Roof Drain Cleaning Leaf Build-Up A Deficiency has been corrected or addressed
International Student Center at Midway 3 Building 2012 Roofing Debris In Gutter Removal Leaf Build-Up A Deficiency has been corrected or addressed
International Student Center at Midway 2 Building 2012 Roofing Gutter Joint Repair Leaking A Deficiency has been corrected or addressed
International Student Center at Midway 3 Building 2020 Roofing Debris In Gutter Removal Leaf Build-Up A Deficiency has been corrected or addressed
John Lewis Elementary School 3 Building 2010 Exterior Brick Exterior Repair Birch Dripping Plan West Of Level 3 Exit Wall A Deficiency has been corrected or addressed
John Lewis Elementary School 3 Building 2010 Roofing Debris In Gutter Removal A Deficiency has been corrected or addressed
John Lewis Elementary School 3 Building 2010 Roofing Roof Drain Cleaning A Deficiency has been corrected or addressed
John Lewis Elementary School 2 Building 2010 Conveyances Elevator Cab And/Or Controls Repair Staff States Elevator Breaks Down Often. A Deficiency has been corrected or addressed
Jolly Elementary School 1 Building 2010 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Jolly Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Panel Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Jolly Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Jolly Elementary School 1 Building 2011 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Jolly Elementary School 1 Building 2011 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Jolly Elementary School 1 Building 2012 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Jolly Elementary School 1 Building 2012 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Jolly Elementary School 1 Building 2020 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Jolly Elementary School 1 Building 2020 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Jolly Elementary School 1 Building 2010 Fire and Life Safety Fire Sprinkler System Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Jolly Elementary School 1 Building 2011 Fire and Life Safety Fire Sprinkler System Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Zone 13 And Zone 19 Issue That Needs To Be
Kelley Lake Elementary School 1 Building 2010 Fire and Life Safety Security Alarm Replacement A Deficiency has been corrected or addressed
Resolved Immediately
17 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Beyond Useful Life - According To The
Building Maintenance Staff It Has A Lot Of
Kelley Lake Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Issues. The System Was Installed Before
2013. Replace The Whole System
Kelley Lake Elementary School 1 Building 2010 Fire and Life Safety Security Alarm Camera Replacement A Deficiency has been corrected or addressed
Fire Alarm System Needs To Be Replaced.
Kelley Lake Elementary School 1 Building 2011 Fire and Life Safety Fire Alarm Replacement According To Building Staff, It Has Lot Of A Deficiency has been corrected or addressed
Issues. The System Was Installed Before 2013
According To Building Staff It Has A Lot Of
Kelley Lake Elementary School 1 Building 2012 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Issues. It Was Installed Before 2013
According To Building Staff It Has A Lot Of
Kelley Lake Elementary School 1 Building 2020 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Issues The System Was Installed Before 2013
Kingsley Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Kingsley Elementary School 3 Building 2010 Roofing Roof Drain Cleaning Leaf Build-Up A Deficiency has been corrected or addressed
Kittredge Magnet 1 Building 2010 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Kittredge Magnet 1 Building 2011 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Kittredge Magnet 1 Building 2012 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Kittredge Magnet 1 Building 2020 Fire and Life Safety Emergency Exit Signage Replacement Entry Main A Deficiency has been corrected or addressed
Kittredge Magnet 1 Building 2020 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Lakeside High School 3 Building 5010 Mechanical Kitchen Air/Exhaust Installation A Deficiency has been corrected or addressed
Owner Stated All 112 Ccrv Cameras Were Not
Lakeside High School 1 Building 5010 Fire and Life Safety Security Alarm Replacement A Deficiency has been corrected or addressed
Working.
Lakeside High School 1 Building 5010 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Lakeside High School 1 Building 5011 Fire and Life Safety Security Alarm Replacement A Deficiency has been corrected or addressed
Lakeside High School 1 Building 5011 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Lakeside High School 1 Building 5012 Fire and Life Safety Security Alarm Replacement A Deficiency has been corrected or addressed
Lakeside High School 1 Building 5012 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Lakeside High School 1 Building 5013 Fire and Life Safety Security Alarm Replacement A Deficiency has been corrected or addressed
Lakeside High School 1 Building 5013 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Lakeside High School 1 Building 5014 Fire and Life Safety Security Alarm Replacement A Deficiency has been corrected or addressed
Lakeside High School 1 Building 5014 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Lakeside High School 1 Building 5015 Fire and Life Safety Security Alarm Replacement Building Is Served From Building 5010 A Deficiency has been corrected or addressed
Lakeside High School 1 Building 5015 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Damaged - High Gable Roof. Metal Gutter
Lakeside High School 3 Building 5012 Roofing Gutter Replacement A Deficiency has been corrected or addressed
Damaged And Install New Down Spouts.
Lakeside High School 3 Building 5012 Roofing Metal Downspout Replacement Install A Deficiency has been corrected or addressed
Lakeside High School 3 Building 5030 Exterior Exterior Metal Door Repainting Repaint A Deficiency has been corrected or addressed
Lakeside High School 3 Building 5015 Exterior Exterior Metal Door Repainting Repaint Doors A Deficiency has been corrected or addressed
Lakeside High School 3 Building 5015 Exterior Exterior Metal Door Repainting Repaint Doors A Deficiency has been corrected or addressed
Lakeside High School 3 Building 5011 Roofing Modified Covering Has Blisters That Should Be Repaired Near Rtu-12 A Deficiency has been corrected or addressed
Lakeside High School 3 Building 5010 Electrical Interior Power Wiring Replacement A Deficiency has been corrected or addressed
Lakeside High School 2 Building 5010 Electrical Panelboard Replacement A Deficiency has been corrected or addressed
Lakeside High School 2 Building 5010 Electrical Panelboard Replacement A Deficiency has been corrected or addressed
Lakeside High School 2 Building 5010 Electrical Panelboard Replacement A Deficiency has been corrected or addressed
Lakeside High School 2 Building 5010 Electrical Panelboard Replacement A Deficiency has been corrected or addressed
Lakeside High School 2 Building 5010 Electrical Panelboard Replacement A Deficiency has been corrected or addressed
Lakeside High School 2 Building 5010 Electrical Panelboard Replacement A Deficiency has been corrected or addressed
Lakeside High School 2 Building 5010 Electrical Panelboard Replacement A Deficiency has been corrected or addressed
Lakeside High School 2 Building 5010 Electrical Panelboard Replacement A Deficiency has been corrected or addressed
Lakeside High School 2 Building 5010 Electrical Panelboard Replacement A Deficiency has been corrected or addressed
Lakeside High School 2 Building 5010 Electrical Panelboard Replacement A Deficiency has been corrected or addressed
Lakeside High School 2 Building 5010 Electrical Panelboard Replacement A Deficiency has been corrected or addressed
Lakeside High School 2 Building 5010 Electrical Panelboard Replacement A Deficiency has been corrected or addressed
Lakeside High School 2 Building 5010 Electrical Panelboard Replacement A Deficiency has been corrected or addressed
Lakeside High School 2 Building 5010 Electrical Panelboard Replacement A Deficiency has been corrected or addressed
Lakeside High School 3 Building 5015 Mechanical Kitchen Air/Exhaust Installation A Deficiency has been corrected or addressed
Lakeside High School 2 Building 5012 Electrical Electrical Transformer Replacement A Deficiency has been corrected or addressed
18 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Lakeside High School 2 Building 5012 Electrical Electrical Transformer Replacement Gym Stage Storage A Deficiency has been corrected or addressed
Lakeside High School 2 Building 5012 Electrical Panelboard Replacement A Deficiency has been corrected or addressed
Lakeside High School 2 Building 5012 Electrical Panelboard Replacement A Deficiency has been corrected or addressed
Lakeside High School 2 Building 5012 Electrical Panelboard Replacement A Deficiency has been corrected or addressed
Lakeside High School 2 Building 5012 Electrical Panelboard Replacement Upper Level Gym Balcony A Deficiency has been corrected or addressed
Lakeside High School 2 Building 5012 Electrical Panelboard Replacement A Deficiency has been corrected or addressed
Lakeside High School 2 Building 5012 Electrical Panelboard Replacement Gym Pe 2502 Stage A Deficiency has been corrected or addressed
Lakeside High School 2 Building 5010 Electrical Switchgear Replacement Beyond Useful Life. Mech Room 1403 A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 3 Building 2010 Roofing Debris In Gutter Removal Clogged With Debris And Vegetation A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 3 Building 2010 Roofing Roof Drain Cleaning Clogged Drains With Debris A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 3 Building 2011 Roofing Roof Drain Cleaning Clogged With Debris A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 3 Building 2012 Roofing Roof Drain Cleaning Clogged With Debris A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Horn/Strobe Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 1 Building 2011 Fire and Life Safety Wall Pack Lighting Replacement Not Working A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 1 Building 2012 Fire and Life Safety Wall Pack Lighting Replacement Not Working A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2020 Electrical Exterior Liquid Filled Transformer Replacement Beyond Useful Life 75 Kva A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2010 Electrical Exterior Dry Type Transformer Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2010 Electrical Distribution Panel Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life 120 And 208 60A A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life 120 And 240 125A A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life 120 And 208 200A A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 3 Building 2011 Electrical Interior Power Wiring Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2011 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 3 Building 2012 Electrical Interior Power Wiring Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2012 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2012 Electrical Panelboard Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 3 Building 2012 Electrical Electrical Receptacle Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 3 Building 2020 Interior Athletic Sport Flooring Replacement Beyond Useful Life Faded And Bubbling A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2010 Roofing Built-up Roofing Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2010 Roofing Gutter Joint Repair Leaking At Joints A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2010 Mechanical Electric Unit Heater Replacement Damaged A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 3 Building 2010 Electrical Electrical Receptacle Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2011 Roofing Built-up Roofing Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 3 Building 2011 Electrical Canopy Lighting Replacement Not Working A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 3 Building 2011 Electrical Electrical Receptacle Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2012 Roofing Built-up Roofing Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 3 Building 2020 Roofing Gutter Replacement Beyond Useful Life And Leaking A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 3 Building 2020 Roofing Metal Downspout Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement Not Working A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 3 Electrical Pole Lighting Repair Not Connected To Electricity A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2012 Exterior Aluminum Window Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2012 Exterior Aluminum Window Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2012 Exterior Aluminum Window Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 2 Building 2012 Exterior Aluminum Window Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 3 Building 2012 Electrical Lighting Fixtures Replacement A Deficiency has been corrected or addressed
Laurel Ridge Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement A Deficiency has been corrected or addressed
Lithonia High School 3 Electrical Pole Lighting Repair Damaged A Deficiency has been corrected or addressed
Lithonia High School 1 Building 5010 Fire and Life Safety Emergency Exit Signage Replacement A Few Need Replacing A Deficiency has been corrected or addressed
Lithonia High School 2 Building 5010 Fire and Life Safety Emergency Exit Signage Is Missing More Needed A Deficiency has been corrected or addressed
19 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Cracking In CMU Block Wall In Several
Lithonia High School 1 Building 5010 Structural Evidence of Structural Deficiency Locations. Some Cracks Observed From Both A Deficiency has been corrected or addressed
Sides Of Wall
Lithonia High School 2 Building 5010 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility
Cracked A Deficiency has been corrected or addressed
Lithonia High School 3 Building 5010 Plumbing Toilet Plumbing Fixture Repair Repair Toilet Flush Valves A Deficiency has been corrected or addressed
Lithonia Middle School 2 Building 4010 Roofing Built-up Roofing Replacement Beyond Useful Life - Leaks A Deficiency has been corrected or addressed
Lithonia Middle School 3 Building 4010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Throughout A Deficiency has been corrected or addressed
Cctv Camera Was Installed But Not Wired To
Lithonia Middle School 1 Building 4010 Fire and Life Safety Security Alarm Camera Replacement A Deficiency has been corrected or addressed
The System - All Other Cameras Are Working.
Lithonia Middle School 3 Building 4010 Roofing Membrane Flashing At Parapet (>2') Repair Above Gym A Deficiency has been corrected or addressed
Lithonia Middle School 3 Building 4010 Roofing Metal Downspout Replacement Room 903 And 923 A Deficiency has been corrected or addressed
Livsey Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Livsey Elementary School 3 Building 2010 Roofing Debris In Gutter Removal Clean Alum. Walkway Roof And Gutters. A Deficiency has been corrected or addressed
Livsey Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Leaves And Front And Back A Deficiency has been corrected or addressed
Livsey Elementary School 2 Building 2020 Roofing Gutter Joint Repair Leaking And Front A Deficiency has been corrected or addressed
Marbut Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Marbut Elementary School 1 Building 2010 Fire and Life Safety Fire Sprinkler System Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Marbut Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Panel Replacement A Deficiency has been corrected or addressed
Marbut Elementary School 1 Building 2020 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Marbut Elementary School 1 Building 2020 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Margaret Harris Comprehensive 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Martin Luther King, Jr. High School 1 Building 5010 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Martin Luther King, Jr. High School 1 Building 5010 Fire and Life Safety Fire Alarm Panel Replacement Replace Old Panel A Deficiency has been corrected or addressed
Replace Front Panels And The One In
Martin Luther King, Jr. High School 2 Building 5011 Fire and Life Safety Security Alarm Panel Replacement A Deficiency has been corrected or addressed
Electrical Room And Fix Errors.
(5) 3.5'X7' Curtainwall Glass Panels Have
Martin Luther King, Jr. High School 2 Building 5011 Exterior Storefront/Curtain Wall Replacement (Bldg SF) Shattered (Internal Pane In 4 Cases, External A Deficiency has been corrected or addressed
Pane In 1 Case). Replace Panels.
Mary McLeod Bethune Middle School 2 Building 4010 Roofing Modified Roof Covering Replacement Beyond Useful Life - Replace All A Deficiency has been corrected or addressed
Mentioned There Were 93 Total In The
Mary McLeod Bethune Middle School 1 Building 4010 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Building
Mary McLeod Bethune Middle School 1 Building 4010 Fire and Life Safety Security Alarm Camera Replacement Old And Broken A Deficiency has been corrected or addressed
Mary McLeod Bethune Middle School 3 Electrical Pole Lighting Repair Not Working And Various A Deficiency has been corrected or addressed
McLendon Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
McLendon Elementary School 3 Building 2011 Mechanical Large Diameter Exhausts/Hoods Replacement A Deficiency has been corrected or addressed
McLendon Elementary School 2 Building 2013 Electrical Electrical Transformer Replacement Aged And Obsolete. A Deficiency has been corrected or addressed
McNair Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
McNair Elementary School 3 Building 2010 Exterior Exterior Metal Door Repainting A Deficiency has been corrected or addressed
McNair Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Debris And Plants A Deficiency has been corrected or addressed
McNair Elementary School 3 Building 2010 Roofing Roof Drain Cleaning Debris A Deficiency has been corrected or addressed
McNair High School 3 Building 5012 Exterior Exterior Metal Door Repainting Repaint A Deficiency has been corrected or addressed
McNair High School 3 Building 5030 Exterior Exterior Metal Door Repainting A Deficiency has been corrected or addressed
McNair High School 3 Building 5013 Exterior Exterior Metal Door Repainting A Deficiency has been corrected or addressed
McNair High School 3 Building 5013 Exterior Aluminum Storefront Exterior Door Repair Repair Door Threshold A Deficiency has been corrected or addressed
McNair High School 1 Building 5020 Fire and Life Safety Wall Pack Lighting Replacement Beyond Useful Life A Deficiency has been corrected or addressed
McNair High School 1 Building 5020 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
McNair High School 1 Building 5030 Fire and Life Safety Wall Pack Lighting Replacement Beyond Useful Life A Deficiency has been corrected or addressed
McNair High School 1 Building 5030 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
McNair High School 3 Building 5010 Exterior Exterior Metal Door Repainting A Deficiency has been corrected or addressed
McNair High School 3 Building 5011 Electrical Electrical Receptacle Replacement Missing Light Switch Cover Plate A Deficiency has been corrected or addressed
McNair High School 2 Building 5010 Electrical Electrical Receptacle Repair Missing Cover Plate A Deficiency has been corrected or addressed
McNair High School 1 Building 5010 Electrical Exposed Wiring / Conduit Repair A Deficiency has been corrected or addressed
Midvale Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Midvale Elementary School 3 Building 2010 Roofing Roof Drain Cleaning Throughout A Deficiency has been corrected or addressed
Midvale Elementary School 3 Building 2011 Roofing Roof Drain Cleaning Throughout A Deficiency has been corrected or addressed
Midvale Elementary School 2 Building 2020 Electrical Exterior Liquid Filled Transformer Replacement Outside Gym A Deficiency has been corrected or addressed
Midvale Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Mech Room A Deficiency has been corrected or addressed
Midvale Elementary School 2 Building 2010 Electrical Panelboard Replacement Kitchen A Deficiency has been corrected or addressed
20 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Midvale Elementary School 2 Building 2010 Electrical Panelboard Replacement Janitor And Custodian A Deficiency has been corrected or addressed
Midvale Elementary School 2 Building 2010 Electrical Panelboard Replacement Stage A Deficiency has been corrected or addressed
Midvale Elementary School 2 Building 2010 Electrical Panelboard Replacement Janitor Closet A Deficiency has been corrected or addressed
Midvale Elementary School 2 Building 2010 Electrical Panelboard Replacement Janitor Closet A Deficiency has been corrected or addressed
Midvale Elementary School 2 Building 2010 Electrical Panelboard Replacement Janitor Closet A Deficiency has been corrected or addressed
Midvale Elementary School 2 Building 2010 Electrical Panelboard Replacement Custodian Room A Deficiency has been corrected or addressed
Midvale Elementary School 2 Building 2010 Electrical Panelboard Replacement Custodian Room - Lower Level A Deficiency has been corrected or addressed
Midvale Elementary School 2 Building 2010 Electrical Panelboard Replacement Old, Mech Room A Deficiency has been corrected or addressed
Midvale Elementary School 2 Building 2010 Electrical Panelboard Replacement Old Mech Room A Deficiency has been corrected or addressed
Midvale Elementary School 3 Building 2010 Electrical Electrical Receptacle Replacement Multiple Locations A Deficiency has been corrected or addressed
Midvale Elementary School 2 Building 2011 Electrical Panelboard Replacement Storage Room 121.2 A Deficiency has been corrected or addressed
Midvale Elementary School 3 Building 2011 Electrical Electrical Receptacle Replacement Rooms 120 -125 And Outside Door. A Deficiency has been corrected or addressed
Midvale Elementary School 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Many Areas With Ponding. A Deficiency has been corrected or addressed
Midvale Elementary School 3 Building 2011 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Many Areas With Ponding A Deficiency has been corrected or addressed
Midvale Elementary School 2 Building 2011 Mechanical Package Roof Top Unit Replacement Not Working, Sw Corner A Deficiency has been corrected or addressed
Midvale Elementary School 3 Building 2020 Interior Athletic Sport Flooring Replacement Bubbling Near Storage Room A Deficiency has been corrected or addressed
Midvale Elementary School 3 Site Concrete Walks Replacement Damaged, South Walkway A Deficiency has been corrected or addressed
Midvale Elementary School 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility A Deficiency has been corrected or addressed
The Only Ramp To Get To Building 2020
(Gym) Is A Make Shift Wood Ramp Placed At
Midvale Elementary School 3 Site Exterior Ramp Replacement Lower Stairwell And Egress In North West A Deficiency has been corrected or addressed
Corner. Install Proper Egress Ramp, ADA
Compliant.
Midvale Elementary School 3 Interior Access Is Not ADA Compliant A Deficiency has been corrected or addressed
Midvale Elementary School 3 Interior Entry Door Does Not Have Power Assist Device Install Powered Door At North West Stairwell. A Deficiency has been corrected or addressed
Midvale Elementary School 3 Exterior Exterior Entry Door Hardware Is Not ADA Compliant Install Set Of Power Assist Double Doors. A Deficiency has been corrected or addressed
No Ramp Or Elevator At Stage. Install One
Midvale Elementary School 3 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation A Deficiency has been corrected or addressed
Knob Hardware In Hallway, Not Compliant.
East Ramp Next To Covered Walkway.
Midvale Elementary School 3 Site Exterior Signage At Accessible Parking Area Does Not Meet ADA Requirements A Deficiency has been corrected or addressed
Repaint ADA Ramp Of Covered Walkway East.
Miller Grove High School 1 Building 5010 Fire and Life Safety Fire Alarm Panel Replacement A Deficiency has been corrected or addressed
Miller Grove High School 1 Building 5020 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Miller Grove High School 1 Building 5020 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Miller Grove Middle School 3 Building 4010 Exterior Brick Exterior Repair Cracked A Deficiency has been corrected or addressed
Open Joints. Mtl Coping Flashing And
Miller Grove Middle School 3 Building 4010 Roofing Membrane Flashing At Parapet (>2') Repair A Deficiency has been corrected or addressed
Sealant.
Miller Grove Middle School 3 Building 4010 Plumbing Shower Replacement Boys Locker Room A Deficiency has been corrected or addressed
Montclair Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Montclair Elementary School 2 Building 2012 Exterior Aluminum Window Replacement Broken Window A Deficiency has been corrected or addressed
Montclair Elementary School 1 Building 2010 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Montclair Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Montclair Elementary School 1 Building 2011 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Montclair Elementary School 1 Building 2012 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Montclair Elementary School 1 Building 2020 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Montclair Elementary School 1 Building 2020 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Montclair Elementary School 3 Building 2010 Roofing Debris In Gutter Removal Leaves And Debris A Deficiency has been corrected or addressed
Montclair Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Debris In Gutter A Deficiency has been corrected or addressed
Replace 2 Receptacles With (7F) Tyde In Pre-K
Montclair Elementary School 3 Building 2011 Electrical Electrical Receptacle Replacement Classrooms; All Electrical Panels For This A Deficiency has been corrected or addressed
Building Are Located In Bldg 2010
Montclair Elementary School 3 Building 2011 Roofing Gutter Replacement Leaks And Damaged A Deficiency has been corrected or addressed
Montgomery Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Montgomery Elementary School 1 Building 2020 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Montgomery Elementary School 1 Building 2020 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Montgomery Elementary School 3 Building 2010 Roofing Debris In Gutter Removal Around The Building A Deficiency has been corrected or addressed
Montgomery Elementary School 3 Building 2012 Roofing Debris In Gutter Removal A Deficiency has been corrected or addressed
21 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Montgomery Elementary School 3 Building 2013 Roofing Debris In Gutter Removal Behind The Building A Deficiency has been corrected or addressed
Montgomery Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Around The Gym A Deficiency has been corrected or addressed
Montgomery Elementary School 3 Building 2012 Plumbing Urinal Repair Repair - Boys 27.1 A Deficiency has been corrected or addressed
Murphey Candler Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement Old A Deficiency has been corrected or addressed
Murphey Candler Elementary School 1 Building 2011 Fire and Life Safety Fire Alarm Replacement Old A Deficiency has been corrected or addressed
Murphey Candler Elementary School 1 Building 2012 Fire and Life Safety Fire Alarm Panel Replacement Old A Deficiency has been corrected or addressed
Murphey Candler Elementary School 1 Building 2012 Fire and Life Safety Fire Alarm Replacement Old A Deficiency has been corrected or addressed
Murphey Candler Elementary School 1 Building 2020 Fire and Life Safety Fire Alarm Replacement Old A Deficiency has been corrected or addressed
Murphey Candler Elementary School 3 Building 2020 Plumbing Urinal Repair Repair - Boys 319.1 A Deficiency has been corrected or addressed
Nancy Creek Facility 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Nancy Creek Facility 1 Building 2010 Fire and Life Safety Fire Sprinkler System Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Nancy Creek Facility 1 Building 2010 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Nancy Creek Facility 1 Building 2010 Fire and Life Safety Fire Alarm Panel Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Nancy Creek Facility 1 Building 2010 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Nancy Creek Facility 1 Building 2020 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Nancy Creek Facility 1 Building 2020 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Nancy Creek Facility 3 Building 2010 Roofing Debris In Gutter Removal Leaves A Deficiency has been corrected or addressed
Nancy Creek Facility 3 Building 2020 Roofing Debris In Gutter Removal Leaves A Deficiency has been corrected or addressed
Nancy Creek Facility 3 Roofing Debris In Gutter Removal At Covered Walkway A Deficiency has been corrected or addressed
Nancy Creek Facility 3 Building 2010 Roofing Roof Drain Cleaning Leaves A Deficiency has been corrected or addressed
Roof Leaking At 5 Locations At Roof Drains.
Leaks Causing Damage To Ceilings. Repair
Nancy Creek Facility 2 Building 2010 Roofing Single-Ply Membrane Has Holes That Should Be Repaired A Deficiency has been corrected or addressed
Roof. Slope Roof To Drains, Ponding In Some
Locations
Narvie Harris Elementary School 3 Site Playground Equipment Replacement Rusting A Deficiency has been corrected or addressed
Narvie Harris Elementary School 3 Building 2010 Roofing Debris In Gutter Removal A Deficiency has been corrected or addressed
Narvie Harris Elementary School 3 Building 2010 Exterior Exterior Metal Door Repainting Fading, Paint Chipping, Rust A Deficiency has been corrected or addressed
North DeKalb Stadium 1 Building 8010 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
North DeKalb Stadium 3 Building 8020 Exterior Brick Exterior Repointing Building Foundation A Deficiency has been corrected or addressed
Oak Grove Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Oak Grove Elementary School 2 Building 2010 Roofing Built-up Roofing Replacement Aged, Ponding A Deficiency has been corrected or addressed
Oak Grove Elementary School 2 Building 2011 Roofing Built-up Roofing Replacement Aged, Ponding A Deficiency has been corrected or addressed
Oak Grove Elementary School 2 Building 2012 Roofing Modified Roof Covering Replacement Bubbled Surface A Deficiency has been corrected or addressed
Oak Grove Elementary School 3 Building 2010 Roofing Roof Drain Cleaning Leaf Build-Up A Deficiency has been corrected or addressed
Oak Grove Elementary School 3 Building 2011 Roofing Roof Drain Cleaning Leaf Build-Up A Deficiency has been corrected or addressed
Oak Grove Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Leaves A Deficiency has been corrected or addressed
Oak Grove Elementary School 1 Building 2010 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Oak Grove Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Oak Grove Elementary School 1 Building 2011 Fire and Life Safety Fire Sprinkler System Replacement (SF Basis) Beyond Useful Life A Deficiency has been corrected or addressed
Oak Grove Elementary School 2 Building 2010 Mechanical Exterior Metal Cooling Tower Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Oak Grove Elementary School 2 Building 2010 Electrical Exterior Dry Type Transformer Replacement Beyond Useful Life - 150 Kva A Deficiency has been corrected or addressed
Oak View Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Oak View Elementary School 3 Building 2010 Roofing Roof Operable Hatch Repair A Deficiency has been corrected or addressed
Oak View Elementary School 1 Building 2010 Fire and Life Safety Fire Sprinklers Heads Repair Damaged A Deficiency has been corrected or addressed
Oak View Elementary School 1 Building 2010 Fire and Life Safety Security Alarm Camera Replacement A Deficiency has been corrected or addressed
Oak View Elementary School 3 Building 2010 Exterior Exterior Metal Door Repainting A Deficiency has been corrected or addressed
Damaged Lens Cover- Could Fall And Hurt A
Oak View Elementary School 3 Building 2010 Electrical 2 X 4 Interior Fluorescent Lighting Replacement A Deficiency has been corrected or addressed
Student And Staff
Oak View Elementary School 3 Building 2010 Plumbing Toilet Plumbing Fixture Repair Toilet Leaking A Deficiency has been corrected or addressed
Oak View Elementary School 3 Building 2010 Plumbing Urinal Repair Leaking Urinal A Deficiency has been corrected or addressed
Oakcliff Elementary School 3 Site Playground Equipment Replacement Rusting A Deficiency has been corrected or addressed
Oakcliff Elementary School 3 Building 2010 Exterior Aluminum Window Repair Single Pane Cracked Caulk A Deficiency has been corrected or addressed
Oakcliff Elementary School 3 Building 2010 Exterior Aluminum Window Repair Single Pane Cracked Caulk A Deficiency has been corrected or addressed
Oakcliff Elementary School 3 Building 2010 Exterior Aluminum Window Repair Single Pane Cracked Caulk A Deficiency has been corrected or addressed
Oakcliff Elementary School 1 Electrical Area Lighting Installation None Installed For Security A Deficiency has been corrected or addressed
Oakcliff Elementary School 3 Building 2010 Roofing Roof Drain Cleaning Debris In Drains A Deficiency has been corrected or addressed
Oakcliff Elementary School 3 Building 2011 Roofing Roof Drain Cleaning A Deficiency has been corrected or addressed
Oakcliff Elementary School 3 Building 2012 Roofing Roof Drain Cleaning A Deficiency has been corrected or addressed
Old Rock Gym 1 Building 8010 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Old Rock Gym 1 Building 8010 Fire and Life Safety Security Alarm Replacement A Deficiency has been corrected or addressed
Old Rock Gym 1 Building 8010 Fire and Life Safety Fire Alarm Is Missing A Deficiency has been corrected or addressed
22 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Old Rock Gym 2 Building 8010 Fire and Life Safety Emergency Exit Signage Is Missing Old A Deficiency has been corrected or addressed
Old Rock Gym 1 Building 8010 Fire and Life Safety Fire Alarm Panel Is Missing A Deficiency has been corrected or addressed
Panola Way Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Panola Way Elementary School 1 Building 2010 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Panola Way Elementary School 1 Building 2010 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Panola Way Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Panola Way Elementary School 1 Building 2010 Fire and Life Safety Security Alarm Camera Replacement Camera Not Working A Deficiency has been corrected or addressed
Panola Way Elementary School 1 Building 2011 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Panola Way Elementary School 1 Building 2011 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Panola Way Elementary School 1 Building 2011 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Panola Way Elementary School 1 Building 2020 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Panola Way Elementary School 1 Building 2020 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Panola Way Elementary School 1 Building 2020 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Panola Way Elementary School 1 Building 2020 Fire and Life Safety Security Alarm Camera Replacement A Deficiency has been corrected or addressed
Panthersville Administrative 1 Building 8010 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Panthersville Administrative 1 Building 8010 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Panthersville Administrative 1 Building 8030 Fire and Life Safety Fire Alarm Is Missing Not Installed A Deficiency has been corrected or addressed
Panthersville Administrative 2 Building 8030 Fire and Life Safety Emergency Exit Signage Is Missing Not Installed A Deficiency has been corrected or addressed
Panthersville Administrative 1 Building 8030 Fire and Life Safety Security Alarm Is Missing Not Installed A Deficiency has been corrected or addressed
Peachcrest Elementary School 1 Building 2010 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Peachcrest Elementary School 2 Building 2010 Fire and Life Safety Security Alarm Motion Detector Replacement A Deficiency has been corrected or addressed
Peachcrest Elementary School 3 Building 2010 Roofing Roof Drain Cleaning A Deficiency has been corrected or addressed
Peachtree Middle School 1 Building 4010 Fire and Life Safety Emergency Exit Signage Replacement Courtyard A Deficiency has been corrected or addressed
Old, Deficient. Replace. Room 207 Weight
Peachtree Middle School 3 Building 4010 Interior Athletic Sport Flooring Replacement A Deficiency has been corrected or addressed
Room.
Peachtree Middle School 3 Building 4010 Electrical Electrical Receptacle Replacement Multiple Locations A Deficiency has been corrected or addressed
Half-Round And Arched Curtainwall And
Clerestory Window At East Wall Of Room 500
Peachtree Middle School 3 Building 4010 Roofing Membrane Flashing At Parapet (>2') Repair - Gym - Leaks Down To Gypsum Soffit Directly A Deficiency has been corrected or addressed
Below. Re-Flash To Form Sill And To Shed
Water. Recaulk 30 Lf Of Window.
At North-West Corner Of 500 - Gym,
Peachtree Middle School 3 Building 4010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing A Deficiency has been corrected or addressed
Significant Ponding. Add Taper.
Pine Ridge Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Pine Ridge Elementary School 3 Building 2010 Plumbing Emergency Eyewash Replacement A Deficiency has been corrected or addressed
Pine Ridge Elementary School 1 Building 2010 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Pine Ridge Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Pine Ridge Elementary School 1 Building 2010 Fire and Life Safety Security Alarm Camera Replacement A Deficiency has been corrected or addressed
Pine Ridge Elementary School 1 Building 2011 Fire and Life Safety Wall Pack Lighting Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Pine Ridge Elementary School 1 Building 2011 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Pine Ridge Elementary School 1 Building 2011 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Pine Ridge Elementary School 1 Building 2020 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Pleasantdale (New) Elementary School 2 Building 8010 Conveyances Elevator Cab And/Or Controls Repair Inoperable A Deficiency has been corrected or addressed
Pleasantdale (New) Elementary School 3 Building 8010 Plumbing Toilet Plumbing Fixture Repair A Deficiency has been corrected or addressed
Princeton Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Princeton Elementary School 1 Building 2010 Structural Evidence of Structural Deficiency A Deficiency has been corrected or addressed
Rainbow Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Uneven Slabs And Joints And Does Not Drain
Rainbow Elementary School 3 Site Concrete Walks Replacement A Deficiency has been corrected or addressed
Properly During Rain Events
Rainbow Elementary School 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility
Cracked A Deficiency has been corrected or addressed
Rainbow Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Clogged With Leaves A Deficiency has been corrected or addressed
Rainbow Elementary School 3 Building 2010 Roofing Roof Drain Cleaning Clogged With Leaves A Deficiency has been corrected or addressed
Rainbow Elementary School 3 Building 2011 Roofing Roof Drain Cleaning Clogged With Leaf Debris A Deficiency has been corrected or addressed
Rainbow Elementary School 3 Building 2012 Roofing Roof Drain Cleaning Clogged With Leaf Debris A Deficiency has been corrected or addressed
Redan Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Area Of Roof Between Stage And T-Wk-Rm
Redan Elementary School 2 Building 2020 Roofing Modified Roof Covering Replacement A Deficiency has been corrected or addressed
Leaks
Redan Elementary School 2 Building 2021 Roofing Modified Roof Covering Replacement Leaks A Deficiency has been corrected or addressed
Redan Elementary School 2 Building 2030 Roofing Metal Roof Structural Roof Covering Replacement Rusted Roof Of Metal Canopy A Deficiency has been corrected or addressed
23 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Beyond Useful Life - Maintenance Person
Commented About Leaks; Building Has Not
Redan Elementary School 2 Building 2030 Roofing Modified Roof Covering Replacement A Deficiency has been corrected or addressed
Been Redone Recently And Should Be
Replaced
Redan Elementary School 1 Building 2010 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Redan Elementary School 1 Building 2020 Fire and Life Safety Fire Alarm Panel Replacement A Deficiency has been corrected or addressed
Redan Elementary School 1 Building 2021 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Redan Elementary School 1 Building 2022 Fire and Life Safety Emergency Exit Signage Replacement Dim Lights, Replace A Deficiency has been corrected or addressed
Redan Elementary School 1 Building 2040 Fire and Life Safety Security Alarm Is Missing Install System A Deficiency has been corrected or addressed
Redan Elementary School 3 Building 2022 Roofing Debris In Gutter Removal Vegetation Growing In Gutters. A Deficiency has been corrected or addressed
Redan Elementary School 3 Building 2040 Roofing Debris In Gutter Removal Gutters Have Debris And Roof A Deficiency has been corrected or addressed
Redan Elementary School 3 Building 2010 Interior Interior Door Replacement Broken A Deficiency has been corrected or addressed
Redan High School 3 Building 5010 Mechanical Kitchen Air/Exhaust Repair A Deficiency has been corrected or addressed
Redan High School 3 Building 5010 Roofing Roof Drain Cleaning Debris In Drains A Deficiency has been corrected or addressed
Redan High School 3 Building 5011 Roofing Roof Drain Cleaning A Deficiency has been corrected or addressed
Redan High School 3 Building 5012 Roofing Roof Drain Cleaning A Deficiency has been corrected or addressed
Redan Middle School 2 Building 4010 Roofing Modified Roof Covering Replacement Extreme Blisters And Deterioration A Deficiency has been corrected or addressed
Redan Middle School 1 Building 4010 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Redan Middle School 3 Building 4010 Exterior Exterior Metal Door Repainting A Deficiency has been corrected or addressed
Structural Cracks At Multiple Locations In
School; Girls Shower, Room 709 Above Door,
Redan Middle School 1 Building 4010 Structural Evidence of Structural Deficiency Room 701, Wall Separating 304 And 302. A Deficiency has been corrected or addressed
Floor Of Room Next To Girls Showers Is Also
Sloping Down But No Cracks Visible
Redan Middle School 3 Building 4010 Electrical Electrical Receptacle Replacement A Deficiency has been corrected or addressed
Redan Middle School 3 Building 4010 Plumbing Urinal Replacement Coming Off Wall A Deficiency has been corrected or addressed
Robert Shaw Theme 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Robert Shaw Theme 3 Building 2010 Roofing Debris In Gutter Removal Foliage And Debris - Clean Throughout A Deficiency has been corrected or addressed
Foliage And Debris - Clean West And South
Robert Shaw Theme 3 Building 2011 Roofing Debris In Gutter Removal A Deficiency has been corrected or addressed
Ends
Robert Shaw Theme 3 Building 2020 Roofing Debris In Gutter Removal Gutters Need Cleaning Throughout. A Deficiency has been corrected or addressed
Debris Clogging Drains - Clean And Declutter
Robert Shaw Theme 3 Building 2010 Roofing Roof Drain Cleaning A Deficiency has been corrected or addressed
At Central Roof (Above 116 - Media Center)
Robert Shaw Theme 3 Building 2020 Electrical Mounted Building Lighting Installation Install On Either Side Of The Building A Deficiency has been corrected or addressed
Robert Shaw Theme 1 Building 2010 Fire and Life Safety Wall Pack Lighting Replacement Multiple Locations A Deficiency has been corrected or addressed
Robert Shaw Theme 1 Building 2020 Fire and Life Safety Wall Pack Lighting Replacement Inside - Not Working A Deficiency has been corrected or addressed
Robert Shaw Theme 3 Building 2010 Electrical Electrical Receptacle Replacement Multiple Locations A Deficiency has been corrected or addressed
Rock Chapel Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Rock Chapel Elementary School 1 Building 2011 Fire and Life Safety Security Alarm Camera Replacement Cctv Cameras Not Working A Deficiency has been corrected or addressed
Rock Chapel Elementary School 1 Building 2020 Fire and Life Safety Wall Pack Lighting Replacement Battery Units Not Working A Deficiency has been corrected or addressed
Rock Chapel Elementary School 1 Building 2020 Fire and Life Safety Emergency Exit Signage Replacement Battery Units Not Working A Deficiency has been corrected or addressed
Rowland Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Rowland Elementary School 2 Building 2011 Fire and Life Safety Wall Pack Lighting Installation A Deficiency has been corrected or addressed
Rowland Elementary School 1 Building 2011 Fire and Life Safety Wall Pack Lighting Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Rowland Elementary School 1 Building 2011 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Rowland Elementary School 1 Building 2020 Fire and Life Safety Wall Pack Lighting Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Rowland Elementary School 1 Building 2020 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Rowland Elementary School 2 Building 2011 Fire and Life Safety Emergency Exit Signage Is Missing A Deficiency has been corrected or addressed
Sagamore Hills Elementary School 3 Building 2010 Roofing Roof Drain Cleaning All Roof Drains Clogged With Leaf Debris A Deficiency has been corrected or addressed
Sagamore Hills Elementary School 3 Building 2011 Roofing Roof Drain Cleaning All Roof Drains Clogged With Leaf Debris A Deficiency has been corrected or addressed
All Gutters Along The Roof Are Clogged With
Sagamore Hills Elementary School 3 Building 2020 Roofing Debris In Gutter Removal A Deficiency has been corrected or addressed
Leaf Debris
Salem Middle School 1 Building 4010 Fire and Life Safety Emergency Exit Signage Replacement Multiple Locations A Deficiency has been corrected or addressed
Salem Middle School 1 Building 4010 Fire and Life Safety Fire Alarm Actuator Replacement Old A Deficiency has been corrected or addressed
Sam Moss Service Center 2 Building 8010 Roofing Built-up Roofing Replacement A Deficiency has been corrected or addressed
All Metal Coping Needs Replacing (Rusted
Sam Moss Service Center 2 Building 8010 Roofing Modified Roof Covering Replacement A Deficiency has been corrected or addressed
And Corroded)
24 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Sam Moss Service Center 2 Building 8020 Roofing Metal Roof Architectural Roof Covering Replacement A Deficiency has been corrected or addressed
Sam Moss Service Center 2 Building 8040 Roofing Metal Roof Architectural Roof Covering Replacement A Deficiency has been corrected or addressed
Sam Moss Service Center 2 Building 8050 Roofing Metal Roof Architectural Roof Covering Replacement A Deficiency has been corrected or addressed
Sam Moss Service Center 2 Building 8050 Roofing Metal Roof Architectural Roof Covering Replacement A Deficiency has been corrected or addressed
Sam Moss Service Center 3 Building 8050 Roofing Awning Or Canopy Metal Roofing System Replacement A Deficiency has been corrected or addressed
Sam Moss Service Center 2 Building 8060 Roofing Metal Roof Architectural Roof Covering Replacement A Deficiency has been corrected or addressed
Sam Moss Service Center 3 Building 8010 Roofing Debris In Gutter Removal A Deficiency has been corrected or addressed
Sam Moss Service Center 3 Building 8010 Roofing Roof Drain Cleaning A Deficiency has been corrected or addressed
Sam Moss Service Center 3 Building 8020 Roofing Debris In Gutter Removal Clogged A Deficiency has been corrected or addressed
Sam Moss Service Center 1 Building 8010 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Sam Moss Service Center 1 Building 8010 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Sam Moss Service Center 1 Building 8020 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Sam Moss Service Center 1 Building 8030 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life - Broken A Deficiency has been corrected or addressed
Sam Moss Service Center 1 Building 8030 Fire and Life Safety Security Alarm Camera Replacement A Deficiency has been corrected or addressed
Sam Moss Service Center 1 Building 8040 Fire and Life Safety Wall Pack Lighting Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Sam Moss Service Center 1 Building 8040 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Sam Moss Service Center 1 Building 8050 Fire and Life Safety Wall Pack Lighting Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Sam Moss Service Center 1 Building 8050 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Sam Moss Service Center 1 Building 8050 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Long Continuous Gutter With Several
Sam Moss Service Center 2 Building 8010 Roofing Gutter Joint Repair A Deficiency has been corrected or addressed
Separated Joins And Seams
Sam Moss Service Center 2 Building 8030 Exterior Aluminum Window Replacement Replace Broken Glass A Deficiency has been corrected or addressed
Sam Moss Service Center 3 Building 8060 Roofing Gutter Replacement Cloggedanddamaged A Deficiency has been corrected or addressed
Sam Moss Service Center 3 Building 8060 Roofing Metal Downspout Installation Damaged And Clogged A Deficiency has been corrected or addressed
Sam Moss Service Center 3 Building 8010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing A Deficiency has been corrected or addressed
Sam Moss Service Center 2 Building 8020 Roofing Gutter Joint Repair Damaged Joints A Deficiency has been corrected or addressed
Sam Moss Service Center 3 Building 8040 Roofing Metal Downspout Installation Damaged A Deficiency has been corrected or addressed
Sam Moss Service Center 3 Building 8050 Roofing Gutter Replacement A Deficiency has been corrected or addressed
Sam Moss Service Center 3 Building 8050 Roofing Metal Downspout Installation A Deficiency has been corrected or addressed
Shadow Rock Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Shadow Rock Elementary School 3 Building 2010 Roofing Debris In Gutter Removal Leaf Debris Build Up A Deficiency has been corrected or addressed
Shadow Rock Elementary School 3 Building 2010 Roofing Roof Drain Cleaning Leaf Debris Built Up A Deficiency has been corrected or addressed
Silver Hill Facility 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Silver Hill Facility 1 Building 2010 Fire and Life Safety Wall Pack Lighting Replacement Old, Throughout Building A Deficiency has been corrected or addressed
Silver Hill Facility 1 Building 2010 Fire and Life Safety Emergency Exit Signage Replacement Old, Throughout Building A Deficiency has been corrected or addressed
Silver Hill Facility 1 Building 2010 Fire and Life Safety Fire Alarm Is Missing Old, Throughout Building A Deficiency has been corrected or addressed
Silver Hill Facility 1 Building 2011 Fire and Life Safety Fire Alarm Is Missing Old, Throughout Building A Deficiency has been corrected or addressed
Silver Hill Facility 1 Building 2020 Fire and Life Safety Wall Pack Lighting Replacement Gym, Old A Deficiency has been corrected or addressed
Silver Hill Facility 1 Building 2020 Fire and Life Safety Emergency Exit Signage Replacement Gym, Old A Deficiency has been corrected or addressed
Silver Hill Facility 3 Building 2020 Roofing Debris In Gutter Removal Debris A Deficiency has been corrected or addressed
Snapfinger Elementary School 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement Replace Lights That Are Not Working A Deficiency has been corrected or addressed
Snapfinger Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Snapfinger Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Snapfinger Elementary School 1 Building 2011 Fire and Life Safety Emergency Exit Signage Replacement Workroom A Deficiency has been corrected or addressed
Snapfinger Elementary School 1 Building 2011 Fire and Life Safety Emergency Lighting System Replacement A Deficiency has been corrected or addressed
Snapfinger Elementary School 1 Building 2013 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Southwest DeKalb High School 1 Building 5010 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Southwest DeKalb High School 1 Building 5011 Fire and Life Safety Emergency Exit Signage Replacement Gym - Old Light A Deficiency has been corrected or addressed
Southwest DeKalb High School 1 Building 5013 Fire and Life Safety Emergency Exit Signage Replacement Lower Level Of 5310 Near Auditorium A Deficiency has been corrected or addressed
Southwest DeKalb High School 1 Building 5040 Fire and Life Safety Emergency Exit Signage Replacement Replace Old Sign A Deficiency has been corrected or addressed
Install System. Could Not Access Building
Southwest DeKalb High School 1 Building 5050 Fire and Life Safety Fire Alarm Is Missing A Deficiency has been corrected or addressed
Interior.
Southwest DeKalb High School 1 Building 5060 Fire and Life Safety Fire Alarm Is Missing A Deficiency has been corrected or addressed
Southwest DeKalb High School 1 Building 5070 Fire and Life Safety Security Alarm Replacement A Deficiency has been corrected or addressed
Southwest DeKalb High School 1 Building 5070 Fire and Life Safety Fire Alarm Is Missing A Deficiency has been corrected or addressed
Southwest DeKalb High School 1 Building 5011 Fire and Life Safety Emergency Lighting Installation A Deficiency has been corrected or addressed
Southwest DeKalb High School 1 Building 5020 Fire and Life Safety Emergency Lighting Installation A Deficiency has been corrected or addressed
Southwest DeKalb High School 1 Building 5050 Fire and Life Safety Security Alarm Is Missing Install System A Deficiency has been corrected or addressed
Southwest DeKalb High School 1 Building 5060 Fire and Life Safety Security Alarm Is Missing A Deficiency has been corrected or addressed
Southwest DeKalb High School 3 Building 5030 Roofing Debris In Gutter Removal Tree Debris And West Side Of Building A Deficiency has been corrected or addressed
Southwest DeKalb High School 3 Building 5011 Roofing Roof Drain Cleaning Clogged And Above 5200 Hallway A Deficiency has been corrected or addressed
25 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Stephenson High School 1 Building 5010 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Stephenson High School 1 Building 5010 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Stephenson High School 1 Building 5010 Fire and Life Safety Security Alarm Camera Replacement Cctv Cameras Not Working A Deficiency has been corrected or addressed
Stephenson High School 1 Building 5011 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Stephenson High School 1 Building 5020 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Stephenson High School 3 Building 5010 Roofing Roof Drain Cleaning A Deficiency has been corrected or addressed
Stephenson High School 3 Building 5010 Specialties Auditorium Seating Replacement Damaged A Deficiency has been corrected or addressed
Stephenson High School 3 Building 5010 Exterior Exterior Metal Door Repainting Paint Is Peeling A Deficiency has been corrected or addressed
Stephenson Middle School 2 Building 4010 Plumbing Water Heater Replacement A Deficiency has been corrected or addressed
Stephenson Middle School 2 Building 4010 Plumbing Water Heater Replacement A Deficiency has been corrected or addressed
Stephenson Middle School 2 Building 4011 Plumbing Water Heater Replacement A Deficiency has been corrected or addressed
Stephenson Middle School 1 Building 4010 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Stephenson Middle School 1 Building 4010 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Stephenson Middle School 1 Building 4011 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Stephenson Middle School 1 Building 4011 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Exposed Wiring At Switch And Receptacles In
Stephenson Middle School 3 Building 4011 Electrical Electrical Receptacle Replacement A Deficiency has been corrected or addressed
Cr806, 827, 820.
Stephenson Middle School 2 Building 4010 Roofing Modified Roof Covering Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Stone Mill Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Stone Mill Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Very Clogged A Deficiency has been corrected or addressed
Stone Mill Elementary School 3 Building 2010 Roofing Roof Drain Cleaning Very Clogged A Deficiency has been corrected or addressed
Stone Mill Elementary School 3 Building 2011 Roofing Roof Drain Cleaning Very Clogged A Deficiency has been corrected or addressed
Stone Mill Elementary School 3 Building 2012 Roofing Roof Drain Cleaning Clogged A Deficiency has been corrected or addressed
Stone Mill Elementary School 1 Building 2010 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Stone Mill Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Panel Replacement A Deficiency has been corrected or addressed
Stone Mountain Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Stone Mountain Elementary School 1 Building 2020 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Stone Mountain Elementary School 3 Building 2010 Roofing Roof Drain Cleaning Clogged With Debris Causing Ponding A Deficiency has been corrected or addressed
Stone Mountain High School 2 Building 5010 Exterior Storefront / Curtain Wall Repair Replace Gasket And Silicone Seals A Deficiency has been corrected or addressed
Stone Mountain High School 3 Building 5010 Roofing Roof Drain Cleaning A Deficiency has been corrected or addressed
Stoneview Elementary School 3 Site Playground Equipment Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Stoneview Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Toney Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Toney Elementary School 1 Building 2010 Fire and Life Safety Security Alarm Camera Replacement Cctv Not Working A Deficiency has been corrected or addressed
Toney Elementary School 1 Building 2011 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Toney Elementary School 1 Building 2012 Fire and Life Safety Fire Alarm Replacement Old A Deficiency has been corrected or addressed
Toney Elementary School 1 Building 2020 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Toney Elementary School 1 Building 2020 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Toney Elementary School 1 Building 2020 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Towers High School 3 Site Asphalt Driveway Replacement Potholes And Cracking A Deficiency has been corrected or addressed
Towers High School 3 Building 5010 Electrical 2 X 4 Interior Fluorescent Lighting Replacement Room Light Switch Damaged And Sparking A Deficiency has been corrected or addressed
Towers High School 3 Building 5013 Roofing Roof Drain Cleaning Debris A Deficiency has been corrected or addressed
Pull Handles On Exterior Storefront Doors
Tucker High School 3 Building 5010 Exterior Aluminum Storefront Exterior Door Repair Break Easily, Need To Repair 12 Broken A Deficiency has been corrected or addressed
Handles
Tucker High School 3 Building 5010 Roofing Roof Drain Cleaning Clean Roof Drains A Deficiency has been corrected or addressed
Tucker High School 3 Building 5020 Roofing Debris In Gutter Removal Leaves In Gutter A Deficiency has been corrected or addressed
Tucker Middle School 3 Building 4010 Roofing Roof Drain Cleaning Leaves A Deficiency has been corrected or addressed
Roof Soft Above Girls Locker Room At The
Tucker Middle School 2 Building 4010 Roofing Asphalt Shingle Roof Covering Repair A Deficiency has been corrected or addressed
Back Of Building (Behind Hvac Unity)
Tucker Middle School 3 Building 4010 Mechanical Testing And Balancing A Deficiency has been corrected or addressed
Tucker Middle School 3 Building 4010 Site Car Accessible Parking Spaces Restiriping Paint Faded A Deficiency has been corrected or addressed
Tucker Middle School 3 Building 4010 Electrical Public Address System Head-End Requires Replacement A Deficiency has been corrected or addressed
Tucker Middle School 3 Building 4010 Electrical Public Address System Replacement, Non-main Building A Deficiency has been corrected or addressed
Vanderlyn Elementary School 3 Site Playground Equipment Replacement Rusted Equipment A Deficiency has been corrected or addressed
Batteries And Test Switches Not Working On
Vanderlyn Elementary School 1 Building 2010 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Wall Pack Emergency Lights
Vanderlyn Elementary School 1 Building 2010 Fire and Life Safety Emergency Exit Signage Replacement Some Exit Signs Are Not Working A Deficiency has been corrected or addressed
Vanderlyn Elementary School 1 Building 2011 Fire and Life Safety Emergency Exit Signage Replacement Exit Signs Not Working A Deficiency has been corrected or addressed
26 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Vanderlyn Elementary School 1 Building 2020 Fire and Life Safety Emergency Exit Signage Replacement All 4 Exit Signs A Deficiency has been corrected or addressed
Vanderlyn Elementary School 3 Building 2011 Roofing Debris In Gutter Removal A Deficiency has been corrected or addressed
Vanderlyn Elementary School 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility A Deficiency has been corrected or addressed
Vanderlyn Elementary School 3 Building 2011 Exterior Exterior Metal Door Repainting A Deficiency has been corrected or addressed
Vanderlyn Elementary School 3 Building 2010 Exterior Exterior Metal Door Repainting Paint Peeling On All Exterior Doors A Deficiency has been corrected or addressed
Vanderlyn Elementary School 3 Building 2010 Roofing Modified Covering Has Blisters That Should Be Repaired Large Blister A Deficiency has been corrected or addressed
Vanderlyn Elementary School 3 Building 2010 Roofing Roof Drain Cleaning A Deficiency has been corrected or addressed
Vanderlyn Elementary School 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing A Deficiency has been corrected or addressed
Vanderlyn Elementary School 3 Building 2010 Roofing Roof Access Ladder Replacement Access Ladders Are Rusting Badly A Deficiency has been corrected or addressed
Wadsworth Magnet School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Wadsworth Magnet School 1 Building 2010 Fire and Life Safety Wall Pack Lighting Replacement Mech Room. Light Not Working A Deficiency has been corrected or addressed
Wadsworth Magnet School 3 Site Asphalt Driveway Replacement Damaged, Main Driveway A Deficiency has been corrected or addressed
Replace 7700 Sf Of Asphalt Blacktop For
Wadsworth Magnet School 3 Site Asphalt Walks Replacement A Deficiency has been corrected or addressed
Basketball Court. Damaged Near Playground.
Wadsworth Magnet School 3 Site Concrete Walks Replacement Damaged, Various A Deficiency has been corrected or addressed
Warren Technical Chamblee 3 Building 4010 Roofing Debris In Gutter Removal Tree Debris A Deficiency has been corrected or addressed
Some Ds Are Disconnected From Boots Or
Warren Technical Chamblee 3 Building 4010 Roofing Metal Downspout Replacement A Deficiency has been corrected or addressed
Boots Are Clogged, So Ds Are Overflowing.
Warren Technical Chamblee 3 Building 4011 Roofing Roof Drain Cleaning Tree Debris A Deficiency has been corrected or addressed
Warren Technical Chamblee 3 Building 4010 Mechanical Kitchen Air/Exhaust Repair Not Operating A Deficiency has been corrected or addressed
William Bradley Bryant Technology Center 3 Building 8010 Roofing Roof Drain Cleaning A Deficiency has been corrected or addressed
William Bradley Bryant Technology Center 1 Building 8010 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
William Bradley Bryant Technology Center 1 Building 8010 Fire and Life Safety Fire Alarm Panel Replacement A Deficiency has been corrected or addressed
William Buck Godfrey Stadium 1 Building 8010 Fire and Life Safety Security Alarm Replacement A Deficiency has been corrected or addressed
William Buck Godfrey Stadium 1 Building 8010 Fire and Life Safety Fire Alarm Replacement Not Installed A Deficiency has been corrected or addressed
William Buck Godfrey Stadium 2 Building 8010 Fire and Life Safety Emergency Exit Signage Is Missing Not Installed A Deficiency has been corrected or addressed
Woodridge Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Woodridge Elementary School 1 Building 2010 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Woodridge Elementary School 1 Building 2010 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Woodridge Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Woodridge Elementary School 1 Building 2010 Fire and Life Safety Security Alarm Camera Replacement All 4 Camera'S Not Working A Deficiency has been corrected or addressed
Woodridge Elementary School 1 Building 2011 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Woodridge Elementary School 1 Building 2020 Fire and Life Safety Wall Pack Lighting Replacement A Deficiency has been corrected or addressed
Woodridge Elementary School 1 Building 2020 Fire and Life Safety Emergency Exit Signage Replacement A Deficiency has been corrected or addressed
Woodridge Elementary School 1 Building 2020 Fire and Life Safety Fire Alarm Replacement A Deficiency has been corrected or addressed
Woodridge Elementary School 3 Building 2011 Plumbing Urinal Repair Repair - Boys 947.1 A Deficiency has been corrected or addressed
Woodridge Elementary School 3 Site Asphalt Driveway Replacement Around Kitchen Front A Deficiency has been corrected or addressed
Woodridge Elementary School 3 Site Concrete Walks Replacement Outside Room 907, 913, 903 A Deficiency has been corrected or addressed
Woodridge Elementary School 3 Building 2011 Exterior Exterior Metal Door Repainting All Doors A Deficiency has been corrected or addressed
Woodridge Elementary School 3 Building 2010 Exterior Exterior Metal Door Repainting Around Building A Deficiency has been corrected or addressed
Woodridge Elementary School 3 Building 2020 Exterior Exterior Metal Door Repainting Main Doors A Deficiency has been corrected or addressed
Woodridge Elementary School 3 Building 2010 Exterior Brick Exterior Repair Outside Mech Room A Deficiency has been corrected or addressed
Woodridge Elementary School 3 Building 2010 Plumbing Toilet Replacement Replace Toilets At Classroom 913. A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2010 Mechanical Heat Exchanger Replacement Mech Room 918.3 A Deficiency has been corrected or addressed
Woodridge Elementary School 3 Building 2010 Mechanical Circulation Pump Replacement 7.5Hp - Mech 918.3 A Deficiency has been corrected or addressed
Woodridge Elementary School 3 Building 2010 Mechanical Circulation Pump Replacement 15Hp - Mech 918.3 A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2010 Mechanical Exterior Metal Cooling Tower Replacement 150 Tons - Mech Room 918.3 A Deficiency has been corrected or addressed
2.5 Tons - Water Source Heat Pumps -
Woodridge Elementary School 2 Building 2010 Mechanical Package DX Unit Replacement A Deficiency has been corrected or addressed
Replace Entire Building
3.5 Tons - Water Source Heat Pumps -
Woodridge Elementary School 2 Building 2010 Mechanical Package DX Unit Replacement A Deficiency has been corrected or addressed
Replace Entire Building
Woodridge Elementary School 3 Building 2010 Mechanical Testing And Balancing A Deficiency has been corrected or addressed
2.5 Tons - Water Source Heat Pumps - Entire
Woodridge Elementary School 2 Building 2011 Mechanical Package DX Unit Replacement A Deficiency has been corrected or addressed
Building - Replace.
3.5 Tons - Water Source Heat Pumps - Entire
Woodridge Elementary School 2 Building 2011 Mechanical Package DX Unit Replacement A Deficiency has been corrected or addressed
Building - Replace
Woodridge Elementary School 3 Building 2011 Mechanical Testing And Balancing A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2011 Electrical Panelboard Replacement Janitor 947.3 A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2020 Roofing Gutter Joint Repair Behind Gym A Deficiency has been corrected or addressed
27 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Woodridge Elementary School 3 Building 2020 Roofing Membrane Flashing At Parapet (>2') Repair Behind Gym A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2020 Mechanical Electric Unit Heater Replacement Gym Toilets And Controls A Deficiency has been corrected or addressed
Woodridge Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant All Classroom And Other Area. A Deficiency has been corrected or addressed
Woodridge Elementary School 3 Building 2011 Interior Existing Door Hardware Is Not ADA Compliant Classroom And Restroom A Deficiency has been corrected or addressed
Woodridge Elementary School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsMain (Modify Full)
Office A Deficiency has been corrected or addressed
Woodridge Elementary School 3 Building 2010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
Cafeteria Stage A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2010 Electrical Switchgear Replacement 1000 Amps - Mech 918.3 A Deficiency has been corrected or addressed
Woodridge Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement Old Building Wiring A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Mech 918.3 A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Janitor 918.8 A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Mech 918.3 A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Janitor 905.4 A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Janitor 906.6 A Deficiency has been corrected or addressed
Woodridge Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Old T8 Lamps A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2010 Electrical Panelboard Replacement 50A - Janitor 918.8 A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2010 Electrical Panelboard Replacement 50A A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2010 Electrical Panelboard Replacement 50A A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2010 Electrical Panelboard Replacement 50A Janitor 906.6 A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2010 Electrical Panelboard Replacement 50A Janitor 905.4 A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2010 Electrical Panelboard Replacement 50A - Mech 918.3 A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2010 Electrical Panelboard Replacement Janitor 918.8 A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2010 Electrical Panelboard Replacement A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2010 Electrical Panelboard Replacement A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2010 Electrical Panelboard Replacement A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2010 Electrical Panelboard Replacement Janitor 905.4 A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2010 Electrical Panelboard Replacement Janitor 906.6 A Deficiency has been corrected or addressed
Woodridge Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building A Deficiency has been corrected or addressed
Woodridge Elementary School 3 Building 2011 Electrical Interior Power Wiring Replacement Old Building Wiring A Deficiency has been corrected or addressed
Woodridge Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement Old T8 Lamps A Deficiency has been corrected or addressed
Woodridge Elementary School 2 Building 2011 Electrical Panelboard Replacement Janitor 947.3 A Deficiency has been corrected or addressed
Intercom System Is Served From Building
Woodridge Elementary School 3 Building 2011 Electrical Public Address System Replacement, Non-main Building A Deficiency has been corrected or addressed
2010
Woodridge Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement Old T8 Lamps A Deficiency has been corrected or addressed
Intercom System Is Served From Building
Woodridge Elementary School 3 Building 2020 Electrical Public Address System Replacement, Non-main Building A Deficiency has been corrected or addressed
2010
Woodward Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Woodward Elementary School 1 Building 2010 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Woodward Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Panel Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Woodward Elementary School 1 Building 2010 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Woodward Elementary School 1 Building 2011 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Woodward Elementary School 1 Building 2011 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Woodward Elementary School 1 Building 2012 Fire and Life Safety Security Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Woodward Elementary School 1 Building 2012 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Woodward Elementary School 1 Building 2020 Fire and Life Safety Fire Alarm Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Woodward Elementary School 3 Building 2010 Roofing Debris In Gutter Removal Pine Needles And All A Deficiency has been corrected or addressed
Woodward Elementary School 3 Building 2011 Roofing Debris In Gutter Removal Pine Needles And All A Deficiency has been corrected or addressed
Woodward Elementary School 3 Building 2012 Roofing Debris In Gutter Removal Pine Needles And All Location A Deficiency has been corrected or addressed
Woodward Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Pine Needles And Front And Back A Deficiency has been corrected or addressed
Woodward Elementary School 2 Building 2020 Roofing Gutter Joint Repair Leaking And Front And Back A Deficiency has been corrected or addressed
Wynbrooke Elementary School 3 Site Playground Equipment Replacement A Deficiency has been corrected or addressed
Wynbrooke Elementary School 2 Building 2010 Roofing Modified Roof Covering Replacement Roof Leaking A Deficiency has been corrected or addressed
Wynbrooke Elementary School 2 Building 2010 Roofing Single-Ply Membrane Roof Covering Replacement Roof Leaking A Deficiency has been corrected or addressed
Wynbrooke Elementary School 1 Building 2010 Fire and Life Safety Emergency Exit Signage Replacement Beyond Useful Life A Deficiency has been corrected or addressed
Administrative and Instructional Complex (AIC) 3 Building 9010 Exterior Exterior Metal Door Repainting North Side Of Building B Deficiency can be corrected by DCSD Staff
Administrative and Instructional Complex (AIC) 3 Building 9010 Roofing Modified Covering Has Blisters That Should Be Repaired B Deficiency can be corrected by DCSD Staff
Administrative and Instructional Complex (AIC) 3 Building 9012 Roofing Modified Covering Has Blisters That Should Be Repaired B Deficiency can be corrected by DCSD Staff
Arabia Mountain High School 3 Building 5010 Interior Athletic Sport Flooring Replacement Damaged B Deficiency can be corrected by DCSD Staff
Arabia Mountain High School 3 Building 5010 Roofing Gutter Replacement Damaged B Deficiency can be corrected by DCSD Staff
Arabia Mountain High School 3 Building 5010 Roofing Modified Covering Has Blisters That Should Be Repaired Large B Deficiency can be corrected by DCSD Staff
Arabia Mountain High School 2 Building 5020 Roofing Plexiglass/Polycarbonate Sheet Roof Replacement Beyond Useful Life - Baten Failing B Deficiency can be corrected by DCSD Staff
28 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Soil Erosion Sink Hole At Downspout Located
At Outside Corner Of Aerobics (A201). Soil
Arabia Mountain High School 3 Site Site Requires Civil/Drainage Study B Deficiency can be corrected by DCSD Staff
Erosion At Softball Field And Tennis Storage
Building Perimeter.
Austin Elementary School 2 Building 2010 Conveyances Elevator Cab And/Or Controls Repair Bottom B Deficiency can be corrected by DCSD Staff
Avondale High DSA 3 Building 5022 Specialties Auditorium Seating Replacement B Deficiency can be corrected by DCSD Staff
Avondale High DSA 3 Building 5011 Exterior Brick Exterior Repair B Deficiency can be corrected by DCSD Staff
Avondale High DSA 3 Building 5011 Exterior Brick Exterior Repointing B Deficiency can be corrected by DCSD Staff
Avondale High DSA 3 Building 5022 Exterior Brick Exterior Repointing B Deficiency can be corrected by DCSD Staff
Avondale High DSA 3 Building 5010 Roofing Membrane Flashing At Parapet (>2') Repair B Deficiency can be corrected by DCSD Staff
Crosswalk From ADA Spots (Asphalt) Is
Bob Mathis Elementary School 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility
Cracked. Included In Site Calculation. B Deficiency can be corrected by DCSD Staff
Replace And Restripe.
Briar Vista Elementary School 3 Building 2010 Exterior Brick Exterior Repointing Various Areas B Deficiency can be corrected by DCSD Staff
Briar Vista Elementary School 3 Building 2011 Exterior Brick Exterior Repointing Various Small Areas B Deficiency can be corrected by DCSD Staff
Briar Vista Elementary School 3 Site Site Requires Civil/Drainage Study Corner Of Building 2012 B Deficiency can be corrected by DCSD Staff
Briarlake Elementary School 3 Building 2010 Roofing Gutter Replacement Damaged By Truck B Deficiency can be corrected by DCSD Staff
Briarlake Elementary School 2 Building 2010 Roofing Modified Membrane Has Holes That Should Be Repaired Reported Roof Leaks B Deficiency can be corrected by DCSD Staff
Briarlake Elementary School 2 Building 2011 Roofing Modified Membrane Has Holes That Should Be Repaired Reported Roof Leaks B Deficiency can be corrected by DCSD Staff
Briarlake Elementary School 2 Building 2012 Roofing Modified Membrane Has Holes That Should Be Repaired Reported Roof Leaks B Deficiency can be corrected by DCSD Staff
Cracked And Worn Out. Replace Expansion
Brockett Elementary School 3 Building 2020 Exterior Brick Exterior Repair B Deficiency can be corrected by DCSD Staff
Joint.
Brockett Elementary School 2 Building 2011 Exterior Concrete Pre-Cast Panel Replacement (Bldg SF) Cracked And Spalling B Deficiency can be corrected by DCSD Staff
Brockett Elementary School 2 Building 2012 Exterior Concrete Pre-Cast Panel Replacement (Bldg SF) Cracked And Spalling B Deficiency can be corrected by DCSD Staff
Gfc Receptacles + Regulator In Multiple
Browns Mill Elementary School 3 Building 2010 Electrical Electrical Receptacle Replacement B Deficiency can be corrected by DCSD Staff
Locations
Browns Mill Elementary School 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility B Deficiency can be corrected by DCSD Staff
Browns Mill Elementary School 2 Building 2010 Roofing Single-Ply Membrane Has Holes That Should Be Repaired Significant Holes B Deficiency can be corrected by DCSD Staff
Browns Mill Elementary School 3 Building 2010 Mechanical Small Diameter Exhausts/Hoods Replacement Damaged B Deficiency can be corrected by DCSD Staff
South Central Segment Of Roof Near Middle
Courtyard, Rooms 205, 207, 209, 307 - Need
Browns Mill Elementary School 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing B Deficiency can be corrected by DCSD Staff
To Have Insulation Adjustment To Reduce
Ponding.
Canby Lane Elementary School 3 Building 2030 Roofing Batt Insulation Under Metal Roof Deck Split-Open And Possible Water Damage B Deficiency can be corrected by DCSD Staff
Canby Lane Elementary School 3 Building 2020 Exterior Brick Exterior Repointing Weathered B Deficiency can be corrected by DCSD Staff
Canby Lane Elementary School 3 Building 2030 Exterior Brick Exterior Repointing Weathered B Deficiency can be corrected by DCSD Staff
Canby Lane Elementary School 2 Building 2030 Roofing Gutter Joint Repair Separation Joints B Deficiency can be corrected by DCSD Staff
Canby Lane Elementary School 3 Building 2010 Interior Rubber Flooring Replacement Beyond Useful Life B Deficiency can be corrected by DCSD Staff
Canby Lane Elementary School 2 Building 2010 Exterior Slate Tile Wall Replacement Cracked B Deficiency can be corrected by DCSD Staff
Cedar Grove Elementary School 3 Building 2010 Exterior Brick Exterior Repointing Eroded B Deficiency can be corrected by DCSD Staff
Cedar Grove Elementary School 3 Building 2011 Exterior Brick Exterior Repointing Eroded B Deficiency can be corrected by DCSD Staff
Cedar Grove Elementary School 3 Building 2012 Exterior Brick Exterior Repointing Eroded B Deficiency can be corrected by DCSD Staff
Cedar Grove Elementary School 2 Building 2010 Exterior Hardi-Plank Exterior Replacement (Bldg SF) Damaged B Deficiency can be corrected by DCSD Staff
Cedar Grove Elementary School 2 Building 2011 Exterior Hardi-Plank Exterior Replacement (Bldg SF) Damaged B Deficiency can be corrected by DCSD Staff
Cedar Grove Elementary School 3 Building 2011 Plumbing Toilet Plumbing Fixture Repair B Deficiency can be corrected by DCSD Staff
Cedar Grove High School 3 Building 5010 Exterior Brick Exterior Repointing Repoint Eroded And Cracked Brick B Deficiency can be corrected by DCSD Staff
Some Of The Brick Is Eroded And Weathered.
Cedar Grove High School 3 Building 5011 Exterior Brick Exterior Repointing B Deficiency can be corrected by DCSD Staff
Repoint
Cedar Grove High School 3 Building 5012 Exterior Brick Exterior Repointing Brick Is Eroded And Deteriorated. Repoint B Deficiency can be corrected by DCSD Staff
Concrete Is Spalling Near Windows Shades.
Cedar Grove High School 2 Building 5010 Exterior Concrete Pre-Cast Panel Replacement (Bldg SF) B Deficiency can be corrected by DCSD Staff
Repair
Cedar Grove High School 3 Site Concrete Walks Replacement Concrete Sidewalk Is Cracked And Spalling B Deficiency can be corrected by DCSD Staff
Cedar Grove High School 3 Building 5010 Roofing Membrane Flashing At Parapet (>2') Repair Repair Cracked Membrane Flashing B Deficiency can be corrected by DCSD Staff
Numerous Blisters Present Throughout The
Entire Roof: Roof Was Either Installed
Cedar Grove High School 3 Building 5011 Roofing Modified Covering Has Blisters That Should Be Repaired B Deficiency can be corrected by DCSD Staff
Incorrectly Or Major Vapor Barrier Issues Are
Occurring
29 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Rubber Tile Is Aged Beyond Useful Life.
Cedar Grove High School 3 Building 5010 Interior Rubber Flooring Replacement B Deficiency can be corrected by DCSD Staff
Replace
North Side Against The Exterior Wall Has
Significant Issues With Water Ponding. Signs
Of Soil Erosion Are Present. Floor Slab Nears
Cedar Grove High School 3 Site Site Requires Civil/Drainage Study B Deficiency can be corrected by DCSD Staff
Rooms 223, 231,230 Is Sloping Towards The
Courtyard: Possible Sign Of A Drainage Issue
Undermining The Exterior Wall
Metal Roof: Open Joints And Cracked Sealant;
Cedar Grove Middle School 3 Building 4010 Interior Expansion Joints Missing or Deteriorated B Deficiency can be corrected by DCSD Staff
Roof Leaks (Staff Mentioned)
Cedar Grove Middle School 3 Building 4010 Exterior Exterior Metal Door Repainting Faded B Deficiency can be corrected by DCSD Staff
Chamblee High School 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility B Deficiency can be corrected by DCSD Staff
Chamblee High School 3 Building 5010 Interior Interior Door Replacement Water Damaged And Kitchen B Deficiency can be corrected by DCSD Staff
Missing Opening Arm. Roof Hatch Safety Rail
Chamblee High School 3 Building 5010 Roofing Roof Operable Hatch Repair B Deficiency can be corrected by DCSD Staff
Need Repair.
9X6 - Repair Window Sill Of Two Windows At
Chamblee Middle School 3 Building 4010 Exterior Aluminum Window Repair Front Of School On Third Floor. Sill Sheet B Deficiency can be corrected by DCSD Staff
Metal Coming Off.
Repair Damaged Dryvit At Kitchen Loading
Chamblee Middle School 2 Building 4010 Exterior Dryvit Exterior Repair B Deficiency can be corrected by DCSD Staff
Dock Damaged By Trucks.
Chapel Hill Middle School 3 Building 4010 Exterior Brick Exterior Repointing Cracked B Deficiency can be corrected by DCSD Staff
Clarkston High School 3 Building 5011 Roofing Debris In Gutter Removal Clogged With Debris B Deficiency can be corrected by DCSD Staff
Clarkston High School 3 Building 5012 Roofing Debris In Gutter Removal Clogged With Leaf Debris B Deficiency can be corrected by DCSD Staff
Reported Leaks At Gym Wall Below, Repair
Clarkston High School 3 Building 5012 Roofing Membrane Flashing At Parapet (>2') Repair B Deficiency can be corrected by DCSD Staff
Flashing
Columbia Elementary School 3 Building 2020 Interior Athletic Sport Flooring Replacement Bubbling B Deficiency can be corrected by DCSD Staff
Columbia Elementary School 3 Building 2010 Exterior Brick Exterior Repointing Around Kitchen And Outside Room 208 B Deficiency can be corrected by DCSD Staff
Columbia High School 3 Building 5011 Exterior Aluminum Window Repair Missing Weather Stripping On The Inside B Deficiency can be corrected by DCSD Staff
Columbia High School 3 Building 5020 Roofing Debris In Gutter Removal Overgrown Vegetation B Deficiency can be corrected by DCSD Staff
Columbia High School 3 Building 5011 Electrical Electrical Receptacle Replacement Pool Area B Deficiency can be corrected by DCSD Staff
Columbia High School 3 Building 5011 Roofing Gutter Replacement Damaged And Missing B Deficiency can be corrected by DCSD Staff
Columbia High School 3 Building 5016 Roofing Membrane Flashing At Parapet (>2') Repair Damaged B Deficiency can be corrected by DCSD Staff
Columbia High School 3 Building 5011 Roofing Metal Downspout Replacement Damaged And Missing B Deficiency can be corrected by DCSD Staff
Concession 504.1 With GFI Protective Device,
Columbia Middle School 3 Building 4010 Electrical Electrical Receptacle Installation B Deficiency can be corrected by DCSD Staff
Lab 811-Circuit That Is Shorted At Device
Repair Sidewalk At Interior Courtyard.
DeKalb Elementary School of the Arts 3 Site Concrete Walks Replacement B Deficiency can be corrected by DCSD Staff
Concrete Surface Is Spalling Off.
DeKalb Elementary School of the Arts 2 Building 4010 Mechanical Package Roof Top Unit Replacement Dead - Roof B Deficiency can be corrected by DCSD Staff
DeKalb Elementary School of the Arts 3 Building 4010 Mechanical Small Diameter Exhausts/Hoods Replacement Beyond Useful Life B Deficiency can be corrected by DCSD Staff
DeKalb Elementary School of the Arts 3 Building 4010 Mechanical Testing And Balancing B Deficiency can be corrected by DCSD Staff
Doraville Administrative 3 Site Concrete Driveways Replacement Cracked B Deficiency can be corrected by DCSD Staff
Doraville Administrative 3 Building 8010 Exterior Exterior Metal Door Repainting Paint B Deficiency can be corrected by DCSD Staff
Doraville Administrative 3 Building 8010 Interior Interior Brick/Stone Replacement (Bldg SF) Damaged B Deficiency can be corrected by DCSD Staff
Bolt Holding Roof Hatch On The Top Has
Doraville Administrative 3 Building 8010 Roofing Roof Operable Hatch Repair B Deficiency can be corrected by DCSD Staff
Cracked "The 2X8"
Doraville United Elementary School 2 Building 2010 Conveyances Elevator Cab And/Or Controls Repair B Deficiency can be corrected by DCSD Staff
Doraville United Elementary School 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility
Court Yard Plan North Exit Into Building B Deficiency can be corrected by DCSD Staff
Plan South Of Admin Metal Roof Coming
Doraville United Elementary School 3 Building 2010 Roofing Membrane Flashing At Parapet (>2') Repair B Deficiency can be corrected by DCSD Staff
Undone
Druid Hills Middle School 3 Building 4011 Interior Athletic Sport Flooring Replacement B Deficiency can be corrected by DCSD Staff
Druid Hills Middle School 3 Building 4010 Exterior Brick Exterior Repointing B Deficiency can be corrected by DCSD Staff
Druid Hills Middle School 3 Building 4011 Exterior Brick Exterior Repointing B Deficiency can be corrected by DCSD Staff
Druid Hills Middle School 3 Building 4010 Exterior Exterior Metal Door Repainting B Deficiency can be corrected by DCSD Staff
Druid Hills Middle School 3 Building 4010 Exterior Metal Exterior Door Repair B Deficiency can be corrected by DCSD Staff
Dunaire Elementary School 3 Building 2020 Roofing Metal Downspout Replacement Damaged B Deficiency can be corrected by DCSD Staff
Dunaire Elementary School 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding B Deficiency can be corrected by DCSD Staff
Dunaire Elementary School 3 Building 2011 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding B Deficiency can be corrected by DCSD Staff
Dunaire Elementary School 3 Building 2012 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding B Deficiency can be corrected by DCSD Staff
30 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Dunwoody Elementary School 3 Site Concrete Walks Replacement B Deficiency can be corrected by DCSD Staff
Blistering On East Edge Of The Roof Over
Mech Room And Elec 1148. No Apparent
Leaks Below. Ne Part Of Building Presents
Dunwoody Elementary School 3 Building 2010 Roofing Modified Covering Has Blisters That Should Be Repaired B Deficiency can be corrected by DCSD Staff
Water Leaks At 2Nd Floor Hallway (Next To
Planning Room 2106). Also Custodial Closet
At 1127 (1St Floor). Repaired By Custodian.
Ne Corner At Stage. Room 1130.1 At
Dunwoody Elementary School 3 Building 2010 Interior Rubber Flooring Replacement B Deficiency can be corrected by DCSD Staff
Cafeteria, Replace Rubber Flooring Peeling.
Dunwoody High School 3 Building 5013 Specialties Auditorium Seating Replacement B Deficiency can be corrected by DCSD Staff
Repair Sidewalk To The East Of Main Building
Dunwoody High School 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility B Deficiency can be corrected by DCSD Staff
(8Lf) And Near Building 5012 (40 Lf)
Dunwoody High School 3 Building 5013 Roofing Modified Covering Has Blisters That Should Be Repaired B Deficiency can be corrected by DCSD Staff
Roof Leaks Above Room 1311 Per Interview
Dunwoody High School 2 Building 5011 Roofing Modified Roof Covering Replacement B Deficiency can be corrected by DCSD Staff
With Site Representatives
Dunwoody High School 3 Building 5012 Interior Rubber Flooring Replacement B Deficiency can be corrected by DCSD Staff
Dunwoody High School 2 Building 5012 Electrical Stage Lighting Replacement B Deficiency can be corrected by DCSD Staff
No Access To Roof, Based On Interview With
Dunwoody High School 3 Building 5010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing B Deficiency can be corrected by DCSD Staff
Plant Engineer
1.5 Tons Doesn't Work, Above Room 137. No
Eagle Woods Academy 2 Building 8010 Mechanical Air Cooled Condenser Replacement B Deficiency can be corrected by DCSD Staff
Roof Access For Picture.
Eagle Woods Academy 2 Building 8030 Roofing Asphalt Shingle Roof Covering Replacement No Good View And Access To Roof B Deficiency can be corrected by DCSD Staff
Eagle Woods Academy 2 Building 8010 Mechanical Ductless Split System AC Replacement 1.5 Tons Doesn't Work Room 137 B Deficiency can be corrected by DCSD Staff
Add Gutter And Downspouts (2) At North End
Eagle Woods Academy 3 Building 8030 Roofing Metal Downspout Installation Of Shed Roof (Low Point) Non-Existent, B Deficiency can be corrected by DCSD Staff
Currently.
Early Learning Academy 3 Building 2010 Exterior Brick Exterior Repointing Weathered Mortar B Deficiency can be corrected by DCSD Staff
Early Learning Academy 3 Building 2011 Exterior Brick Exterior Repointing Weathered B Deficiency can be corrected by DCSD Staff
Early Learning Academy 3 Site Concrete Walks Replacement Cracked B Deficiency can be corrected by DCSD Staff
Early Learning Academy 3 Building 2010 Interior Rubber Flooring Replacement Beyond Useful Life B Deficiency can be corrected by DCSD Staff
East Campus #1 DeKalb Alternative 3 Building 8010 Exterior Brick Exterior Repointing East Side Of Building B Deficiency can be corrected by DCSD Staff
East Campus #1 DeKalb Alternative 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility
Nw Building 8010 And Stairs To Building 8020 B Deficiency can be corrected by DCSD Staff
East Campus #1 DeKalb Alternative 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility
Nw Building 8010 And Stairs To Building 8020 B Deficiency can be corrected by DCSD Staff
East Campus #1 DeKalb Alternative 2 Electrical Exterior Electrical Enclosure Repair South Building 8010, North Building 8020 B Deficiency can be corrected by DCSD Staff
East Campus #1 DeKalb Alternative 3 Building 8010 Exterior Exterior Metal Door Repainting B Deficiency can be corrected by DCSD Staff
East Campus #2 Transportation 3 Building 8020 Roofing Gutter Replacement B Deficiency can be corrected by DCSD Staff
East Campus #2 Transportation 3 Building 8020 Exterior Handrail Replacement B Deficiency can be corrected by DCSD Staff
Concrete Stairs - Metal Railing At South Exit
East Campus #2 Transportation 3 Exterior Handrail Replacement B Deficiency can be corrected by DCSD Staff
Not Secure
East Campus #2 Transportation 3 Building 8030 Roofing Metal Downspout Installation B Deficiency can be corrected by DCSD Staff
East Campus #2 Transportation 3 Building 8020 Roofing Metal Downspout Replacement B Deficiency can be corrected by DCSD Staff
Building Engineer Reported Leaks From The
Edward L. Bouie, Sr. Elementary School 3 Building 2010 Mechanical HVAC Piping System Repair Chill Water Line Over Hallways 100 And 200 - B Deficiency can be corrected by DCSD Staff
Estimated Qty
Edward L. Bouie, Sr. Elementary School 3 Site Parking Or Roadway Curbs Replacement Damaged Curb Near Storage Shed B Deficiency can be corrected by DCSD Staff
Edward L. Bouie, Sr. Elementary School 2 Building 2010 Plumbing Water Heater Replacement Beyond Useful Life 232.2 B Deficiency can be corrected by DCSD Staff
Principal States That Pole Lighting Is Missing
Evansdale Elementary School 3 Electrical Area Lighting Installation B Deficiency can be corrected by DCSD Staff
And Needed
Evansdale Elementary School 2 Building 2010 Exterior Brick Exterior Replacement (Bldg SF) Cracked Wall B Deficiency can be corrected by DCSD Staff
Evansdale Elementary School 2 Building 2011 Exterior Brick Exterior Replacement (Bldg SF) Wall Cracked B Deficiency can be corrected by DCSD Staff
Evansdale Elementary School 3 Building 2010 Exterior Brick Exterior Repointing Weathered And Eroded B Deficiency can be corrected by DCSD Staff
Evansdale Elementary School 3 Building 2011 Exterior Brick Exterior Repointing Weathered And Eroded B Deficiency can be corrected by DCSD Staff
Evansdale Elementary School 3 Site Concrete Walks Replacement Cracked B Deficiency can be corrected by DCSD Staff
Evansdale Elementary School 3 Site Parking Or Roadway Curbs Replacement Cracked And Damaged B Deficiency can be corrected by DCSD Staff
Evansdale Elementary School 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Water Ponding Issues B Deficiency can be corrected by DCSD Staff
31 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Evansdale Elementary School 3 Building 2011 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Water Ponding Issues B Deficiency can be corrected by DCSD Staff
Fernbank Elementary School 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Around Rtu 12 B Deficiency can be corrected by DCSD Staff
Repoint Stone With New Mortar, It's Scraping
Fernbank Science Center 3 Building 8010 Exterior Brick Exterior Repointing B Deficiency can be corrected by DCSD Staff
Off With Hands And Fingers. Cause Leaks.
Fernbank Science Center 3 Building 8020 Exterior Exterior Metal Door Repainting Rusted And Dirty B Deficiency can be corrected by DCSD Staff
Replace Door At Room 3 Chem Lab Damaged
Fernbank Science Center 3 Building 8020 Interior Interior Door Replacement B Deficiency can be corrected by DCSD Staff
At Bottom.
Repair Door Panel At Exit On North Wall
Fernbank Science Center 2 Building 8010 Exterior Wood Exterior Door Repair B Deficiency can be corrected by DCSD Staff
Outside Boiler Room.
Flat Rock Elementary School 3 Building 2010 Mechanical Kitchen Air/Exhaust Installation 10'-0"X18'-0" B Deficiency can be corrected by DCSD Staff
Flat Rock Elementary School 3 Building 2010 Mechanical Testing And Balancing B Deficiency can be corrected by DCSD Staff
Flat Shoals Elementary School 3 Site Concrete Walks Replacement Cracked B Deficiency can be corrected by DCSD Staff
Flat Shoals Elementary School 2 Building 2040 Roofing Gutter Joint Repair B Deficiency can be corrected by DCSD Staff
Flat Shoals Elementary School 3 Building 2020 Mechanical Small Diameter Exhausts/Hoods Replacement Beyond Useful Life B Deficiency can be corrected by DCSD Staff
Freedom Middle School 3 Building 4010 Exterior Exterior Metal Door Repainting Repaint Outside Face B Deficiency can be corrected by DCSD Staff
Freedom Middle School 3 Building 4010 Specialties Retractable Bleacher Repair Retractable. Repair Stain B Deficiency can be corrected by DCSD Staff
Hambrick Elementary School 3 Building 2010 Exterior Exterior Metal Door Repainting Paint Beyond Useful Life B Deficiency can be corrected by DCSD Staff
Hambrick Elementary School 3 Building 2012 Exterior Exterior Metal Door Repainting Paint Peeling B Deficiency can be corrected by DCSD Staff
Hambrick Elementary School 3 Building 2010 Exterior Metal Exterior Door Repair Repair Glass Window Panes B Deficiency can be corrected by DCSD Staff
Henderson Middle School 3 Site Concrete Walks Replacement B Deficiency can be corrected by DCSD Staff
John Lewis Elementary School 3 Building 2010 Plumbing Condensate Drain Repair Broken Roof B Deficiency can be corrected by DCSD Staff
John Lewis Elementary School 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility
Courtyard Plan North B Deficiency can be corrected by DCSD Staff
John Lewis Elementary School 3 Building 2010 Roofing Membrane Flashing At Parapet (>2') Repair Level 2 B Deficiency can be corrected by DCSD Staff
John Lewis Elementary School 3 Building 2010 Roofing Modified Covering Has Blisters That Should Be Repaired Lvl3, Lvl2, Lvl1 B Deficiency can be corrected by DCSD Staff
Kelley Lake Elementary School 3 Building 2012 Exterior Brick Exterior Repair B Deficiency can be corrected by DCSD Staff
Kelley Lake Elementary School 3 Site Concrete Walks Replacement B Deficiency can be corrected by DCSD Staff
Kelley Lake Elementary School 3 Building 2010 Electrical Electrical Receptacle Installation B Deficiency can be corrected by DCSD Staff
Kelley Lake Elementary School 3 Building 2011 Electrical Electrical Receptacle Installation Replace B Deficiency can be corrected by DCSD Staff
Kelley Lake Elementary School 3 Building 2010 Roofing Metal Downspout Replacement B Deficiency can be corrected by DCSD Staff
Kelley Lake Elementary School 3 Building 2020 Roofing Metal Downspout Replacement B Deficiency can be corrected by DCSD Staff
Kelley Lake Elementary School 3 Building 2010 Roofing Roof Operable Hatch Repair B Deficiency can be corrected by DCSD Staff
Kingsley Elementary School 3 Building 2011 Exterior Brick Exterior Repair B Deficiency can be corrected by DCSD Staff
Kingsley Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Leaves B Deficiency can be corrected by DCSD Staff
Kingsley Elementary School 3 Building 2010 Exterior Exterior Metal Door Repainting Rusted B Deficiency can be corrected by DCSD Staff
Kingsley Elementary School 3 Building 2011 Roofing Roof Drain Cleaning Leaves B Deficiency can be corrected by DCSD Staff
Lakeside High School 3 Building 5012 Roofing Debris In Gutter Removal Clogged B Deficiency can be corrected by DCSD Staff
Lakeside High School 3 Building 5020 Roofing Debris In Gutter Removal Behind Building B Deficiency can be corrected by DCSD Staff
Lakeside High School 3 Building 5011 Exterior Exterior Metal Door Repainting B Deficiency can be corrected by DCSD Staff
Lakeside High School 3 Building 5012 Exterior Exterior Metal Door Repainting All Doors B Deficiency can be corrected by DCSD Staff
Lakeside High School 3 Building 5013 Exterior Exterior Metal Door Repainting All Doors B Deficiency can be corrected by DCSD Staff
Lakeside High School 3 Building 5014 Exterior Exterior Metal Door Repainting Behind Auditorium Stage And Mech Room B Deficiency can be corrected by DCSD Staff
Lakeside High School 2 Building 5020 Roofing Gutter Joint Repair Behind Building B Deficiency can be corrected by DCSD Staff
Lakeside High School 3 Building 5014 Roofing Roof Drain Cleaning Next To Rtu 8-09 And Rtu 4-09 B Deficiency can be corrected by DCSD Staff
Lithonia High School 3 Site Site Requires Civil/Drainage Study Issues Reported B Deficiency can be corrected by DCSD Staff
Lithonia High School 3 Building 5010 Plumbing Urinal Repair B Deficiency can be corrected by DCSD Staff
Lithonia Middle School 3 Building 4010 Exterior Brick Exterior Repair Outside Rooms 236, 204, 641, 624 B Deficiency can be corrected by DCSD Staff
Lithonia Middle School 3 Building 4010 Exterior Brick Exterior Repointing Behind The Gym B Deficiency can be corrected by DCSD Staff
Lithonia Middle School 2 Building 4010 Exterior Concrete Pre-Cast Panel Replacement (Bldg SF) Reseal Joints B Deficiency can be corrected by DCSD Staff
Lithonia Middle School 2 Building 4010 Conveyances Elevator Cab And/Or Controls Repair Repair Chair Lift At Cafeteria - 624 B Deficiency can be corrected by DCSD Staff
234, 218, 204, Stairs Outside Room, 624, 921,
Lithonia Middle School 3 Building 4010 Exterior Exterior Metal Door Repainting B Deficiency can be corrected by DCSD Staff
923
Lithonia Middle School 2 Building 4010 Exterior Metal Panel Exterior Replacement (Bldg SF) Above Gym B Deficiency can be corrected by DCSD Staff
Lithonia Middle School 2 Building 4010 Plumbing Sewer System Investigation B Deficiency can be corrected by DCSD Staff
Lithonia Middle School 3 Building 4010 Plumbing Urinal Repair Repair 1 - Boys Toilet - 611 B Deficiency can be corrected by DCSD Staff
Marbut Elementary School 2 Roofing Asphalt Shingle Roof Covering Replacement Shingle Roof At Wood Pavilion At Playground B Deficiency can be corrected by DCSD Staff
Marbut Elementary School 3 Building 2010 Plumbing Backflow Preventer Replacement Beyond Useful Life B Deficiency can be corrected by DCSD Staff
Marbut Elementary School 3 Building 2010 Plumbing Backflow Preventer Replacement Beyond Useful Life B Deficiency can be corrected by DCSD Staff
Marbut Elementary School 3 Building 2010 Plumbing Backflow Preventer Replacement Beyond Useful Life B Deficiency can be corrected by DCSD Staff
32 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Marbut Elementary School 3 Building 2010 Exterior Brick Exterior Repair Damaged Lintels At Windows B Deficiency can be corrected by DCSD Staff
Marbut Elementary School 3 Building 2020 Roofing Gutter Replacement All Gutters Damaged B Deficiency can be corrected by DCSD Staff
Marbut Elementary School 3 Building 2010 Roofing Metal Downspout Replacement B Deficiency can be corrected by DCSD Staff
Marbut Elementary School 3 Building 2020 Roofing Metal Downspout Replacement Downspouts Damaged B Deficiency can be corrected by DCSD Staff
Mary McLeod Bethune Middle School 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility B Deficiency can be corrected by DCSD Staff
Mary McLeod Bethune Middle School 3 Building 4010 Exterior Steel Window Repair B Deficiency can be corrected by DCSD Staff
Restroom Door Handles Are Damaged And
McLendon Elementary School 3 Building 2020 Interior Interior Door Hardware Replacement B Deficiency can be corrected by DCSD Staff
Broken
McLendon Elementary School 3 Building 2010 Mechanical Large Diameter Exhausts/Hoods Replacement B Deficiency can be corrected by DCSD Staff
Flooding At The Walkway Between Buildings
McLendon Elementary School 3 Site Site Requires Civil/Drainage Study B Deficiency can be corrected by DCSD Staff
2013 And 2020
McNair Elementary School 3 Building 2020 Roofing Batt Insulation Under Metal Roof Deck Roof Insulation Underside B Deficiency can be corrected by DCSD Staff
Rainwater Overflows From Pitched Roof
Having Already Damaged A Substantial
Amount Of The Fiber Cement Soffit, And
McNair Elementary School 2 Building 2010 Roofing Gutter Joint Repair Siding Study Recommended To Determine If B Deficiency can be corrected by DCSD Staff
Gutter And Shingles Connection Is
Appropriate Or If A Gutter Is Sloped Correctly
Or Potentially Undersized .
McNair Elementary School 2 Building 2020 Roofing Gutter Joint Repair Water Leaking Thru B Deficiency can be corrected by DCSD Staff
Gaps At Tpo And Asphalt Shingles Joints,
McNair Elementary School 3 Building 2010 Roofing Membrane Flashing At Parapet (>2') Repair B Deficiency can be corrected by DCSD Staff
Gaps At Some Roof Scuppers
McNair Elementary School 3 Site Site Requires Civil/Drainage Study B Deficiency can be corrected by DCSD Staff
McNair Elementary School 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Water Ponding Issues B Deficiency can be corrected by DCSD Staff
Water Damage In The Walls Could Damage
McNair High School 3 Building 5020 Electrical Electrical Receptacle Replacement B Deficiency can be corrected by DCSD Staff
Wiring And Devices
McNair High School 3 Building 5020 Interior Interior Brick/Stone Replacement (Bldg SF) Water Damage From The Roof B Deficiency can be corrected by DCSD Staff
Miller Grove High School 2 Building 5020 Roofing Asphalt Shingle Roof Covering Repair Shingles Missing B Deficiency can be corrected by DCSD Staff
Gym Gutter Is Partially Missing. Install New
Miller Grove High School 3 Building 5010 Roofing Gutter Replacement B Deficiency can be corrected by DCSD Staff
(Larger Gutter)
Miller Grove High School 3 Building 5010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding B Deficiency can be corrected by DCSD Staff
Miller Grove Middle School 3 Building 4011 Exterior Brick Exterior Repair Cracked B Deficiency can be corrected by DCSD Staff
Miller Grove Middle School 3 Building 4010 Exterior Brick Exterior Repointing Cracked Mortar And Roof B Deficiency can be corrected by DCSD Staff
Miller Grove Middle School 3 Building 4011 Exterior Brick Exterior Repointing Cracked Mortar B Deficiency can be corrected by DCSD Staff
Miller Grove Middle School 3 Site Site Requires Civil/Drainage Study Water Ponding At West School Lawn B Deficiency can be corrected by DCSD Staff
Miller Grove Middle School 3 Building 4010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding B Deficiency can be corrected by DCSD Staff
Miller Grove Middle School 3 Building 4011 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding B Deficiency can be corrected by DCSD Staff
Montclair Elementary School 3 Building 2010 Exterior Brick Exterior Repair Brick Wall Failing B Deficiency can be corrected by DCSD Staff
Montclair Elementary School 3 Building 2020 Roofing Gutter Replacement Damaged Gutter B Deficiency can be corrected by DCSD Staff
Montclair Elementary School 3 Building 2012 Roofing Metal Downspout Installation Missing B Deficiency can be corrected by DCSD Staff
Montgomery Elementary School 3 Building 2010 Exterior Exterior Metal Door Repainting Mech Room 48.1 B Deficiency can be corrected by DCSD Staff
Montgomery Elementary School 2 Building 2020 Roofing Gutter Joint Repair Front Of Gym B Deficiency can be corrected by DCSD Staff
Narvie Harris Elementary School 3 Building 2010 Exterior Aluminum Window Repair Recaulk - 4X4 B Deficiency can be corrected by DCSD Staff
Narvie Harris Elementary School 3 Building 2010 Exterior Aluminum Window Repair Recaulk - 3X6 B Deficiency can be corrected by DCSD Staff
Narvie Harris Elementary School 3 Building 2010 Exterior Brick Exterior Repointing All Exterior Walls B Deficiency can be corrected by DCSD Staff
Narvie Harris Elementary School 3 Building 2010 Mechanical Circulation Pump Replacement Mech Room B Deficiency can be corrected by DCSD Staff
Narvie Harris Elementary School 3 Building 2010 Plumbing Condensate Drain Repair Roof Broken B Deficiency can be corrected by DCSD Staff
Narvie Harris Elementary School 2 Building 2010 Roofing Gutter Joint Repair B Deficiency can be corrected by DCSD Staff
Narvie Harris Elementary School 3 Building 2010 Roofing Metal Downspout Replacement Rusting B Deficiency can be corrected by DCSD Staff
The Main Panel And Mcc Are Combs Unit It
Narvie Harris Elementary School 2 Building 2010 Electrical Motor Control Center Repair Looks Like One Of The Mcc Buckets Had An B Deficiency can be corrected by DCSD Staff
Arc Flash Incident
The Main Panel And Mcc Are Combs Unit It
Narvie Harris Elementary School 2 Building 2010 Electrical Motor Control Center Replacement Looks Like One Of The Mcc Buckets Had An B Deficiency can be corrected by DCSD Staff
Arc Flash Incident
North DeKalb Stadium 3 Building 8020 Electrical 2 X 4 Interior Fluorescent Lighting Replacement Not Working B Deficiency can be corrected by DCSD Staff
North DeKalb Stadium 3 Building 8010 Exterior Brick Exterior Repointing Above Boiler Room B Deficiency can be corrected by DCSD Staff
North DeKalb Stadium 3 Building 8010 Exterior Exterior Metal Door Repainting Elec And Storage B Deficiency can be corrected by DCSD Staff
33 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
School Requests Adding 6 Light Poles For
Oak Grove Elementary School 3 Electrical Area Lighting Installation B Deficiency can be corrected by DCSD Staff
Safety. 2 At Front, 2 On Right, 2 At Back
Oak View Elementary School 2 Building 2010 Exterior EIFS Exterior Replacement (Bldg SF) B Deficiency can be corrected by DCSD Staff
Oak View Elementary School 2 Building 2010 Electrical Electrical Disconnect Replacement B Deficiency can be corrected by DCSD Staff
Oakcliff Elementary School 3 Building 2010 Exterior Brick Exterior Repointing Plan South, Main Entrance B Deficiency can be corrected by DCSD Staff
Oakcliff Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Foliage In Gutters B Deficiency can be corrected by DCSD Staff
Oakcliff Elementary School 3 Building 2020 Exterior Exterior Metal Door Repainting Paint Peeling And Fading B Deficiency can be corrected by DCSD Staff
Oakcliff Elementary School 2 Building 2020 Roofing Gutter Joint Repair Leaks B Deficiency can be corrected by DCSD Staff
Oakcliff Elementary School 3 Building 2020 Roofing Metal Downspout Replacement Damaged B Deficiency can be corrected by DCSD Staff
Oakcliff Elementary School 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Water Ponding B Deficiency can be corrected by DCSD Staff
Panola Way Elementary School 3 Building 2010 Exterior Aluminum Window Repair Weathering In Room 130 - Music B Deficiency can be corrected by DCSD Staff
Building Shift (8 Sf) At Room 130. Vandalism
Panola Way Elementary School 3 Building 2010 Exterior Brick Exterior Repair B Deficiency can be corrected by DCSD Staff
(3 Sf) At Room 124
Panola Way Elementary School 3 Building 2011 Exterior Brick Exterior Repair B Deficiency can be corrected by DCSD Staff
Damaged On The Ne And Sw Sides Of The
Panola Way Elementary School 3 Building 2011 Roofing Metal Downspout Replacement B Deficiency can be corrected by DCSD Staff
Building
Panola Way Elementary School 3 Building 2020 Roofing Metal Downspout Replacement B Deficiency can be corrected by DCSD Staff
Panola Way Elementary School 3 Site Parking Or Roadway Curbs Replacement Damaged Concrete Curbs B Deficiency can be corrected by DCSD Staff
Wood Ramp - Wood Rotting And Splitting
Panthersville Administrative 2 Building 8040 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility B Deficiency can be corrected by DCSD Staff
Replace
Peachcrest Elementary School 3 Building 2010 Roofing Debris In Gutter Removal Gutter Is Clogged B Deficiency can be corrected by DCSD Staff
Peachcrest Elementary School 3 Building 2010 Exterior Exterior Metal Door Repainting B Deficiency can be corrected by DCSD Staff
Repair Flashing At Canopy Outside The
Peachcrest Elementary School 3 Building 2010 Roofing Membrane Flashing At Parapet (>2') Repair Kitchen To Eliminate Water Steak Against The B Deficiency can be corrected by DCSD Staff
Brick Wall.
Peachcrest Elementary School 3 Building 2010 Roofing Modified Covering Has Blisters That Should Be Repaired B Deficiency can be corrected by DCSD Staff
Peachcrest Elementary School 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing B Deficiency can be corrected by DCSD Staff
Peachcrest Elementary School 3 Building 2010 Plumbing Urinal Repair Leaking B Deficiency can be corrected by DCSD Staff
Pine Ridge Elementary School 2 Building 2011 Roofing Gutter Joint Repair B Deficiency can be corrected by DCSD Staff
Pine Ridge Elementary School 3 Building 2011 Roofing Metal Downspout Replacement B Deficiency can be corrected by DCSD Staff
Pine Ridge Elementary School 3 Building 2010 Roofing Skylight Repair Minor Leaks B Deficiency can be corrected by DCSD Staff
Pine Ridge Elementary School 2 Building 2010 Plumbing Water Heater Replacement B Deficiency can be corrected by DCSD Staff
Pine Ridge Elementary School 2 Building 2010 Plumbing Water Heater Replacement B Deficiency can be corrected by DCSD Staff
Pleasantdale (New) Elementary School 3 Building 8010 Roofing Membrane Flashing At Parapet (>2') Repair B Deficiency can be corrected by DCSD Staff
Replace Missing Bricks At Front Entry Box
Princeton Elementary School 2 Building 2010 Exterior Brick Exterior Replacement (Bldg SF) B Deficiency can be corrected by DCSD Staff
Planters
Repair 10 Feet Of Broken Curb At Dumpster
Princeton Elementary School 3 Site Concrete Driveways Replacement B Deficiency can be corrected by DCSD Staff
And Compacter
Princeton Elementary School 2 Building 2010 Exterior Dryvit Exterior Repair Cracks At Front B Deficiency can be corrected by DCSD Staff
Princeton Elementary School 3 Building 2010 Roofing Roof Drain Cleaning Clean Gutters At 3 Stair Towers B Deficiency can be corrected by DCSD Staff
Rainbow Elementary School 3 Building 2010 Roofing Modified Covering Has Blisters That Should Be Repaired Blisters B Deficiency can be corrected by DCSD Staff
Rainbow Elementary School 3 Building 2011 Roofing Modified Covering Has Blisters That Should Be Repaired Blisters On Roof B Deficiency can be corrected by DCSD Staff
Redan Elementary School 3 Building 2020 Exterior Brick Exterior Repointing B Deficiency can be corrected by DCSD Staff
Redan Elementary School 2 Building 2011 Electrical Exterior Electrical Enclosure Replacement B Deficiency can be corrected by DCSD Staff
Two Disconnect Switches Outside Upstream
Redan Elementary School 2 Building 2040 Electrical Exterior Electrical Enclosure Replacement And Downstream Of Dry Type Transformers, B Deficiency can be corrected by DCSD Staff
Enclosures Appear Worn Out
Redan Elementary School 3 Building 2030 Interior Interior Door Replacement Broken B Deficiency can be corrected by DCSD Staff
Study Needed To Assess Flood Of Walkway
Redan Elementary School 3 Site Site Requires Civil/Drainage Study B Deficiency can be corrected by DCSD Staff
Connecting Building 2021 And 2030
Redan High School 3 Building 5011 Exterior Brick Exterior Repair Damage And Ne Corner B Deficiency can be corrected by DCSD Staff
Redan High School 2 Building 5010 Electrical Electrical Transformer Repair Old Elec Room B Deficiency can be corrected by DCSD Staff
Redan High School 2 Building 5010 Electrical Electrical Transformer Repair Old Elec Rooms B Deficiency can be corrected by DCSD Staff
Redan High School 2 Building 5010 Electrical Electrical Transformer Repair Old Elec Rooms B Deficiency can be corrected by DCSD Staff
Redan High School 2 Building 5010 Electrical Electrical Transformer Repair Elec Rooms B Deficiency can be corrected by DCSD Staff
Redan High School 2 Building 5010 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility
South Side Of Building B Deficiency can be corrected by DCSD Staff
Redan High School 3 Building 5010 Roofing Modified Covering Has Blisters That Should Be Repaired West Roof B Deficiency can be corrected by DCSD Staff
Redan High School 3 Building 5010 Roofing Roof Operable Hatch Replacement B20 Mech Room B Deficiency can be corrected by DCSD Staff
34 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Redan High School 3 Building 5010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
At Se Corner Gym Roof B Deficiency can be corrected by DCSD Staff
Redan Middle School 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility B Deficiency can be corrected by DCSD Staff
Robert Shaw Theme 2 Building 2020 Mechanical Electric Unit Heater Replacement Damaged, Each Restroom B Deficiency can be corrected by DCSD Staff
Robert Shaw Theme 2 Building 2010 Electrical Panelboard Replacement Old, Replace Custodian B Deficiency can be corrected by DCSD Staff
Significant Ponding On The East Side Of West
Robert Shaw Theme 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing B Deficiency can be corrected by DCSD Staff
Wing (Above Rooms 419, 414, 412, 408)
Significant Ponding On West Side Of Roof
Robert Shaw Theme 3 Building 2011 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing B Deficiency can be corrected by DCSD Staff
(Above Rooms 401 Thru 417)
Need To Regrout Or Recaulk Brick Joint On
Rockbridge Elementary School 3 Building 2010 Exterior Brick Exterior Repointing Left Side Of The School At Back Corner Over B Deficiency can be corrected by DCSD Staff
Doors
Flashing On Roof Parapet Blew Off. Flashing
Rockbridge Elementary School 3 Building 2010 Roofing Gutter Replacement B Deficiency can be corrected by DCSD Staff
For Parapet On 3Rd Floor At Back Left
Rockbridge Elementary School 3 Building 2010 Roofing Roof Drain Cleaning Leaves B Deficiency can be corrected by DCSD Staff
Rowland Elementary School 3 Building 2010 Plumbing Backflow Preventer Replacement 1.5" Backflow Preventer B Deficiency can be corrected by DCSD Staff
Rowland Elementary School 3 Building 2012 Exterior Caulking Replacement B Deficiency can be corrected by DCSD Staff
Rowland Elementary School 3 Building 2010 Roofing Debris In Gutter Removal Debris Visible B Deficiency can be corrected by DCSD Staff
Rowland Elementary School 3 Building 2020 Roofing Debris In Gutter Removal B Deficiency can be corrected by DCSD Staff
Rowland Elementary School 3 Building 2010 Electrical Electrical Receptacle Replacement Lounge Receptacle B Deficiency can be corrected by DCSD Staff
Replace Receptacle Near Sink With A GFI
Rowland Elementary School 3 Building 2012 Electrical Electrical Receptacle Replacement B Deficiency can be corrected by DCSD Staff
Protected Receptacle
Rowland Elementary School 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility
Damaged B Deficiency can be corrected by DCSD Staff
Rowland Elementary School 3 Building 2020 Exterior Exterior Metal Door Repainting B Deficiency can be corrected by DCSD Staff
Rowland Elementary School 3 Building 2010 Roofing Metal Downspout Replacement Rust And Damage B Deficiency can be corrected by DCSD Staff
Rowland Elementary School 3 Building 2011 Roofing Metal Downspout Replacement Rust And Damaged B Deficiency can be corrected by DCSD Staff
Rowland Elementary School 3 Building 2020 Roofing Metal Downspout Replacement B Deficiency can be corrected by DCSD Staff
Sagamore Hills Elementary School 3 Building 2010 Exterior Brick Exterior Repointing Bottom 2Ft Of Brick Wall Needs Repointing B Deficiency can be corrected by DCSD Staff
Sagamore Hills Elementary School 2 Building 2010 Roofing Single-Ply Covering Has Blisters That Should Be Repaired Large Blisters In Single Ply Membrane B Deficiency can be corrected by DCSD Staff
Sam Moss Service Center 3 Building 8040 Plumbing Backflow Preventer Replacement B Deficiency can be corrected by DCSD Staff
Sam Moss Service Center 3 Building 8020 Exterior Exterior Metal Door Repainting B Deficiency can be corrected by DCSD Staff
Shadow Rock Elementary School 3 Site Asphalt Driveway Replacement Fill Potholes B Deficiency can be corrected by DCSD Staff
Shadow Rock Elementary School 3 Building 2010 Exterior Exterior Metal Door Repainting Rusted Paint B Deficiency can be corrected by DCSD Staff
Shadow Rock Elementary School 3 Building 2020 Roofing Metal Downspout Replacement Bent And Damaged At Bottom Of Downspout B Deficiency can be corrected by DCSD Staff
Snapfinger Elementary School 3 Building 2010 Roofing Debris In Gutter Removal Leaves And Debris In Gutter B Deficiency can be corrected by DCSD Staff
Snapfinger Elementary School 3 Building 2020 Roofing Debris In Gutter Removal B Deficiency can be corrected by DCSD Staff
Snapfinger Elementary School 2 Building 2013 Exterior Dryvit Exterior Repair Eifs Wall @ Ground Level B Deficiency can be corrected by DCSD Staff
Snapfinger Elementary School 2 Building 2010 Mechanical Ductless Split System AC Replacement Beyond Useful Life - Room 114.3 B Deficiency can be corrected by DCSD Staff
Gfi Receptacle Needed In Science Room 103.
Snapfinger Elementary School 3 Building 2012 Electrical Electrical Receptacle Replacement B Deficiency can be corrected by DCSD Staff
New Receptacle Needed In Room 104
Snapfinger Elementary School 3 Building 2020 Electrical Electrical Receptacle Replacement Outside Electrical Room Receptacles B Deficiency can be corrected by DCSD Staff
Snapfinger Elementary School 2 Building 2020 Roofing Gutter Joint Repair Leaking At Seams B Deficiency can be corrected by DCSD Staff
Snapfinger Elementary School 3 Building 2013 Roofing Metal Downspout Replacement Missing B Deficiency can be corrected by DCSD Staff
Snapfinger Elementary School 3 Building 2020 Roofing Metal Downspout Replacement 2 Downspouts Nw And Sw Corners B Deficiency can be corrected by DCSD Staff
Minor Leaks - Heavy Rain - Room 115,
Snapfinger Elementary School 3 Building 2010 Roofing Modified Covering Has Blisters That Should Be Repaired B Deficiency can be corrected by DCSD Staff
Hallway By Rm 121 - Approximately 100 Sf
Snapfinger Elementary School 3 Site Site Requires Civil/Drainage Study Pooling, Southside Of The School B Deficiency can be corrected by DCSD Staff
Southwest DeKalb High School 3 Building 5020 Roofing Awning Or Canopy Metal Roofing System Replacement Metal Canopy At Room 5100.15 Mech Room. B Deficiency can be corrected by DCSD Staff
Southwest DeKalb High School 3 Building 5030 Exterior Brick Exterior Repair Brick Pushed In And Wall Deformed B Deficiency can be corrected by DCSD Staff
Southwest DeKalb High School 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility
Cracked B Deficiency can be corrected by DCSD Staff
Southwest DeKalb High School 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility
Next To Stair That Leads To Building B Deficiency can be corrected by DCSD Staff
Paint Is Chipped And East And West Sides Of
Southwest DeKalb High School 3 Building 5040 Exterior Exterior Metal Door Repainting B Deficiency can be corrected by DCSD Staff
Building
Southwest DeKalb High School 2 Building 5040 Roofing Gutter Joint Repair Dripping B Deficiency can be corrected by DCSD Staff
35 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Damaged And Covered Walkway To Front
Southwest DeKalb High School 3 Building 5012 Roofing Metal Downspout Replacement B Deficiency can be corrected by DCSD Staff
Entrance By Room 2222
Bottom Portion Of East And West Side Of
Southwest DeKalb High School 3 Building 5040 Roofing Metal Downspout Replacement B Deficiency can be corrected by DCSD Staff
Building
Southwest DeKalb High School 2 Building 5040 Roofing Metal Roof Architectural Roof Covering Replacement Leaking In 103 B Deficiency can be corrected by DCSD Staff
Southwest DeKalb High School 3 Building 5012 Roofing Modified Covering Has Blisters That Should Be Repaired Large Blister Above Room 6354 B Deficiency can be corrected by DCSD Staff
Southwest DeKalb High School 3 Building 5013 Roofing Modified Covering Has Blisters That Should Be Repaired Near The Cooling Tower B Deficiency can be corrected by DCSD Staff
Ponding Above 5200 Hallway Building -
Southwest DeKalb High School 3 Building 5011 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing B Deficiency can be corrected by DCSD Staff
Western 5011 Building
Stephenson High School 3 Building 5010 Exterior Aluminum Window Repair Moisture Between Double Pane Window B Deficiency can be corrected by DCSD Staff
Stephenson High School 3 Building 5010 Exterior Brick Exterior Repair B Deficiency can be corrected by DCSD Staff
Stephenson High School 3 Building 5010 Exterior Brick Exterior Repointing B Deficiency can be corrected by DCSD Staff
Stephenson High School 3 Building 5011 Roofing Built Up Roofing (Bur) Covering Has Blisters That Should Be Repaired B Deficiency can be corrected by DCSD Staff
Stephenson High School 3 Building 5010 Electrical Electrical Receptacle Replacement B Deficiency can be corrected by DCSD Staff
Stephenson High School 3 Building 5011 Electrical Electrical Receptacle Replacement B Deficiency can be corrected by DCSD Staff
Stephenson High School 3 Building 5060 Exterior Exterior Metal Door Repainting B Deficiency can be corrected by DCSD Staff
Stephenson High School 3 Building 5050 Roofing Metal Downspout Replacement Damaged B Deficiency can be corrected by DCSD Staff
Stephenson Middle School 3 Building 4010 Electrical Electrical Receptacle Replacement B Deficiency can be corrected by DCSD Staff
Stephenson Middle School 3 Building 4010 Exterior Exterior Metal Door Repainting B Deficiency can be corrected by DCSD Staff
Stephenson Middle School 3 Building 4011 Exterior Exterior Metal Door Repainting B Deficiency can be corrected by DCSD Staff
Stephenson Middle School 3 Building 4011 Roofing Membrane Flashing At Parapet (>2') Repair Repair Flashing B Deficiency can be corrected by DCSD Staff
Stephenson Middle School 3 Building 4010 Interior Rubber Flooring Replacement Beyond Useful Life B Deficiency can be corrected by DCSD Staff
5' X 5' Windows. Repair And Paint Wood
Stone Mill Elementary School 3 Building 2010 Exterior Steel Window Repair B Deficiency can be corrected by DCSD Staff
Below Windows
Stone Mountain Elementary School 3 Site Concrete Walks Replacement Damaged And Raised Sidewalks B Deficiency can be corrected by DCSD Staff
Stone Mountain Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Debris And Vegetation In Gutters B Deficiency can be corrected by DCSD Staff
Stone Mountain Elementary School 3 Building 2010 Electrical Electrical Receptacle Replacement Beyond Useful Life B Deficiency can be corrected by DCSD Staff
Stone Mountain Elementary School 3 Building 2011 Electrical Electrical Receptacle Replacement Beyond Useful Life B Deficiency can be corrected by DCSD Staff
Stone Mountain Elementary School 3 Building 2012 Electrical Electrical Receptacle Replacement Beyond Useful Life B Deficiency can be corrected by DCSD Staff
Stone Mountain Elementary School 3 Building 2013 Electrical Electrical Receptacle Replacement Beyond Useful Life B Deficiency can be corrected by DCSD Staff
Asphalt Crosswalk Is Cracked And Needs
Stone Mountain Elementary School 2 Building 2010 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility B Deficiency can be corrected by DCSD Staff
Striping
Stone Mountain Elementary School 3 Building 2010 Roofing Metal Downspout Installation Downspout Not Existing B Deficiency can be corrected by DCSD Staff
Add Insulation To Increase Slope To Eliminate
Stone Mountain Elementary School 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing B Deficiency can be corrected by DCSD Staff
Ponding
Back Of Corrugated Metal Panel Parapets
Stone Mountain High School 3 Building 5010 Interior Expansion Joints Missing or Deteriorated B Deficiency can be corrected by DCSD Staff
Have Open Joints (Repair)
Stone Mountain High School 3 Building 5010 Roofing Membrane Flashing At Parapet (>2') Repair Cracked B Deficiency can be corrected by DCSD Staff
Stone Mountain High School 3 Building 5010 Roofing Modified Covering Has Blisters That Should Be Repaired Blisters B Deficiency can be corrected by DCSD Staff
Stone Mountain High School 2 Building 5010 Roofing Modified Membrane Has Holes That Should Be Repaired Holes B Deficiency can be corrected by DCSD Staff
Stone Mountain High School 3 Building 5010 Roofing Roof Operable Hatch Replacement Broken B Deficiency can be corrected by DCSD Staff
Stone Mountain Middle School 3 Building 4010 Roofing Built Up Roofing (Bur) Membrane Has Holes That Should Be Repaired B Deficiency can be corrected by DCSD Staff
Stone Mountain Middle School 2 Building 4010 Roofing Expansion Joint Cover Replacement Cracked And Broken B Deficiency can be corrected by DCSD Staff
Stone Mountain Middle School 3 Building 4010 Exterior Exterior Metal Door Repainting Faded Paint And Throughout B Deficiency can be corrected by DCSD Staff
Stone Mountain Middle School 3 Building 4010 Roofing Roof Drain Cleaning B Deficiency can be corrected by DCSD Staff
Stone Mountain Middle School 3 Building 4010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Water Ponding B Deficiency can be corrected by DCSD Staff
Towers High School 3 Building 5010 Plumbing Backflow Preventer Replacement Over 25 Years Old B Deficiency can be corrected by DCSD Staff
Towers High School 3 Building 5010 Roofing Debris In Gutter Removal B Deficiency can be corrected by DCSD Staff
Towers High School 3 Building 5011 Plumbing Domestic Water Piping Repair Cold Water Piping Leaking Needs Rapier B Deficiency can be corrected by DCSD Staff
Staff Reported Safety Issues With Work
Towers High School 3 Building 5010 Electrical Electrical Receptacle Replacement Stations And Cords; Requested Power Poles B Deficiency can be corrected by DCSD Staff
For Work Stations (Add Not Replace)
Towers High School 2 Building 5010 Conveyances Elevator Cab And/Or Controls Repair Elevator Out Of Commission B Deficiency can be corrected by DCSD Staff
Towers High School 3 Building 5010 Plumbing Toilet Plumbing Fixture Repair Toilet Damaged B Deficiency can be corrected by DCSD Staff
Tucker Middle School 2 Building 4010 Exterior Brick Exterior Replacement (Bldg SF) Replace Missing Brick B Deficiency can be corrected by DCSD Staff
Concrete Sidewalk. (420Sf) Replaced Cracked
Tucker Middle School 3 Building 4010 Site Concrete Walks Replacement B Deficiency can be corrected by DCSD Staff
Sidewalk At Front Of School (100Sf).
36 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Repair Dryvit At Three Locations. Corner
Outside Back Kitchen Door (Hit By Vehicle),
Tucker Middle School 2 Building 4010 Exterior Dryvit Exterior Repair B Deficiency can be corrected by DCSD Staff
Back Corner Close To Cooling Tower (Rusting)
And Above Door At Courtyard
Gutters Damaged In 7 Various Locations
Around Building. Looks Like Damage Caused
Tucker Middle School 2 Building 4010 Roofing Gutter Joint Repair B Deficiency can be corrected by DCSD Staff
By People Climbing Onto Roof. Need To Clean
Bricks At Damaged Gutter Locations
Replace Downspout At Column Outside Back
Tucker Middle School 3 Building 4010 Roofing Metal Downspout Replacement B Deficiency can be corrected by DCSD Staff
Kitchen Door
Tucker Middle School 3 Building 4010 Roofing Modified Covering Has Blisters That Should Be Repaired Bubbles B Deficiency can be corrected by DCSD Staff
West At Cafeteria And Kitchen. Brick Work
Wadsworth Magnet School 2 Building 2010 Exterior Brick Exterior Replacement (Bldg SF) Missing At Base (North Wall Of Storage Rm B Deficiency can be corrected by DCSD Staff
For Kitchen)
Room 303, Teacher Lounge, Old Hallway.
Install New Electrical Receptacles In Multiple
Wadsworth Magnet School 3 Building 2010 Electrical Electrical Receptacle Replacement B Deficiency can be corrected by DCSD Staff
Areas, Especially Classrooms Where Students
Can Plug In Their Devices.
Wadsworth Magnet School 3 Building 2012 Electrical Electrical Receptacle Replacement Clinic And Room 101 B Deficiency can be corrected by DCSD Staff
Wadsworth Magnet School 3 Building 2020 Electrical Electrical Receptacle Replacement Office Area B Deficiency can be corrected by DCSD Staff
Wadsworth Magnet School 3 Building 2010 Roofing Metal Downspout Installation Estimated B Deficiency can be corrected by DCSD Staff
Wadsworth Magnet School 3 Building 2011 Roofing Metal Downspout Installation Estimated B Deficiency can be corrected by DCSD Staff
Warren Technical Chamblee 3 Building 4011 Roofing Metal Downspout Replacement Disconnected B Deficiency can be corrected by DCSD Staff
2 Each - Ponding In Courtyard, Ponding At
Warren Technical Chamblee 3 Site Site Requires Civil/Drainage Study B Deficiency can be corrected by DCSD Staff
Rear Of School.
Warren Technical Chamblee 3 Building 4010 Mechanical Testing And Balancing Mech Room Equip B Deficiency can be corrected by DCSD Staff
William Bradley Bryant Technology Center 3 Building 8010 Exterior Exterior Metal Door Repainting Paint Is Chipping B Deficiency can be corrected by DCSD Staff
William Bradley Bryant Technology Center 3 Building 8010 Exterior Exterior Metal Door Repainting Paint Is Chipping B Deficiency can be corrected by DCSD Staff
Wynbrooke Elementary School 3 Site Concrete Driveways Replacement B Deficiency can be corrected by DCSD Staff
Wynbrooke Elementary School 3 Building 2010 Exterior Exterior Metal Door Repainting Faded And Rusting B Deficiency can be corrected by DCSD Staff
Wynbrooke Elementary School 3 Building 2010 Exterior Handrail Replacement Stage Handrail In Cafeteria Broken B Deficiency can be corrected by DCSD Staff
Adams Stadium 3 Interior Existing Door Hardware Is Not ADA Compliant Bathroom Door Handles Not ADA C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2010 Conveyances Platform Lift Needed for Access C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2010 Roofing Debris In Gutter Removal C Deficiency is included in a CIP project
Existing Panel Has Exposed Electrical Buss,
Allgood Elementary School 2 Building 2010 Electrical Distribution Panel Replacement Open Pull Box With Conductors Exposed To C Deficiency is included in a CIP project
Water
Allgood Elementary School 3 Building 2011 Roofing Debris In Gutter Removal C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2012 Roofing Debris In Gutter Removal C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2013 Roofing Debris In Gutter Removal C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2013 Mechanical Ductwork Replacement (SF Basis) C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2014 Roofing Gutter Replacement C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2014 Roofing Metal Downspout Replacement C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Clean Gutters C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2020 Roofing Gutter Joint Repair C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2014 Exterior Exterior Metal Door Repainting All Exterior Doors C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2010 Mechanical Circulation Pump Replacement C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2013 Exterior Concrete Pre-Cast Panel Replacement (Bldg SF) Columns Show Signs Of Structure Failure C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2010 Mechanical Ductwork Replacement (SF Basis) C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2011 Mechanical Ductwork Replacement (SF Basis) C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2010 Mechanical Electric Unit Heater Replacement C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2010 Mechanical Electric Unit Heater Replacement C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2011 Mechanical Electric Unit Heater Replacement C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2013 Mechanical Electric Unit Heater Replacement C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2013 Mechanical Electric Unit Heater Replacement C Deficiency is included in a CIP project
37 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Cr 142 Exposed Wire At Receptacle, Cr 136
Allgood Elementary School 3 Building 2014 Electrical Electrical Receptacle Replacement Exposed Wire At Receptacle, Cr 136 Floor C Deficiency is included in a CIP project
Outlet Broken Cover
Allgood Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2020 Exterior Exterior Metal Door Repainting Repaint Doors C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2011 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2012 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2013 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2014 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2010 Mechanical Gas Piping Replacement (SF Basis) C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2011 Mechanical Gas Piping Replacement (SF Basis) C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2012 Mechanical Gas Piping Replacement (SF Basis) C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2013 Mechanical Gas Piping Replacement (SF Basis) C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2011 Mechanical Heat Pump HVAC Component Replacement C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2012 Mechanical Heat Pump HVAC Component Replacement C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2013 Mechanical Heat Pump HVAC Component Replacement C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2014 Interior Interior Door Replacement C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement Old Wiring C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2011 Electrical Interior Power Wiring Replacement C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2012 Electrical Interior Power Wiring Replacement Beyond Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2013 Electrical Interior Power Wiring Replacement Wiring Original To Building C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2013 Mechanical Large Diameter Exhausts/Hoods Replacement C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Old T8 Lamps C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement Beyond Useful Life - Old T8 Lamps C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2012 Electrical Lighting Fixtures Replacement Beyond Useful Life - Old T8 Lamps C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2013 Electrical Lighting Fixtures Replacement Old T8 Fl Lamps C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2014 Electrical Lighting Fixtures Replacement Old T8 Light Fixtures C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement Beyond Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2011 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2012 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2013 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2011 Exterior Metal Exterior Door Replacement Hardware Broken At Pull C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Beyond Useful Life - Maintain NEC Required
Allgood Elementary School 2 Building 2012 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Clearances
Allgood Elementary School 2 Building 2013 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2013 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2011 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2012 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2013 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2010 Electrical Public Address System Head-End Requires Replacement C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2011 Electrical Public Address System Replacement, Non-main Building PA System Is Served From Building 2010 C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2012 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2013 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life C Deficiency is included in a CIP project
Beyond Useful Life - Pa Served From Building
Allgood Elementary School 3 Building 2014 Electrical Public Address System Replacement, Non-main Building C Deficiency is included in a CIP project
2010
Allgood Elementary School 3 Building 2020 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2010 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2011 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2012 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Allgood Elementary School 3 Building 2013 Mechanical Testing And Balancing C Deficiency is included in a CIP project
38 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Allgood Elementary School 2 Building 2010 Plumbing Water Heater Replacement C Deficiency is included in a CIP project
Allgood Elementary School 2 Building 2013 Plumbing Water Heater Replacement C Deficiency is included in a CIP project
Arabia Mountain High School 3 Building 5020 Exterior Exterior Entry Door Hardware Is Not ADA Compliant Door Knobs C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height Requirements (Modify Full) C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Plumbing Water Heater Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Mechanical Cast Iron Water Boiler Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Mechanical Heat Exchanger Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2010 Mechanical Circulation Pump Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2010 Mechanical Circulation Pump Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Mechanical Electric Unit Heater Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Mechanical Exterior Metal Cooling Tower Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement 2 Ton C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2010 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2010 Mechanical Large Diameter Exhausts/Hoods Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement Old Wiring C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2011 Plumbing Water Heater Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2011 Mechanical Heat Pump HVAC Component Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2011 Mechanical Heat Pump HVAC Component Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2011 Mechanical Heat Pump HVAC Component Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2011 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2011 Mechanical Large Diameter Exhausts/Hoods Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2011 Electrical Interior Power Wiring Replacement Old Building Wiring C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2011 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2011 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2011 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2020 Plumbing Water Heater Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2020 Mechanical Electric Unit Heater Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Site Site Requires Civil/Drainage Study Stairs Towards The Gym C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Site Concrete Walks Replacement Around Flag Pole C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Site Concrete Walks Replacement Cracked C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2020 Exterior Exterior Metal Door Repainting Dirty C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2011 Electrical Canopy Lighting Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2011 Electrical Exterior Mounted Building Lighting Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement Beyond Useful Life C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2011 Interior Interior Door Hardware Replacement Beyond Useful Life C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2011 Interior Interior Door Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2010 Interior Interior Door Replacement Beyond Useful Life C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Old T8 Lamps C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement Old T8 Lamps C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement Old Light Fixtures C Deficiency is included in a CIP project
39 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Ashford Park Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Installed C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Not Installed C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Not Installed C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2010 Electrical Public Address System Head-End Requires Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2011 Electrical Public Address System Replacement, Non-main Building C Deficiency is included in a CIP project
Ashford Park Elementary School 3 Building 2020 Electrical Public Address System Replacement, Non-main Building C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Exterior Steel Window Replacement C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2011 Exterior Steel Window Replacement Beyond Useful Life C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2011 Exterior Steel Window Replacement Beyond Useful Life C Deficiency is included in a CIP project
Ashford Park Elementary School 2 Building 2010 Exterior Wood Exterior Door Replacement Damaged At Kitchen C Deficiency is included in a CIP project
Avondale Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant All Interior Door Hardware Not Compliant C Deficiency is included in a CIP project
Avondale Elementary School 3 Building 2010 Plumbing Existing Lavatory/Sink Is Not ADA Compliant Missing Pipe Insulation At Sinks C Deficiency is included in a CIP project
Avondale Elementary School 3 Building 2010 Site Car Accessible Parking Spaces Restiriping Beyond Useful Life C Deficiency is included in a CIP project
All Door Hardware In Building 2011Is Not
Avondale Elementary School 3 Building 2011 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Compliant
Avondale Elementary School 3 Building 2011 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
Not Existing Ramp C Deficiency is included in a CIP project
Avondale Elementary School 3 Building 2012 Interior Existing Door Hardware Is Not ADA Compliant All Interior Door Hardware Not Compliant C Deficiency is included in a CIP project
Avondale Elementary School 3 Building 2012 Plumbing Existing Lavatory/Sink Is Not ADA Compliant Missing Pipe Insulation At Sinks C Deficiency is included in a CIP project
Avondale High DSA 3 Building 5010 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Avondale High DSA 3 Building 5020 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Avondale High DSA 3 Building 5010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
Missing C Deficiency is included in a CIP project
Avondale High DSA 3 Building 5011 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
Missing C Deficiency is included in a CIP project
Non-Compliant Height. Add ADA Compliant
Bob Mathis Elementary School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height Requirements (Modify Full) C Deficiency is included in a CIP project
Segment.
Bob Mathis Elementary School 3 Building 2010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
No Ramp Or Lift For Stage Access. Add Ramp. C Deficiency is included in a CIP project
Bob Mathis Elementary School 3 Building 2010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA
AddRequirements
ADA Sign C Deficiency is included in a CIP project
Should Have A ADA Sign And Power Assist
Bob Mathis Elementary School 3 Building 2011 Interior Entry Door Does Not Have Power Assist Device C Deficiency is included in a CIP project
Hardware.
East Entry Doors Accessed From Concrete
Ramp (Connected To Car Drop Off Area)
Bob Mathis Elementary School 3 Building 2011 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements C Deficiency is included in a CIP project
Should Have A ADA Sign And Power Assist
Hardware.
There Is A Power-Assist Hardware Door At
Bob Mathis Elementary School 3 Building 2010 Exterior Exterior Entry Door Hardware Is Not ADA Compliant Front Entry, But It Is Deficient. Repair Or C Deficiency is included in a CIP project
Replace.
Bob Mathis Elementary School 3 Building 2020 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA
AddRequirements
1 ADA Sign C Deficiency is included in a CIP project
Curb Ramp East Of 2011 (By Car Drop Off)
Bob Mathis Elementary School 3 Site Curb Ramp Does Not Meet Minimum ADA Compliance Requirements Concrete Material Is Ok (Not Cracked) But C Deficiency is included in a CIP project
Signage Is Faded. Repaint.
Bob Mathis Elementary School 3 Building 2020 Exterior Exterior Entry Door Hardware Is Not ADA Compliant Add 1 Power Assist C Deficiency is included in a CIP project
Bob Mathis Elementary School 3 Building 2010 Mechanical Circulation Pump Replacement Damaged, Outside Room 126.1 C Deficiency is included in a CIP project
Bob Mathis Elementary School 2 Building 2010 Mechanical Exterior Metal Cooling Tower Replacement Damaged, Outside 126-1 C Deficiency is included in a CIP project
Roof Appears To Be Bur With Ballast Atop A
Mod-Bit Roof. Various Areas Of Ponding, Soft
Briar Vista Elementary School 2 Building 2010 Roofing Built-up Roofing Replacement C Deficiency is included in a CIP project
Areas Observed. Roof Replacement
Recommended.
Briar Vista Elementary School 3 Building 2010 Roofing Metal Downspout Installation Courtyard Area C Deficiency is included in a CIP project
Beyond Useful Life - Roof Appears To Be Bur
With Ballast Atop A Mod-Bit Roof. Various
Briar Vista Elementary School 2 Building 2011 Roofing Built-up Roofing Replacement C Deficiency is included in a CIP project
Areas Of Ponding, Soft Areas Observed. Roof
Replacement Recommended.
40 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Roof Appears To Be Bur With Ballast Atop A
Briar Vista Elementary School 2 Building 2012 Roofing Built-up Roofing Replacement Mod-Bit Roof. Various Areas Of Ponding C Deficiency is included in a CIP project
Observed. Roof Replacement Recommended.
Briar Vista Elementary School 3 Building 2012 Roofing Metal Downspout Replacement Downspout Boot C Deficiency is included in a CIP project
Briarlake Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant All Interior Door Hardware Not Compliant C Deficiency is included in a CIP project
Briarlake Elementary School 3 Building 2011 Interior Existing Door Hardware Is Not ADA Compliant All Interior Door Hardware Not Compliant C Deficiency is included in a CIP project
Power Assist Doors Needed For Front
Briarlake Elementary School 3 Building 2010 Exterior Exterior Entry Door Threshold Exceeds The Maximum Threshold Height C Deficiency is included in a CIP project
Entrance
Outside Ramp Needed At End Of
Briarlake Elementary School 3 Building 2010 Site Curb Ramp Does Not Meet Minimum ADA Compliance Requirements Kindergarten Wing To Access Playground C Deficiency is included in a CIP project
Sidewalk
Briarlake Elementary School 3 Building 2010 Site Sidewalk Longitudinal Or Cross Slope Exceeds Maximum Slope Criteria
Slope Is Too Steep, Not Compliant C Deficiency is included in a CIP project
Briarlake Elementary School 3 Building 2010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
No Ramp Existing To Access Stage C Deficiency is included in a CIP project
Briarlake Elementary School 3 Building 2010 Mechanical Testing And Balancing Test C Deficiency is included in a CIP project
Briarlake Elementary School 3 Building 2010 Mechanical Make Up Air Equipment Replacement Beyond Useful Life C Deficiency is included in a CIP project
Briarlake Elementary School 3 Building 2011 Mechanical Testing And Balancing Test C Deficiency is included in a CIP project
Briarlake Elementary School 3 Building 2012 Mechanical Testing And Balancing Test C Deficiency is included in a CIP project
Brockett Elementary School 3 Building 2010 Interior Entry Door Does Not Have Power Assist Device Missing At Main Entrance C Deficiency is included in a CIP project
Brockett Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant Door Knobs Non-ADA C Deficiency is included in a CIP project
Brockett Elementary School 3 Building 2010 Conveyances Platform Lift Needed for Access Missing C Deficiency is included in a CIP project
Brockett Elementary School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsMissing(ModifyLowFull)Counter Tip C Deficiency is included in a CIP project
Brockett Elementary School 3 Building 2010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
Missing C Deficiency is included in a CIP project
Browns Mill Elementary School 3 Building 2010 Exterior Exterior Entry Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Browns Mill Elementary School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height Requirements (Modify Full) C Deficiency is included in a CIP project
Browns Mill Elementary School 3 Site Car Accessible Parking Spaces Restiriping Old, Faded C Deficiency is included in a CIP project
Browns Mill Elementary School 3 Site Van Accessible Parking Spaces Are Not Properly Striped Old, Faded C Deficiency is included in a CIP project
Browns Mill Elementary School 3 Site Too Requirements
Exterior Entry Signage At The Building Entry Does Not Meet ADA Small C Deficiency is included in a CIP project
Canby Lane Elementary School 3 Building 2010 Interior Entry Door Does Not Have Power Assist Device Missing C Deficiency is included in a CIP project
Canby Lane Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Canby Lane Elementary School 3 Building 2010 Conveyances Platform Lift Needed for Access Missing C Deficiency is included in a CIP project
Canby Lane Elementary School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsNo (Modify
LowerFull)
Counter C Deficiency is included in a CIP project
Canby Lane Elementary School 3 Building 2010 Site Curb Ramp Does Not Meet Minimum ADA Compliance Requirements Cracked C Deficiency is included in a CIP project
Canby Lane Elementary School 3 Site Asphalt Driveway Replacement Beyond Useful Life C Deficiency is included in a CIP project
Canby Lane Elementary School 3 Site Asphalt Walks Replacement Beyond Useful Life Play Yard Cracked C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2010 Interior Entry Door Does Not Have Power Assist Device C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2010 Interior Access Is Not ADA Compliant C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2013 Interior Entry Door Does Not Have Power Assist Device Plan West Entrance C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2010 Interior Existing Toilet Stall Does Not Meet Minimum ADA Requirements C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2010 Conveyances Platform Lift Needed for Access C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2010 Plumbing Existing Lavatory/Sink Is Not ADA Compliant No Covers Under Sinks C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2010 Plumbing Restroom Grab Bars Are Not ADA Compliant C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2010 Plumbing Restroom Is Not ADA Compliant C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height Requirements (Modify Full) C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2012 Interior Existing Door Hardware Is Not ADA Compliant Rooms 22 And 13 C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2013 Interior Existing Toilet Stall Does Not Meet Minimum ADA RequirementsRooms 44.1 And 36.1 C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2013 Plumbing Existing Lavatory/Sink Is Not ADA Compliant No Covers Under Sink C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Site Curb Ramp Does Not Meet Minimum ADA Compliance Requirements Plan West C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Site Car Accessible Parking Spaces Do Not Meet ADA Requirements C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Site Van Accessible Parking Spaces Are Not Properly Striped C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Site Exterior Signage At Accessible Parking Area Does Not Meet ADA Requirements
Fading. C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2010 Exterior Brick Exterior Repointing Plan West C Deficiency is included in a CIP project
Cary Reynolds Elementary School 2 Building 2010 Roofing Modified Roof Covering Replacement Roof Leaks C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2010 Roofing Membrane Flashing At Parapet (>2') Repair C Deficiency is included in a CIP project
Cary Reynolds Elementary School 2 Building 2011 Roofing Modified Roof Covering Replacement Leaks C Deficiency is included in a CIP project
41 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Cary Reynolds Elementary School 3 Building 2011 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2011 Roofing Membrane Flashing At Parapet (>2') Repair C Deficiency is included in a CIP project
Cary Reynolds Elementary School 2 Building 2011 Mechanical Ductwork Replacement (SF Basis) Null C Deficiency is included in a CIP project
Cary Reynolds Elementary School 2 Building 2012 Roofing Modified Roof Covering Replacement Roof Leaks C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2012 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2012 Roofing Membrane Flashing At Parapet (>2') Repair C Deficiency is included in a CIP project
Cary Reynolds Elementary School 2 Building 2013 Roofing Modified Roof Covering Replacement Roof Leaks C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2013 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2013 Roofing Membrane Flashing At Parapet (>2') Repair C Deficiency is included in a CIP project
Cary Reynolds Elementary School 2 Building 2013 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility
Plan West C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Foliage Growing C Deficiency is included in a CIP project
Cary Reynolds Elementary School 2 Building 2020 Roofing Gutter Joint Repair Leaking C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2020 Roofing Gutter Replacement Plan North, West C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2020 Roofing Metal Downspout Installation Plan North C Deficiency is included in a CIP project
Cary Reynolds Elementary School 2 Building 2020 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility
Plan North, South C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Site Asphalt Walks Replacement Plan East C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Site Concrete Walks Replacement Plan South, North. C Deficiency is included in a CIP project
Cary Reynolds Elementary School 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility
Plan West, North, South C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2013 Interior Interior Door Hardware Replacement Courtyard (North, East) C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2020 Exterior Exterior Metal Door Repainting Paint Fading C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2010 Exterior Exterior Metal Door Repainting Paint Peeling C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2012 Exterior Exterior Metal Door Repainting Paint Peeling C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2013 Exterior Exterior Metal Door Repainting Plan East And South C Deficiency is included in a CIP project
Cary Reynolds Elementary School 3 Building 2013 Exterior Exterior Metal Door Repainting Plan West. C Deficiency is included in a CIP project
Cedar Grove Elementary School 3 Building 2010 Interior Entry Door Does Not Have Power Assist Device Missing C Deficiency is included in a CIP project
Cedar Grove Elementary School 3 Building 2010 Conveyances Platform Lift Needed for Access Missing C Deficiency is included in a CIP project
Cedar Grove Elementary School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsMissing(Modify Full) C Deficiency is included in a CIP project
Cedar Grove Elementary School 3 Building 2010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
Missing C Deficiency is included in a CIP project
Cedar Grove High School 3 Building 5010 Conveyances Platform Lift Needed for Access Install A Lift At The Cafeteria C Deficiency is included in a CIP project
Cedar Grove High School 3 Building 5010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsNo (Modify Full)
Counter Present C Deficiency is included in a CIP project
Cedar Grove Middle School 3 Building 4010 Interior Entry Door Does Not Have Power Assist Device At Entry Door Missing C Deficiency is included in a CIP project
Cedar Grove Middle School 3 Building 4010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding C Deficiency is included in a CIP project
Cedar Grove Middle School 3 Building 4010 Roofing Roof Access Ladder Replacement Not Well Anchored To Wall (Missing Bolts) C Deficiency is included in a CIP project
Some Shingles Missing (Blown Off). Need To
Chamblee Middle School 2 Building 4010 Roofing Asphalt Shingle Roof Covering Replacement C Deficiency is included in a CIP project
Replace Missing Shingles.
Chamblee Middle School 2 Building 4010 Roofing Modified Roof Covering Replacement Old, Bubbles, Leaks And All C Deficiency is included in a CIP project
Chamblee Middle School 3 Building 4010 Roofing Roof Drain Cleaning Clogged And All Roof C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4010 Interior Entry Door Does Not Have Power Assist Device C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4010 Conveyances Platform Lift Needed for Access C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4010 Plumbing Restroom Is Not ADA Compliant C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4011 Plumbing Restroom Is Not ADA Compliant C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Interior Entry Door Does Not Have Power Assist Device C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Conveyances Platform Lift Needed for Access C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Plumbing Restroom Is Not ADA Compliant C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Site Car Accessible Parking Spaces Do Not Meet ADA Requirements None Provided C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Site Van Accessible Parking Spaces Do Not Meet ADA Requirements None Provided C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA
NoneRequirements
Provided C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Site Exterior Signage At Accessible Parking Area Does Not Meet ADA Requirements
None Provided C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4013 Plumbing Restroom Is Not ADA Compliant C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4013 Specialties Counter Heights Exceed Maximum ADA Height RequirementsNone (Modify Full)
Provided C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4013 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA
NoneRequirements
Provided C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4010 Roofing Membrane Flashing At Parapet (>2') Repair Cracking Sealant C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4010 Mechanical Unit Ventilator Replacement C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4010 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4011 Exterior Brick Exterior Repointing Weathered And Eroded C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4011 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4011 Roofing Membrane Flashing At Parapet (>2') Repair Cracking Sealant C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4011 Roofing Roof Drain Cleaning Debris Clogging C Deficiency is included in a CIP project
42 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Champion Middle Theme 3 Building 4011 Plumbing Toilet Replacement C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4011 Plumbing Urinal Replacement C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4011 Mechanical Unit Ventilator Replacement C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4011 Mechanical Fan Coil (Chilled Water) HVAC Component Replacement Hot And Chilled Water Unit Ventilators C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4011 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4011 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4011 Mechanical Large Diameter Exhausts/Hoods Replacement C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4011 Electrical Panelboard Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4012 Roofing Metal Roof Architectural Roof Covering Replacement Fallen Rake C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Roofing Debris In Gutter Removal C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Roofing Membrane Flashing At Parapet (>2') Repair Cracking C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Roofing Roof Drain Cleaning Debris Clogging C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Interior Athletic Sport Flooring Replacement Beyond Useful Life C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Plumbing Water Storage Tank Replacement C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Plumbing Gas Water Heater Replacement C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4012 Mechanical Unit Ventilator Replacement C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4012 Mechanical Fan Coil (Chilled Water) HVAC Component Replacement C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4012 Mechanical Fan Coil (Chilled Water) HVAC Component Replacement C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4012 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4013 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4013 Roofing Roof Drain Cleaning Debris Clogging C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4013 Mechanical Boiler Replacement C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4013 Mechanical Heat Exchanger Replacement C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4013 Mechanical Circulation Pump Replacement C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4013 Mechanical Circulation Pump Replacement C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4013 Mechanical Exterior Metal Cooling Tower Replacement C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4013 Mechanical Package DX Unit Replacement C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4013 Mechanical Package DX Unit Replacement C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4013 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4013 Mechanical Package Roof Top Unit Replacement C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4020 Roofing Metal Downspout Installation Missing C Deficiency is included in a CIP project
Champion Middle Theme 3 Site Concrete Walks Replacement Cracked C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4012 Exterior Aluminum Window Replacement Beyond Useful Life C Deficiency is included in a CIP project
Champion Middle Theme 3 Site Asphalt Driveway Replacement Beyond Useful Life - Cracked C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4010 Exterior Brick Exterior Repointing Weathered And Eroded C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Exterior Brick Exterior Repointing Weathered And Eroded C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4013 Exterior Brick Exterior Repointing Weathered And Eroded C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4010 Electrical Canopy Lighting Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4011 Electrical Canopy Lighting Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Electrical Canopy Lighting Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4013 Electrical Canopy Lighting Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4010 Electrical Distribution Panel Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4013 Electrical Distribution Panel Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4013 Electrical Distribution Panel Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4010 Electrical Electrical Transformer Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4012 Electrical Electrical Transformer Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4012 Electrical Electrical Transformer Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4013 Electrical Electrical Transformer Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4013 Electrical Electrical Transformer Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4013 Electrical Exterior Dry Type Transformer Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4010 Electrical Exterior Mounted Building Lighting Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Electrical Exterior Mounted Building Lighting Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4013 Electrical Exterior Mounted Building Lighting Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4010 Interior Interior Door Replacement Beyond Useful Life C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4011 Interior Interior Door Replacement Beyond Useful Life C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Interior Interior Door Replacement Beyond Useful Life - Damaged C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4013 Interior Interior Door Replacement Beyond Useful Life - Damaged C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4010 Electrical Interior Power Wiring Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4011 Electrical Interior Power Wiring Replacement Old C Deficiency is included in a CIP project
43 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Champion Middle Theme 3 Building 4012 Electrical Interior Power Wiring Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4013 Electrical Interior Power Wiring Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4010 Electrical Lighting Fixtures Replacement C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4011 Electrical Lighting Fixtures Replacement Corridors Are Led, Rest Are Old C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Electrical Lighting Fixtures Replacement C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4013 Electrical Lighting Fixtures Replacement C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4010 Exterior Metal Exterior Door Replacement Beyond Useful Life C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4011 Exterior Metal Exterior Door Replacement Beyond Useful Life C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4012 Exterior Metal Exterior Door Replacement Beyond Useful Life C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4013 Exterior Metal Exterior Door Replacement Beyond Useful Life C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4013 Electrical Motor Control Center Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4010 Electrical Panelboard Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4010 Electrical Panelboard Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4010 Electrical Panelboard Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4010 Electrical Panelboard Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4010 Electrical Panelboard Replacement Old, Missing Cover C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4010 Electrical Panelboard Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4012 Electrical Panelboard Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4012 Electrical Panelboard Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4013 Electrical Panelboard Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4013 Electrical Panelboard Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4013 Electrical Panelboard Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4013 Electrical Panelboard Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4013 Electrical Panelboard Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4011 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4013 Electrical Public Address System Head-End Requires Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4010 Electrical Public Address System Replacement, Non-main Building Old C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4011 Electrical Public Address System Replacement, Non-main Building Old C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Electrical Public Address System Replacement, Non-main Building Old C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4013 Electrical Public Address System Replacement, Non-main Building Old C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4010 Roofing Roof Drain Cleaning Debris Clogging C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Plumbing Shower Replacement C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4012 Exterior Storefront/Curtain Wall Replacement (Bldg SF) C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4010 Exterior Storefront/Curtain Wall Replacement (Bldg SF) C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4011 Exterior Storefront/Curtain Wall Replacement (Bldg SF) Beyond Useful Life C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4011 Exterior Storefront/Curtain Wall Replacement (Bldg SF) C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4010 Electrical Switchgear Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4013 Electrical Switchgear Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 2 Building 4013 Electrical Switchgear Replacement Old C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Plumbing Toilet Replacement C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4013 Plumbing Toilet Replacement C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4012 Plumbing Urinal Replacement C Deficiency is included in a CIP project
Champion Middle Theme 3 Building 4013 Plumbing Urinal Replacement C Deficiency is included in a CIP project
Chapel Hill Elementary School 3 Building 2010 Conveyances Platform Lift Needed for Access None Available C Deficiency is included in a CIP project
Chapel Hill Elementary School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsNon-ADA
(Modify Full) C Deficiency is included in a CIP project
Chapel Hill Middle School 3 Building 4010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsNon-ADA
(Modify Full) C Deficiency is included in a CIP project
Chapel Hill Middle School 2 Building 4010 Exterior Storefront / Curtain Wall Repair Replace Sealant C Deficiency is included in a CIP project
Chapel Hill Middle School 2 Building 4010 Mechanical Copper Tube Boiler Replacement Mech Room 98.14 C Deficiency is included in a CIP project
Chapel Hill Middle School 2 Building 4010 Mechanical Copper Tube Boiler Replacement Mech Room C Deficiency is included in a CIP project
Chapel Hill Middle School 2 Building 4010 Mechanical Heat Exchanger Replacement Mech Room C Deficiency is included in a CIP project
Chapel Hill Middle School 3 Building 4010 Mechanical Circulation Pump Replacement Mech Room C Deficiency is included in a CIP project
Chapel Hill Middle School 3 Building 4010 Mechanical Circulation Pump Replacement Mech Room C Deficiency is included in a CIP project
Chapel Hill Middle School 2 Building 4010 Mechanical Gas Unit Heater Replacement Mech Room C Deficiency is included in a CIP project
Chapel Hill Middle School 2 Building 4010 Mechanical Exterior Metal Cooling Tower Replacement Mech Room Yard C Deficiency is included in a CIP project
Chapel Hill Middle School 2 Building 4010 Mechanical Air Cooled Condenser Replacement Roof C Deficiency is included in a CIP project
Chapel Hill Middle School 2 Building 4010 Mechanical Fan Coil Unit Replacement Throughout C Deficiency is included in a CIP project
Chapel Hill Middle School 2 Building 4010 Mechanical Heat Pump HVAC Component Replacement Throughout C Deficiency is included in a CIP project
Chapel Hill Middle School 3 Building 4010 Mechanical Testing And Balancing Throughout C Deficiency is included in a CIP project
Chapel Hill Middle School 3 Building 4010 Mechanical Kitchen Exhaust Hood Replacement Kitchen C Deficiency is included in a CIP project
44 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Chapel Hill Middle School 3 Building 4010 Mechanical Kitchen Exhaust Hood Replacement Dishwasher Hood C Deficiency is included in a CIP project
Chapel Hill Middle School 2 Building 4010 Mechanical Ductwork Replacement (SF Basis) Throughout C Deficiency is included in a CIP project
Chapel Hill Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement Roof C Deficiency is included in a CIP project
Chapel Hill Middle School 3 Building 4010 Mechanical Large Diameter Exhausts/Hoods Replacement C Deficiency is included in a CIP project
Chapel Hill Middle School 3 Building 4010 Mechanical Large Diameter Exhausts/Hoods Replacement Roof C Deficiency is included in a CIP project
Clarkston High School 3 Building 5010 Interior Existing Door Hardware Is Not ADA Compliant All Interior Door Hardware Not Compliant C Deficiency is included in a CIP project
Clarkston High School 3 Building 5011 Interior Existing Door Hardware Is Not ADA Compliant All Interior Door Hardware Not Compliant C Deficiency is included in a CIP project
Clarkston High School 3 Building 5010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsNot (Modify Full)
Compliant C Deficiency is included in a CIP project
Clarkston High School 3 Building 5010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
No ADA Signage C Deficiency is included in a CIP project
Clarkston High School 3 Building 5012 Interior Existing Door Hardware Is Not ADA Compliant All Interior Door Hardware Not Compliant C Deficiency is included in a CIP project
Clarkston High School 3 Building 5010 Exterior Exterior Entry Door Hardware Is Not ADA Compliant Not Compliant C Deficiency is included in a CIP project
Gym Has Raised Court And Stage That Is Not
Clarkston High School 3 Building 5012 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation C Deficiency is included in a CIP project
ADA Accessible
Entry Doors Have Power Assist Hardware, No
Clarkston High School 3 Building 5013 Exterior Exterior Entry Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
External Button To Activate
Clarkston High School 3 Building 5013 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
No ADA Signage C Deficiency is included in a CIP project
Clarkston High School 2 Building 5012 Mechanical Air Cooled Condenser Replacement 2 Ton, Damaged C Deficiency is included in a CIP project
Clarkston High School 3 Building 5011 Plumbing Condensate Drain Repair Damaged C Deficiency is included in a CIP project
Clarkston High School 3 Building 5012 Plumbing Condensate Drain Repair Damaged, Needs Repair C Deficiency is included in a CIP project
Columbia Elementary School 3 Building 2010 Interior Entry Door Does Not Have Power Assist Device At Main Entrance C Deficiency is included in a CIP project
Columbia Elementary School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsMissing(Modify Full) C Deficiency is included in a CIP project
Columbia Elementary School 3 Building 2010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
Cafeteria Stage C Deficiency is included in a CIP project
Columbia Elementary School 3 Site Concrete Walks Replacement C Deficiency is included in a CIP project
Columbia High School 3 Building 5014 Interior Entry Door Does Not Have Power Assist Device Not Installed C Deficiency is included in a CIP project
Columbia High School 3 Building 5010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation C Deficiency is included in a CIP project
Columbia High School 3 Building 5015 Interior Entry Door Does Not Have Power Assist Device Not Installed C Deficiency is included in a CIP project
Cross Keys High School 3 Building 5010 Conveyances Platform Lift Needed for Access Install Platform Lift To The Stage C Deficiency is included in a CIP project
3 Stairway Wheelchair Lifts Are Broken And
Need To Be Replaced. Lift To 100 Level
Cross Keys High School 3 Building 5010 Conveyances Platform Lift Needed for Access C Deficiency is included in a CIP project
Classrooms, 400 Classroom Hallway, And Lift
To Media Center Stairs
Cross Keys High School 3 Building 5010 Electrical Lightning Protection System Installation C Deficiency is included in a CIP project
Cross Keys High School 3 Building 5011 Electrical Lightning Protection System Installation C Deficiency is included in a CIP project
Cross Keys High School 3 Building 5020 Electrical Lightning Protection System Installation C Deficiency is included in a CIP project
Cross Keys High School 3 Building 5021 Electrical Lightning Protection System Installation C Deficiency is included in a CIP project
Cross Keys High School 3 Building 5010 Interior Interior Door Replacement C Deficiency is included in a CIP project
Cross Keys High School 3 Building 5010 Exterior Brick Exterior Repointing C Deficiency is included in a CIP project
Replace Deteriorated Roof Above Kitchen
Cross Keys High School 2 Building 5010 Roofing Modified Roof Covering Replacement C Deficiency is included in a CIP project
And Cafe
Repair Flashing At Rooftop Equipment Above
Cross Keys High School 3 Building 5010 Roofing Membrane Flashing At Parapet (>2') Repair C Deficiency is included in a CIP project
The 300 Wing
Cross Keys High School 3 Building 5010 Roofing Metal Downspout Replacement C Deficiency is included in a CIP project
Cross Keys High School 3 Building 5010 Roofing Roof Drain Cleaning C Deficiency is included in a CIP project
Cross Keys High School 3 Building 5010 Plumbing Gas Water Heater Replacement Aged And Beyond Useful Life. C Deficiency is included in a CIP project
Cross Keys High School 3 Building 5010 Plumbing Toilet Replacement Damaged C Deficiency is included in a CIP project
Cross Keys High School 2 Building 5010 Mechanical Ductless Split System AC Replacement Aged And Beyond Useful Life. C Deficiency is included in a CIP project
Package Unit Over Main Office Is At Beyond
Cross Keys High School 2 Building 5010 Mechanical Package DX Unit Replacement C Deficiency is included in a CIP project
Useful Life. Replace
Cross Keys High School 3 Building 5010 Mechanical Large Diameter Exhausts/Hoods Replacement C Deficiency is included in a CIP project
Replace Old And Obsolete Lights In Gym And
Cross Keys High School 3 Building 5010 Electrical Lighting Fixtures Replacement Cafeteria In Particular, And Other Locations C Deficiency is included in a CIP project
As Needed
Cross Keys High School 3 Building 5020 Roofing Modified Covering Has Blisters That Should Be Repaired C Deficiency is included in a CIP project
Cross Keys High School 3 Building 5020 Roofing Roof Operable Hatch Repair C Deficiency is included in a CIP project
Cross Keys High School 2 Building 5020 Fire and Life Safety Wall Pack Lighting Installation C Deficiency is included in a CIP project
45 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Top Layer Is Significantly Deteriorated To The
Cross Keys High School 2 Building 5021 Roofing Modified Roof Covering Replacement C Deficiency is included in a CIP project
Point That Roof Underlayer Is Visible. Replace
Cross Keys High School 2 Building 5021 Fire and Life Safety Wall Pack Lighting Installation C Deficiency is included in a CIP project
Asphalt Drives Are Deteriorated And
Cross Keys High School 3 Site Asphalt Driveway Replacement C Deficiency is included in a CIP project
Damaged Throughout The Campus
Cross Keys High School 3 Site Concrete Walks Replacement South Sidewalk Is Damaged C Deficiency is included in a CIP project
Sidewalks Are Cracked South Of Building
Cross Keys High School 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility C Deficiency is included in a CIP project
5010
Doors Connecting The Auto Shop To
Cross Keys High School 3 Building 5020 Interior Interior Door Replacement Construction Area Are Damaged And Need To C Deficiency is included in a CIP project
Be Replaced
Doraville Administrative 3 Building 8010 Plumbing Restroom Grab Bars Are Not ADA Compliant Missing C Deficiency is included in a CIP project
Doraville United Elementary School 3 Building 2010 Interior Entry Door Does Not Have Power Assist Device Not Furnished At Main Entrance C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2010 Exterior Storefront/Curtain Wall Replacement (Bldg SF) C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2011 Exterior Storefront/Curtain Wall Replacement (Bldg SF) Beyond Useful Life C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2012 Exterior Storefront/Curtain Wall Replacement (Bldg SF) C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2010 Interior Entry Door Does Not Have Power Assist Device Missing At Main Door Exit C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2010 Interior Access Is Not ADA Compliant Door Knob Non-ADA C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2010 Interior Access Is Not ADA Compliant Door Knobs Non-ADA C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Installed C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsNo (Modify Full) Top Available
Low Counter C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
Missing C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Not Installed C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement Beyond Useful Life C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2011 Interior Interior Door Hardware Replacement Beyond Useful Life C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2013 Electrical Lightning Protection System Installation Not Installed C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Not Installed C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2012 Interior Interior Door Hardware Replacement Beyond Useful Life C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2010 Interior Interior Door Replacement Beyond Useful Life C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2011 Interior Interior Door Replacement Beyond Useful Life C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2012 Interior Interior Door Replacement Beyond Useful Life C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2010 Exterior Metal Exterior Door Replacement Beyond Useful Life C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2012 Exterior Metal Exterior Door Replacement Beyond Useful Life C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2010 Exterior Brick Exterior Repointing Eroded Mortar C Deficiency is included in a CIP project
Several Of The Concrete Overhangs Are
Crumbling And Breaking Off. All Overhands
Are Potentially Structurally Compromised.
Dresden Elementary School 2 Building 2010 Exterior Concrete Pre-Cast Panel Replacement (Bldg SF) C Deficiency is included in a CIP project
Recommended That A Structural Study Is
Conducted. Some Columns Are Water Eroded
Down To Rebar.
Dresden Elementary School 2 Building 2010 Mechanical Gas Piping Replacement (SF Basis) Throughout C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life
Throughout C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2010 Plumbing Sanitary Sewer Piping Replacement Throughout C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2010 Mechanical Cast Iron Water Boiler Replacement Mech Room C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2010 Mechanical Circulation Pump Replacement Mech Room C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2010 Mechanical Infrared Electric Radiant Heater Replacement Kitchen C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2010 Mechanical Infrared Electric Radiant Heater Replacement Throughout C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement Throughout C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2010 Mechanical Testing And Balancing Throughout C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Throughout C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2010 Mechanical Ductwork Replacement (SF Basis) Throughout C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2010 Mechanical Large Diameter Exhausts/Hoods Replacement No Roof Access C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2010 Electrical Switchgear Replacement Old, Elec Room C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Old, Elec Room C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Old Classrooms Old Fl. C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2010 Electrical Panelboard Replacement Old, Elec Room C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2010 Electrical Panelboard Replacement Old, Elec Room C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2010 Electrical Panelboard Replacement Old, Elec Room C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2011 Exterior Brick Exterior Repointing Eroded Mortar C Deficiency is included in a CIP project
46 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Several Of The Concrete Overhands Are
Crumbling And Breaking Off. All Overhangs
Are Potentially Structurally Compromised.
Dresden Elementary School 2 Building 2011 Exterior Concrete Pre-Cast Panel Replacement (Bldg SF) C Deficiency is included in a CIP project
Recommended That A Structural Study Is
Conducted. Come Columns Are Water Eroded
Down To Rebar
Dresden Elementary School 2 Building 2011 Mechanical Infrared Electric Radiant Heater Replacement Storage 21.6 C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2011 Mechanical Heat Pump HVAC Component Replacement Throughout C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2011 Mechanical Testing And Balancing Throughout C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2011 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Throughout C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2011 Mechanical Ductwork Replacement (SF Basis) Throughout C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2011 Electrical Exterior Electrical Enclosure Replacement Not Installed C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement Old Fl In Crs C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2011 Electrical Panelboard Replacement Old, Elec Room C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2012 Exterior Brick Exterior Repointing Eroded Mortar C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2012 Exterior Concrete Pre-Cast Panel Replacement (Bldg SF) See Note For Building 2010 C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2012 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life
Throughout C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2012 Plumbing Sanitary Sewer Piping Replacement Throughout C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2012 Mechanical Infrared Electric Radiant Heater Replacement Corridor C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2012 Mechanical Heat Pump HVAC Component Replacement Throughout C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2012 Mechanical Testing And Balancing Throughout C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2012 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Throughout C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2012 Mechanical Ductwork Replacement (SF Basis) Throughout C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2012 Electrical Canopy Lighting Replacement Old, Canopy C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2012 Electrical Lighting Fixtures Replacement Old, Classrooms C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2013 Mechanical Testing And Balancing Throughout C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2013 Mechanical HVAC VAV Box Replacement Throughout C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2013 Electrical Canopy Lighting Replacement Old, Exterior C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2013 Electrical Exterior Mounted Building Lighting Replacement Old, Exterior C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2013 Electrical Lighting Fixtures Replacement Old, Classroom Fl C Deficiency is included in a CIP project
Dresden Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Debris And Trees Growing C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2020 Mechanical Thru Wall AC Replacement Coach Office C Deficiency is included in a CIP project
Civil Study Needed At Gym As Soil Is Eroding
Dresden Elementary School 3 Site Site Requires Civil/Drainage Study C Deficiency is included in a CIP project
At Northwest Corner.
Dresden Elementary School 3 Site Asphalt Driveway Replacement Cracked And Beyond Useful Life C Deficiency is included in a CIP project
Dresden Elementary School 3 Electrical Pole Lighting Replacement Beyond Useful Life - Broken C Deficiency is included in a CIP project
Dresden Elementary School 3 Site Asphalt Walks Replacement Cracked Play Yard C Deficiency is included in a CIP project
Dresden Elementary School 3 Site Aluminum Covered Walkways Replacement Damaged C Deficiency is included in a CIP project
Dresden Elementary School 2 Building 2010 Exterior Wood Exterior Door Replacement Rotten C Deficiency is included in a CIP project
Druid Hills High School 3 Building 5010 Interior Entry Door Does Not Have Power Assist Device Add To Access Building C Deficiency is included in a CIP project
Druid Hills High School 3 Building 5010 Conveyances Platform Lift Needed for Access Non Available C Deficiency is included in a CIP project
Druid Hills High School 3 Building 5010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsNot (Modify Full) And Main Buildings.
Low Enough C Deficiency is included in a CIP project
Druid Hills High School 3 Building 5010 Specialties Seating is not ADA Compliant To Meet 2010 ADA C Deficiency is included in a CIP project
Druid Hills High School 3 Building 5010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
Missing C Deficiency is included in a CIP project
Druid Hills High School 3 Building 5011 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
Missing C Deficiency is included in a CIP project
Druid Hills High School 3 Building 5030 Interior Existing Toilet Stall Does Not Meet Minimum ADA RequirementsToo Small, No Grab Bars. C Deficiency is included in a CIP project
Druid Hills High School 3 Building 5030 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
Missing C Deficiency is included in a CIP project
Druid Hills High School 3 Building 5040 Specialties Counter Heights Exceed Maximum ADA Height RequirementsNo (Modify Full) Top Provided
Low Counter C Deficiency is included in a CIP project
Druid Hills High School 2 Building 5010 Exterior Composite Exterior Siding Replacement (Bldg SF) Rotting Wood And Ext. Detailing C Deficiency is included in a CIP project
Druid Hills High School 3 Building 5010 Mechanical Testing And Balancing Throughout C Deficiency is included in a CIP project
Druid Hills High School 2 Building 5010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Throughout C Deficiency is included in a CIP project
Beyond Useful Life - Low Roof. Built Up
Druid Hills High School 2 Building 5011 Roofing Built-up Roofing Replacement Roofing Over Mod. Bit Roof Both Assemblies C Deficiency is included in a CIP project
Need To Be Replaced
Druid Hills High School 3 Building 5011 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Druid Hills High School 2 Building 5011 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Throughout C Deficiency is included in a CIP project
Druid Hills High School 2 Building 5011 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Throughout C Deficiency is included in a CIP project
Druid Hills High School 2 Building 5020 Roofing Modified Roof Covering Replacement Beyond Useful Life C Deficiency is included in a CIP project
Druid Hills High School 3 Building 5020 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding C Deficiency is included in a CIP project
Druid Hills High School 2 Building 5020 Mechanical Gas Piping Replacement (SF Basis) Throughout C Deficiency is included in a CIP project
47 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Druid Hills High School 2 Building 5020 Mechanical Cast Iron Water Boiler Replacement 2880 Mbh Boiler Room C Deficiency is included in a CIP project
Druid Hills High School 2 Building 5020 Mechanical Steam Heat Exchanger Replacement 270 Gpm Boiler Room C Deficiency is included in a CIP project
Druid Hills High School 3 Building 5020 Mechanical Circulation Pump Replacement Boiler Room C Deficiency is included in a CIP project
Druid Hills High School 3 Building 5020 Mechanical Testing And Balancing Throughout C Deficiency is included in a CIP project
Druid Hills High School 2 Building 5020 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Throughout C Deficiency is included in a CIP project
Druid Hills High School 2 Building 5020 Mechanical Ductwork Replacement (SF Basis) Throughout C Deficiency is included in a CIP project
Druid Hills High School 2 Building 5021 Roofing Modified Roof Covering Replacement Beyond Useful Life C Deficiency is included in a CIP project
Druid Hills High School 3 Building 5021 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Druid Hills High School 2 Building 5021 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Throughout C Deficiency is included in a CIP project
Druid Hills High School 2 Building 5021 Mechanical Ductwork Replacement (SF Basis) Throughout C Deficiency is included in a CIP project
Druid Hills High School 2 Building 5021 Electrical Panelboard Replacement Old, Elec Room C Deficiency is included in a CIP project
Druid Hills High School 2 Building 5021 Electrical Panelboard Replacement Old, Elec Room C Deficiency is included in a CIP project
Druid Hills High School 2 Building 5030 Roofing Built-up Roofing Replacement Beyond Useful Life C Deficiency is included in a CIP project
Druid Hills High School 2 Building 5030 Mechanical Gas Piping Replacement (SF Basis) Throughout C Deficiency is included in a CIP project
Druid Hills High School 2 Building 5030 Mechanical Cast Iron Water Boiler Replacement 770 Mbh Boiler Room C Deficiency is included in a CIP project
Dunaire Elementary School 3 Building 2010 Interior Access Is Not ADA Compliant Door Knobs Not Compliant C Deficiency is included in a CIP project
Dunaire Elementary School 3 Building 2010 Conveyances Platform Lift Needed for Access No ADA Access C Deficiency is included in a CIP project
Dunaire Elementary School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsNot (Modify Full)
Low Enough C Deficiency is included in a CIP project
Dunwoody Elementary School 3 Building 2010 Exterior Exterior Entry Door Hardware Is Not ADA Compliant ADA Power Button C Deficiency is included in a CIP project
Dunwoody Elementary School 3 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
No Sign At Entry, Install (North) C Deficiency is included in a CIP project
Dunwoody High School 3 Building 5011 Plumbing Restroom Grab Bars Are Not ADA Compliant Stalls Are Missing Vertical Grab Bars C Deficiency is included in a CIP project
Dunwoody High School 3 Building 5011 Specialties Counter Heights Exceed Maximum ADA Height Requirements (Modify Full) C Deficiency is included in a CIP project
Dunwoody High School 3 Building 5012 Plumbing Restroom Grab Bars Are Not ADA Compliant Install Vertical Grab Bars C Deficiency is included in a CIP project
Dunwoody High School 3 Building 5012 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
Gym Stage Is Not Accessible C Deficiency is included in a CIP project
Eagle Woods Academy 3 Building 8010 Exterior Exterior Entry Door Hardware Is Not ADA Compliant No Power Assist Hardware Or Button. Add. C Deficiency is included in a CIP project
Front And Admin Counter Not ADA
Eagle Woods Academy 3 Building 8010 Specialties Counter Heights Exceed Maximum ADA Height Requirements (Modify Full) C Deficiency is included in a CIP project
Compliant. Add.
No ADA Access To Stage At Room 102, Media
Eagle Woods Academy 3 Building 8010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation C Deficiency is included in a CIP project
Center. Install Ramp Or Lift To Comply.
Eagle Woods Academy 3 Building 8010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
No ADA Sign At Entry. Add. C Deficiency is included in a CIP project
No Power Assist. Install Hardware And
Eagle Woods Academy 3 Building 8020 Exterior Exterior Entry Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Button.
Spots Provided At Other Parts Of The Site But
Eagle Woods Academy 3 Building 8020 Site Car Accessible Parking Spaces Do Not Meet ADA Requirements C Deficiency is included in a CIP project
Recommend Ones Next To 8020
Spots Provided At Other Parts Of The Site But
Eagle Woods Academy 3 Building 8020 Site Van Accessible Parking Spaces Do Not Meet ADA Requirements C Deficiency is included in a CIP project
Recommend Ones Next To 8020
Eagle Woods Academy 3 Building 8020 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
No Sign. Install New C Deficiency is included in a CIP project
Early Learning Academy 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Early Learning Academy 3 Building 2010 Conveyances Platform Lift Needed for Access Missing C Deficiency is included in a CIP project
Early Learning Academy 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsNo (Modify
LowerFull)
Counter C Deficiency is included in a CIP project
East Campus #1 DeKalb Alternative 3 Building 8010 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
East Campus #1 DeKalb Alternative 3 Building 8010 Plumbing Existing Lavatory/Sink Is Not ADA Compliant C Deficiency is included in a CIP project
East Campus #1 DeKalb Alternative 3 Building 8010 Plumbing Restroom Grab Bars Are Not ADA Compliant Grab Bars Missing And Not In The Right Place C Deficiency is included in a CIP project
East Campus #1 DeKalb Alternative 3 Building 8020 Plumbing Existing Lavatory/Sink Pipe Insulation Replacement Replace Insulation On Sink Pipes C Deficiency is included in a CIP project
East Campus #1 DeKalb Alternative 3 Site Curb Ramp Does Not Meet Minimum ADA Compliance Requirements
No Tactical Warning, Too Steep C Deficiency is included in a CIP project
East Campus #1 DeKalb Alternative 3 Site Curb Ramp Does Not Meet Minimum ADA Compliance Requirements
No Tactile Warning, Steep, One Blocked C Deficiency is included in a CIP project
East Campus #1 DeKalb Alternative 3 Site Car Accessible Parking Spaces Do Not Meet ADA Requirements
None Provided C Deficiency is included in a CIP project
East Campus #1 DeKalb Alternative 3 Site Van Accessible Parking Spaces Do Not Meet ADA Requirements C Deficiency is included in a CIP project
East Campus #1 DeKalb Alternative 3 Site Sidewalk Longitudinal Or Cross Slope Exceeds Maximum Slope
NwCriteria
Building 8010 Too Steep X2 Locations C Deficiency is included in a CIP project
East Campus #1 DeKalb Alternative 3 Site Car Accessible Parking Spaces Restiriping North And South Of Building 8010 C Deficiency is included in a CIP project
East Campus #1 DeKalb Alternative 3 Site Van Accessible Parking Spaces Are Not Properly Striped North And South Of Building 8010 C Deficiency is included in a CIP project
Replace Worn And Leaning Sign North Of
East Campus #1 DeKalb Alternative 3 Site Exterior Signage At Accessible Parking Area Does Not Meet ADA Requirements C Deficiency is included in a CIP project
Building 8010
Directional Signage Points To Each Other, No
East Campus #1 DeKalb Alternative 3 Site Exterior Signage At Accessible Parking Area Does Not Meet ADA Requirements C Deficiency is included in a CIP project
Spaces Provided Or Signed
East Campus #2 Transportation 3 Site Car Accessible Parking Spaces Restiriping At Main Entry Building 8010 C Deficiency is included in a CIP project
East Campus #2 Transportation 3 Site Van Accessible Parking Spaces Are Not Properly Striped At Main Entry Building 8010 C Deficiency is included in a CIP project
48 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Evansdale Elementary School 2 Building 2020 Plumbing Water Heater Replacement Gym Storage C Deficiency is included in a CIP project
Evansdale Elementary School 3 Building 2010 Interior Entry Door Does Not Have Power Assist Device Missing C Deficiency is included in a CIP project
Evansdale Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant Doors At Media Center C Deficiency is included in a CIP project
Evansdale Elementary School 3 Building 2010 Conveyances Platform Lift Needed for Access Missing C Deficiency is included in a CIP project
Evansdale Elementary School 3 Building 2010 Specialties (Modify
Counter Heights Exceed Maximum ADA Height RequirementsNo LowerFull)
Counter Provided C Deficiency is included in a CIP project
Fairington Elementary School 2 Building 2010 Mechanical Boiler Replacement 2250 Mbh - Beyond Useful Life - Room 42.3 C Deficiency is included in a CIP project
Fairington Elementary School 2 Building 2010 Mechanical Heat Exchanger Replacement 420 Gpm - Beyond Useful Life - Room 42.3 C Deficiency is included in a CIP project
Fairington Elementary School 2 Building 2010 Mechanical Electric Unit Heater Replacement Beyond Useful Life - Room 42.3 C Deficiency is included in a CIP project
Fairington Elementary School 2 Building 2010 Mechanical Exterior Metal Cooling Tower Replacement 140 Tons - Beyond Useful Life - Room 42.3 C Deficiency is included in a CIP project
Fairington Elementary School 2 Building 2011 Exterior EIFS Exterior Replacement (Bldg SF) Old, Stained, Replace C Deficiency is included in a CIP project
Fairington Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Debris, Clean C Deficiency is included in a CIP project
Fairington Elementary School 3 Building 2020 Roofing Gutter Replacement Detached, Reinstall, Damaged. C Deficiency is included in a CIP project
Fairington Elementary School 3 Building 2020 Interior Athletic Sport Flooring Replacement Cracked, Bumpy Throughout. Replace. C Deficiency is included in a CIP project
Fairington Elementary School 3 Site Asphalt Driveway Replacement Cracked, South Of 2010 C Deficiency is included in a CIP project
Fairington Elementary School 3 Site Asphalt Driveway Replacement Cracked, Deficient C Deficiency is included in a CIP project
Concrete Cracked At Walkway Directly South-
Fairington Elementary School 3 Site Concrete Walks Replacement C Deficiency is included in a CIP project
West Of Building 2011 Back Egress Doors.
Fairington Elementary School 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility
Asphalt Crosswalk - Replace. C Deficiency is included in a CIP project
Fairington Elementary School 3 Building 2010 Interior Access Is Not ADA Compliant Add Power Assist Door If Necessary. C Deficiency is included in a CIP project
Fairington Elementary School 3 Building 2010 Exterior Exterior Entry Door Hardware Is Not ADA Compliant Add Power Assist. C Deficiency is included in a CIP project
Fairington Elementary School 3 Building 2010 Specialties (Modify
Counter Heights Exceed Maximum ADA Height RequirementsTall Full)Add Low And ADA Counter.
Counter. C Deficiency is included in a CIP project
No Ramp. Install Ramp (ADA Compliant) Or
Fairington Elementary School 3 Building 2010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation C Deficiency is included in a CIP project
Lift
Fairington Elementary School 3 Building 2010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
No Signage C Deficiency is included in a CIP project
Fairington Elementary School 3 Building 2020 Exterior Exterior Entry Door Hardware Is Not ADA Compliant ADA Power Assist. C Deficiency is included in a CIP project
Fairington Elementary School 3 Building 2020 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA
AddRequirements
ADA Sign C Deficiency is included in a CIP project
Fairington Elementary School 3 Site Van Accessible Parking Spaces Are Not Properly Striped C Deficiency is included in a CIP project
Fairington Elementary School 3 Site Exterior Signage At Accessible Parking Area Does Not Meet ADA
FadedRequirements
- Replace C Deficiency is included in a CIP project
Fairington Elementary School 3 Building 2010 Electrical 2 X 4 Interior Fluorescent Lighting Replacement Replace Old Cfls From Classrooms C Deficiency is included in a CIP project
Fairington Elementary School 3 Building 2011 Electrical 2 X 4 Interior Fluorescent Lighting Replacement Replace Old Cfls C Deficiency is included in a CIP project
Fairington Elementary School 3 Building 2020 Electrical 2 X 4 Interior Fluorescent Lighting Replacement Replace Old Cfls C Deficiency is included in a CIP project
Fernbank Science Center 3 Building 8010 Interior Existing Door Hardware Is Not ADA Compliant Office And Classrooms C Deficiency is included in a CIP project
Fernbank Science Center 3 Building 8010 Conveyances Platform Lift Needed for Access Both Lifts Are Not Working Well C Deficiency is included in a CIP project
Fernbank Science Center 3 Building 8020 Plumbing Restroom Is Not ADA Compliant No Restrooms In The Building C Deficiency is included in a CIP project
Flat Rock Elementary School 3 Building 2010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
No Ramp To Stage C Deficiency is included in a CIP project
Flat Shoals Elementary School 3 Building 2010 Plumbing Existing Lavatory/Sink Is Not ADA Compliant Add Pipe Insulation C Deficiency is included in a CIP project
Flat Shoals Elementary School 3 Building 2010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
Add Ramp For Stage C Deficiency is included in a CIP project
Freedom Middle School 3 Building 4010 Plumbing Existing Lavatory/Sink Pipe Insulation Replacement Add Insulation To Suite Drains C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2011 Exterior Exterior Metal Door Repainting C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2012 Exterior Exterior Metal Door Repainting C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2010 Interior Interior Door Hardware Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2020 Interior Interior Door Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2020 Exterior Metal Exterior Door Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2010 Exterior Metal Exterior Door Replacement Broken Glass C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2010 Exterior Brick Exterior Repointing C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2010 Roofing Debris In Gutter Removal C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2010 Roofing Metal Downspout Installation C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2010 Roofing Roof Drain Cleaning C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2010 Plumbing Gas Water Heater Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2010 Plumbing Water Heater Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2010 Plumbing Toilet Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2010 Plumbing Urinal Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2010 Mechanical Ductless Split System AC Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2010 Mechanical Fan Coil HVAC Component Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement 4 Ton Units C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2010 Mechanical Testing And Balancing C Deficiency is included in a CIP project
49 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Green Forrest Drive 3 Building 2010 Mechanical Kitchen Exhaust Hood Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2010 Mechanical Ductwork Replacement (SF Basis) C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2010 Mechanical Package Roof Top Unit Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2010 Mechanical Large Diameter Exhausts/Hoods Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2010 Mechanical Small Diameter Exhausts/Hoods Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2010 Electrical Canopy Lighting Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2010 Electrical Electrical Transformer Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2010 Electrical Exterior Dry Type Transformer Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2010 Electrical Distribution Panel Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2010 Electrical Distribution Panel Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2010 Electrical Panelboard Replacement 60 A Panelboard C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2010 Electrical Electrical Receptacle Replacement Burnt Receptacle C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2010 Electrical Public Address System Replacement, Non-main Building C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2011 Roofing Debris In Gutter Removal C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2011 Roofing Metal Downspout Installation C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2011 Roofing Roof Drain Cleaning C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2011 Mechanical Heat Pump HVAC Component Replacement 4 Ton Units C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2011 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2011 Mechanical Thru Wall AC Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2011 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2011 Mechanical Ductwork Replacement (SF Basis) C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2011 Electrical Canopy Lighting Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2011 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2011 Electrical Public Address System Replacement, Non-main Building C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2012 Roofing Debris In Gutter Removal C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2012 Roofing Roof Drain Cleaning C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2012 Plumbing Water Heater Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2012 Plumbing Toilet Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2012 Mechanical Air Compressor Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2012 Mechanical Boiler Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2012 Mechanical Heat Exchanger Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2012 Mechanical Circulation Pump Replacement 20 Hp Pumps C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2012 Mechanical Heat Pump HVAC Component Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2012 Mechanical Heat Pump HVAC Component Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2012 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2012 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2012 Mechanical Ductwork Replacement (SF Basis) C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2012 Mechanical Small Diameter Exhausts/Hoods Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2012 Electrical Canopy Lighting Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2012 Electrical Exterior Mounted Building Lighting Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2012 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2012 Electrical Panelboard Replacement 200 A C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2012 Electrical Panelboard Replacement 125 A C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2012 Electrical Electrical Receptacle Replacement Non GFI Receptacle C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2012 Electrical Public Address System Replacement, Non-main Building C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2020 Roofing Debris In Gutter Removal C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2020 Roofing Gutter Joint Repair C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2020 Roofing Metal Downspout Installation C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2020 Plumbing Water Heater Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2020 Plumbing Toilet Replacement C Deficiency is included in a CIP project
50 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Green Forrest Drive 3 Building 2020 Plumbing Urinal Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2020 Mechanical Electric Unit Heater Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2020 Mechanical Gas Unit Heater Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2020 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Green Forrest Drive 2 Building 2020 Mechanical Thru Wall AC Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2020 Electrical Canopy Lighting Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2020 Electrical H.I.D. Lighting Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Site Asphalt Driveway Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Site Concrete Walks Replacement C Deficiency is included in a CIP project
Green Forrest Drive 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2012 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2020 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2010 Exterior Exterior Entry Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2010 Electrical Public Address System Head-End Requires Replacement C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height Requirements (Modify Full) C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2012 Exterior Exterior Entry Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2020 Exterior Exterior Entry Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2012 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements C Deficiency is included in a CIP project
Green Forrest Drive 3 Building 2020 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements C Deficiency is included in a CIP project
Green Forrest Drive 3 Site Curb Ramp Does Not Meet Minimum ADA Compliance Requirements C Deficiency is included in a CIP project
Green Forrest Drive 3 Site Car Accessible Parking Spaces Restiriping C Deficiency is included in a CIP project
Green Forrest Drive 3 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements C Deficiency is included in a CIP project
Green Forrest Drive 3 Site Exterior Signage At Accessible Parking Area Does Not Meet ADA Requirements C Deficiency is included in a CIP project
No ADA-Compliant Stalls. Add 1 And Grab
Hallford, James R. Stadium 3 Building 8010 Interior Existing Toilet Stall Does Not Meet Minimum ADA Requirements
Bars In Each Restroom. (Men And Women) 4 C Deficiency is included in a CIP project
On West Side Concessions, 2 On East Side.
No ADA-Compliant Stalls. Add 1 And Grab
Hallford, James R. Stadium 3 Building 8010 Plumbing Restroom Grab Bars Are Not ADA Compliant Bars In Each Restroom. (Men And Women) 4 C Deficiency is included in a CIP project
On West Side Concessions, 2 On East Side.
Parking Spots North (East And West) Of Field
Hallford, James R. Stadium 3 Site Car Accessible Parking Spaces Restiriping C Deficiency is included in a CIP project
Faded - Repaint Floor Signs And Restripe All.
Parking Spots North (East And West) Of Field
Hallford, James R. Stadium 3 Site Van Accessible Parking Spaces Are Not Properly Striped C Deficiency is included in a CIP project
Faded - Repaint Floor Signs And Restripe All.
Parking ADA Signage On West Side Faded.
Hallford, James R. Stadium 3 Site Exterior Signage At Accessible Parking Area Does Not Meet ADA Requirements C Deficiency is included in a CIP project
Replace.
Hambrick Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant All Interior Door Hardware Not Compliant C Deficiency is included in a CIP project
Hambrick Elementary School 3 Building 2011 Interior Existing Door Hardware Is Not ADA Compliant All Interior Door Hardware Not Compliant C Deficiency is included in a CIP project
Hambrick Elementary School 3 Building 2010 Conveyances Platform Lift Needed for Access No Ramp At Stage C Deficiency is included in a CIP project
Slope Not Compliant, Concrete Slabs Not
Hambrick Elementary School 3 Building 2010 Site Curb Ramp Does Not Meet Minimum ADA Compliance Requirements C Deficiency is included in a CIP project
Level
See N35 And N36 For Door Locations. Old
Hatton Dr Warehouse 3 Building 8010 Interior Interior Door Hardware Replacement C Deficiency is included in a CIP project
And Deficient.
Hatton Dr Warehouse 3 Building 8010 Exterior Metal Panel Exterior Repair Old, Damaged, Replace C Deficiency is included in a CIP project
Was Not Able To Access Roof (No Building
Hatch Or Ladder Provided). Nonetheless
Evidence Of Significant Leaks From Interior,
Hatton Dr Warehouse 2 Building 8010 Roofing Modified Roof Covering Replacement Both At Internal Points In Steel Doors C Deficiency is included in a CIP project
(Insulation Warn And Exposed) And At
Perimeter Walls, Evidenced By Mold And
Stains.
Gutter And Downspout System Collapsed In
Hatton Dr Warehouse 3 Building 8010 Roofing Gutter Replacement Segments And Deficient. Replace C Deficiency is included in a CIP project
Throughout.
51 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Gutter And Downspout System Collapsed In
Hatton Dr Warehouse 3 Building 8010 Roofing Metal Downspout Replacement Segments And Deficient. Replace C Deficiency is included in a CIP project
Throughout.
Hatton Dr Warehouse 2 Building 8010 Mechanical Gas Furnace HVAC Component Replacement Beyond Useful Life - No Plans C Deficiency is included in a CIP project
Hatton Dr Warehouse 2 Building 8010 Mechanical Electric Unit Heater Replacement Beyond Useful Life - No Plans C Deficiency is included in a CIP project
Hatton Dr Warehouse 2 Building 8010 Mechanical Fin Tube Water Radiant Heater Replacement Beyond Useful Life - No Plans C Deficiency is included in a CIP project
Hatton Dr Warehouse 2 Building 8010 Mechanical Gas Unit Heater Replacement Beyond Useful Life - No Plans C Deficiency is included in a CIP project
Hatton Dr Warehouse 2 Building 8010 Mechanical Gas Unit Heater Replacement Beyond Useful Life - No Plans C Deficiency is included in a CIP project
Beyond Useful Life. Building Exterior -
Hatton Dr Warehouse 2 Building 8010 Mechanical Air Cooled Condenser Replacement C Deficiency is included in a CIP project
Replace 6
Hatton Dr Warehouse 2 Building 8010 Mechanical Air Cooled Condenser Replacement Beyond Useful Life. Building Ext C Deficiency is included in a CIP project
Hatton Dr Warehouse 2 Building 8010 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life - No Plans C Deficiency is included in a CIP project
Hatton Dr Warehouse 2 Building 8010 Mechanical Heat Pump HVAC Component Replacement 7.5 Tons. Beyond Useful Life - No Plans C Deficiency is included in a CIP project
Hatton Dr Warehouse 2 Building 8010 Mechanical Ductwork Replacement (SF Basis) Beyond Useful Life. Office Area C Deficiency is included in a CIP project
Hatton Dr Warehouse 2 Building 8010 Mechanical Package Roof Top Unit Replacement Estimate. No Access. C Deficiency is included in a CIP project
Hatton Dr Warehouse 3 Building 8010 Mechanical Large Diameter Exhausts/Hoods Replacement No Access, Estimate C Deficiency is included in a CIP project
Hatton Dr Warehouse 3 Building 8010 Mechanical Small Diameter Exhausts/Hoods Replacement No Access, Estimate C Deficiency is included in a CIP project
Hatton Dr Warehouse 3 Building 8010 Electrical Electrical Receptacle Replacement Multiple Locations C Deficiency is included in a CIP project
Add Power Assist Hardware North And Main
Hatton Dr Warehouse 3 Building 8010 Exterior Exterior Entry Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Entry Door
Stall Old - Floor Deficiencies. Add (1) ADA
Hatton Dr Warehouse 3 Building 8010 Interior Existing Toilet Stall Does Not Meet Minimum ADA Requirements C Deficiency is included in a CIP project
Stall Per Restroom (4 Total)
Hatton Dr Warehouse 3 Building 8010 Plumbing Restroom Grab Bars Are Not ADA Compliant Stalls Old C Deficiency is included in a CIP project
Single Use Restroom By Kitchen Old, Non-
Hatton Dr Warehouse 3 Building 8010 Plumbing Restroom Is Not ADA Compliant C Deficiency is included in a CIP project
Compliant. Remodel.
Hatton Dr Warehouse 3 Building 8010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA
AddRequirements
Signage C Deficiency is included in a CIP project
Hatton Dr Warehouse 3 Site Car Accessible Parking Spaces Do Not Meet ADA Requirements Not Enough Spaces Observed. C Deficiency is included in a CIP project
Striping Not Visible Due To Foliage And
Hatton Dr Warehouse 3 Site Car Accessible Parking Spaces Restiriping C Deficiency is included in a CIP project
Debris. Likely Faded.
Striping Not Visible Due To Foliage And
Hatton Dr Warehouse 3 Site Van Accessible Parking Spaces Are Not Properly Striped C Deficiency is included in a CIP project
Debris. Likely Faded.
Only 1 Sign Standing, 2 Ripped Out And Put
Hatton Dr Warehouse 3 Site Exterior Signage At Accessible Parking Area Does Not Meet ADA Requirements C Deficiency is included in a CIP project
To The Side.
Hawthorne Elementary School 2 Building 2010 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility
Cracked And Uneven C Deficiency is included in a CIP project
Hawthorne Elementary School 3 Site Site Requires Civil/Drainage Study Flooding C Deficiency is included in a CIP project
Hawthorne Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Hawthorne Elementary School 3 Building 2010 Site Van Accessible Parking Spaces Are Not Properly Striped Worn Striping C Deficiency is included in a CIP project
Henderson Middle School 3 Building 4010 Plumbing Existing Lavatory/Sink Pipe Insulation Replacement Add Drain Pipe Insulation - 12 Lavatories C Deficiency is included in a CIP project
Henderson Middle School 3 Building 4011 Plumbing Existing Lavatory/Sink Pipe Insulation Replacement Add Pipe Insulation - 8 Lavatories C Deficiency is included in a CIP project
Hightower Elementary School 3 Building 2010 Exterior Brick Exterior Repointing Cracked And Kitchen Dock C Deficiency is included in a CIP project
We Were Told That The School Was Getting A
New Roof Soon. Roof Needs To Be Replaced.
Hightower Elementary School 2 Building 2010 Roofing Built-up Roofing Replacement C Deficiency is included in a CIP project
Old, Ponding, Does Not Drain. Drains
Clogged.
Gutter At Front Of School Was Hit By A Truck.
Hightower Elementary School 3 Building 2010 Roofing Gutter Replacement C Deficiency is included in a CIP project
Replace 20' Of Gutter.
Hightower Elementary School 3 Building 2010 Roofing Roof Drain Cleaning Leaves And Various Locations C Deficiency is included in a CIP project
Hightower Elementary School 3 Building 2010 Plumbing Toilet Replacement Beyond Useful Life C Deficiency is included in a CIP project
Hightower Elementary School 3 Building 2010 Plumbing Urinal Replacement Beyond Useful Life C Deficiency is included in a CIP project
Hightower Elementary School 3 Building 2011 Roofing Roof Drain Cleaning Leaves And Various Locations C Deficiency is included in a CIP project
We Were Told The School Is Getting A New
Hightower Elementary School 2 Building 2012 Roofing Built-up Roofing Replacement C Deficiency is included in a CIP project
Roof Soon. Roof Needs To Be Replaced.
Hightower Elementary School 3 Building 2012 Roofing Roof Drain Cleaning Leaves And Various Locations C Deficiency is included in a CIP project
We Were Told The School Is Getting A New
Hightower Elementary School 2 Building 2013 Roofing Built-up Roofing Replacement C Deficiency is included in a CIP project
Roof Soon. Needs A New Roof.
Hightower Elementary School 3 Building 2013 Roofing Roof Drain Cleaning Leaves And Various Locations C Deficiency is included in a CIP project
Hightower Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Leaves And Front And Back C Deficiency is included in a CIP project
Hightower Elementary School 3 Site Concrete Walks Replacement Broken And Various Locations C Deficiency is included in a CIP project
Huntley Hills Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
52 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Idlewood Elementary School 3 Building 2011 Exterior Exterior Metal Door Repainting C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2020 Exterior Exterior Metal Door Repainting C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Exterior Exterior Metal Door Repainting Paint Doors C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2012 Exterior Exterior Metal Door Repainting Worn C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Exterior Composite Exterior Siding Replacement (Bldg SF) Worn C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Roofing Modified Roof Covering Replacement Peeling C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Roofing Roof Drain Cleaning Clogged C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Interior Interior Brick/Stone Replacement (Bldg SF) Replace Broken CMU In Boys Bathroom C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Plumbing Water Storage Tank Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Mechanical Gas Piping Replacement (SF Basis) Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Useful Life
Beyond C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Plumbing Toilet Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Plumbing Toilet Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Plumbing Urinal Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Plumbing Sanitary Sewer Piping Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Mechanical Boiler Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Mechanical Boiler Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Mechanical Circulation Pump Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Mechanical Circulation Pump Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Mechanical Unit Ventilator Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Mechanical Unit Ventilator Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Mechanical Ductless Split System AC Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Mechanical Make Up Air Equipment Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Mechanical Kitchen Exhaust Hood Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Mechanical Ductwork Replacement (SF Basis) Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Mechanical Large Diameter Exhausts/Hoods Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Mechanical Small Diameter Exhausts/Hoods Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Electrical Switchgear Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Electrical Transfer Switch Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Electrical Distribution Panel Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2011 Roofing Roof Drain Cleaning Leaves C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2011 Mechanical Gas Piping Replacement (SF Basis) Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2011 Plumbing Water Heater Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2011 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Useful Life
Beyond C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2011 Plumbing Toilet Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2011 Plumbing Urinal Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2011 Plumbing Sanitary Sewer Piping Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2011 Mechanical Fin Tube Water Radiant Heater Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2011 Mechanical Unit Ventilator Replacement Beyond Useful Life C Deficiency is included in a CIP project
53 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Idlewood Elementary School 3 Building 2011 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2011 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2011 Mechanical Ductwork Replacement (SF Basis) Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2011 Mechanical HVAC VAV Box Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2011 Mechanical Large Diameter Exhausts/Hoods Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2011 Electrical Interior Power Wiring Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2011 Electrical Electrical Transformer Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2011 Electrical Electrical Transformer Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2011 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2011 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2012 Roofing Modified Roof Covering Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2012 Roofing Debris In Gutter Removal Clogged C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2012 Plumbing Water Heater Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2012 Plumbing Toilet Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2012 Plumbing Urinal Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2012 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2012 Mechanical HVAC VAV Box Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2012 Mechanical Package Roof Top Unit Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Leaves In Gutter C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2020 Plumbing Gas Water Heater Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2020 Plumbing Toilet Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2020 Plumbing Urinal Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 2 Building 2020 Mechanical Electric Unit Heater Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2020 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Idlewood Elementary School 3 Site Asphalt Driveway Replacement C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Interior Existing Toilet Stall Does Not Meet Minimum ADA Requirements C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Plumbing Existing Lavatory/Sink Pipe Insulation Replacement Add Insulation To The Sinks - 16 Each C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Plumbing Restroom Grab Bars Are Not ADA Compliant C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Electrical Public Address System Head-End Requires Replacement C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2011 Interior Existing Toilet Stall Does Not Meet Minimum ADA Requirements C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2011 Plumbing Existing Lavatory/Sink Pipe Insulation Replacement Add Pipe Insulation C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2011 Plumbing Restroom Grab Bars Are Not ADA Compliant C Deficiency is included in a CIP project
Idlewood Elementary School 3 Site Curb Ramp Does Not Meet Minimum ADA Compliance Requirements Poor Ramp At Street C Deficiency is included in a CIP project
Idlewood Elementary School 3 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
No Ramp C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement Worn C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2011 Interior Interior Door Hardware Replacement Worn C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Interior Interior Door Replacement Worn C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2011 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life C Deficiency is included in a CIP project
Idlewood Elementary School 3 Building 2012 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life C Deficiency is included in a CIP project
International Student Center at Midway 3 Building 2010 Exterior Exterior Metal Door Repainting C Deficiency is included in a CIP project
International Student Center at Midway 3 Building 2010 Exterior Brick Exterior Repointing Deteriorated C Deficiency is included in a CIP project
International Student Center at Midway 2 Building 2010 Mechanical Boiler Replacement Beyond Useful Life - 2000 Mbh C Deficiency is included in a CIP project
International Student Center at Midway 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
International Student Center at Midway 3 Building 2011 Mechanical Testing And Balancing C Deficiency is included in a CIP project
International Student Center at Midway 3 Building 2012 Mechanical Testing And Balancing C Deficiency is included in a CIP project
International Student Center at Midway 3 Building 2020 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Caulk Grout Pockets At Bottom Of Handrail
International Student Center at Midway 3 Exterior Caulking Replacement Posts To Prevent Holding Water And Prevent C Deficiency is included in a CIP project
Rust.
International Student Center at Midway 3 Site Concrete Driveways Replacement Slab Under Dumpster Is Broken And Cracked. C Deficiency is included in a CIP project
International Student Center at Midway 3 Site Concrete Walks Replacement Cracked C Deficiency is included in a CIP project
International Student Center at Midway 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant Not ADA C Deficiency is included in a CIP project
International Student Center at Midway 3 Building 2011 Interior Existing Door Hardware Is Not ADA Compliant Not ADA C Deficiency is included in a CIP project
International Student Center at Midway 3 Building 2010 Plumbing Existing Lavatory/Sink Is Not ADA Compliant Add Pipe Insulation C Deficiency is included in a CIP project
International Student Center at Midway 3 Building 2010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
No Ramp C Deficiency is included in a CIP project
International Student Center at Midway 3 Building 2011 Interior Existing Toilet Stall Does Not Meet Minimum ADA Requirements
Too Small C Deficiency is included in a CIP project
International Student Center at Midway 3 Building 2011 Plumbing Existing Lavatory/Sink Is Not ADA Compliant No Pipe Insulation C Deficiency is included in a CIP project
54 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
International Student Center at Midway 3 Building 2011 Plumbing Restroom Grab Bars Are Not ADA Compliant No Grab Bars C Deficiency is included in a CIP project
International Student Center at Midway 3 Building 2011 Plumbing Restroom Is Not ADA Compliant Doors Too Small C Deficiency is included in a CIP project
International Student Center at Midway 3 Building 2011 Electrical Lightning Protection System Installation Missing C Deficiency is included in a CIP project
International Student Center at Midway 3 Building 2012 Electrical Lightning Protection System Installation Missing C Deficiency is included in a CIP project
International Student Center at Midway 3 Building 2010 Electrical Lightning Protection Terminal Replacement Missing C Deficiency is included in a CIP project
International Student Center at Midway 3 Building 2020 Electrical Lightning Protection Terminal Replacement Missing C Deficiency is included in a CIP project
International Student Center at Midway 3 Building 2010 Electrical Public Address System Head-End Requires Replacement Beyond Useful Life C Deficiency is included in a CIP project
International Student Center at Midway 3 Building 2010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life C Deficiency is included in a CIP project
International Student Center at Midway 3 Building 2012 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life C Deficiency is included in a CIP project
International Student Center at Midway 2 Building 2010 Exterior Steel Window Replacement Aged C Deficiency is included in a CIP project
International Student Center at Midway 2 Building 2011 Exterior Steel Window Replacement Aged C Deficiency is included in a CIP project
John Lewis Elementary School 3 Building 2010 Plumbing Existing Lavatory/Sink Is Not ADA Compliant Room 1205 No Cover Under Sink C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2010 Exterior Brick Exterior Repointing Eroding Mortar C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Roofing Metal Roof Structural Roof Covering Replacement C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Roofing Built-up Roofing Replacement C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2010 Roofing Awning Or Canopy Concrete Roofing System Replacement C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2010 Roofing Roof Drain Cleaning Clogged C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Mechanical Gas Piping Replacement (SF Basis) Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Plumbing Water Heater Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Useful Life
Beyond C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2010 Plumbing Toilet Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2010 Plumbing Urinal Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Mechanical Infrared Electric Radiant Heater Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Mechanical Radiant Heater (Ceiling Panel) Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Mechanical Ductless Split System AC Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2010 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Mechanical Thru Wall AC Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Mechanical Ductwork Replacement (SF Basis) Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Mechanical Package Roof Top Unit Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Mechanical Package Roof Top Unit Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Mechanical Package Roof Top Unit Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2010 Mechanical Large Diameter Exhausts/Hoods Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2010 Mechanical Small Diameter Exhausts/Hoods Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Electrical Motor Control Center Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2011 Exterior Brick Exterior Repointing Eroding Mortar C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2011 Roofing Built-up Roofing Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2011 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2011 Roofing Awning Or Canopy Concrete Roofing System Replacement C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2011 Mechanical Gas Piping Replacement (SF Basis) Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2011 Plumbing Water Heater Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2011 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Useful Life
Beyond C Deficiency is included in a CIP project
55 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Jolly Elementary School 3 Building 2011 Plumbing Toilet Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2011 Plumbing Urinal Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2011 Mechanical Infrared Electric Radiant Heater Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2011 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2011 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2011 Mechanical Ductwork Replacement (SF Basis) Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2011 Mechanical Package Roof Top Unit Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2011 Mechanical Small Diameter Exhausts/Hoods Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2011 Electrical Electrical Transformer Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2011 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2011 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2011 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2011 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2011 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2012 Roofing Modified Roof Covering Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2012 Roofing Roof Drain Cleaning Clogged C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2012 Plumbing Water Heater Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2012 Plumbing Toilet Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2012 Plumbing Urinal Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2012 Mechanical Package DX Unit Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2012 Mechanical Package DX Unit Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2012 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2012 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Debris C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2020 Roofing Metal Downspout Installation Bent C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2020 Plumbing Water Heater Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2020 Plumbing Toilet Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2020 Plumbing Urinal Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2020 Mechanical Electric Unit Heater Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 2 Building 2020 Mechanical Gas Unit Heater Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2020 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Site Asphalt Driveway Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Site Parking Or Roadway Curbs Replacement C Deficiency is included in a CIP project
Jolly Elementary School 3 Site Concrete Walks Replacement Broken C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2010 Interior Access Is Not ADA Compliant Non Compliant Door Knobs C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2010 Conveyances Platform Lift Needed for Access None Available C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2010 Electrical Public Address System Head-End Requires Replacement Beyond Useful Life C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsNo (Modify Full)
Low Counter C Deficiency is included in a CIP project
Jolly Elementary School 3 Building 2020 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
Missing C Deficiency is included in a CIP project
Kelley Lake Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant Not Lever Handles C Deficiency is included in a CIP project
Kelley Lake Elementary School 3 Building 2020 Plumbing Restroom Grab Bars Are Not ADA Compliant Add Vertical Grab Bars C Deficiency is included in a CIP project
Kingsley Elementary School 3 Building 2011 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding C Deficiency is included in a CIP project
Kingsley Elementary School 3 Building 2011 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Kingsley Elementary School 3 Building 2020 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Kingsley Elementary School 3 Site Asphalt Driveway Replacement Potholes C Deficiency is included in a CIP project
Kingsley Elementary School 3 Site Concrete Walks Replacement Cracked C Deficiency is included in a CIP project
Kingsley Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Kingsley Elementary School 3 Building 2010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
No Ramp C Deficiency is included in a CIP project
Kingsley Elementary School 3 Building 2011 Plumbing Existing Lavatory/Sink Is Not ADA Compliant Add Pipe Insulation C Deficiency is included in a CIP project
Kingsley Elementary School 3 Building 2011 Plumbing Restroom Grab Bars Are Not ADA Compliant No Grab Bars C Deficiency is included in a CIP project
Kittredge Magnet 3 Building 2010 Exterior Brick Exterior Repointing Weathered C Deficiency is included in a CIP project
Kittredge Magnet 2 Building 2010 Roofing Built-up Roofing Replacement Beyond Useful Life C Deficiency is included in a CIP project
Kittredge Magnet 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding C Deficiency is included in a CIP project
Kittredge Magnet 3 Building 2010 Roofing Metal Downspout Replacement Leaks At Joints C Deficiency is included in a CIP project
Kittredge Magnet 3 Building 2010 Roofing Roof Operable Hatch Replacement Missing C Deficiency is included in a CIP project
Kittredge Magnet 3 Building 2010 Plumbing Gas Water Heater Replacement 65 Gal - Mech Room 204.1 C Deficiency is included in a CIP project
Kittredge Magnet 2 Building 2010 Mechanical Boiler Replacement Mech Room 204.1 C Deficiency is included in a CIP project
Wshp - Water Source Heat Pump - Entire
Kittredge Magnet 2 Building 2010 Mechanical Package DX Unit Replacement C Deficiency is included in a CIP project
Building
4 Tons - Wshp - Water Source Heat Pumps -
Kittredge Magnet 2 Building 2010 Mechanical Package DX Unit Replacement C Deficiency is included in a CIP project
Entire Building
56 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Kittredge Magnet 3 Building 2010 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Kittredge Magnet 2 Building 2010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Entire Building C Deficiency is included in a CIP project
Kittredge Magnet 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life C Deficiency is included in a CIP project
Kittredge Magnet 2 Building 2010 Electrical Distribution Panel Replacement Beyond Useful Life C Deficiency is included in a CIP project
Kittredge Magnet 2 Building 2010 Electrical Panelboard Replacement Outside 99.4 C Deficiency is included in a CIP project
Kittredge Magnet 2 Building 2010 Electrical Panelboard Replacement Outside Mech Room 204.1 C Deficiency is included in a CIP project
Kittredge Magnet 2 Building 2011 Roofing Built-up Roofing Replacement Beyond Useful Life C Deficiency is included in a CIP project
Kittredge Magnet 3 Building 2011 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding C Deficiency is included in a CIP project
Kittredge Magnet 3 Building 2011 Roofing Gutter Replacement Damaged C Deficiency is included in a CIP project
Kittredge Magnet 3 Building 2011 Roofing Metal Downspout Replacement Leaks At Joints C Deficiency is included in a CIP project
Wshp - Water Source Heat Pumps - Entire
Kittredge Magnet 2 Building 2011 Mechanical Package DX Unit Replacement C Deficiency is included in a CIP project
Building
Kittredge Magnet 3 Building 2011 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Kittredge Magnet 2 Building 2011 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Entire Building C Deficiency is included in a CIP project
Kittredge Magnet 2 Building 2011 Electrical Electrical Transformer Replacement Beyond Useful Life C Deficiency is included in a CIP project
Kittredge Magnet 2 Building 2011 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Kittredge Magnet 2 Building 2011 Electrical Panelboard Replacement Outside Room 105 C Deficiency is included in a CIP project
Beyond Useful Life - See Building 2010 Code
Kittredge Magnet 2 Building 2012 Roofing Built-up Roofing Replacement C Deficiency is included in a CIP project
R10 Comments.
Kittredge Magnet 3 Building 2012 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding C Deficiency is included in a CIP project
Kittredge Magnet 2 Building 2012 Mechanical Heat Exchanger Replacement 450 Gpm - Mech 215.1 C Deficiency is included in a CIP project
Kittredge Magnet 3 Building 2012 Mechanical Circulation Pump Replacement Mech 215.1 C Deficiency is included in a CIP project
Kittredge Magnet 2 Building 2012 Mechanical Package DX Unit Replacement Wshp - Entire Building C Deficiency is included in a CIP project
Kittredge Magnet 2 Building 2012 Mechanical Package DX Unit Replacement Wshp - Entire Building C Deficiency is included in a CIP project
Kittredge Magnet 3 Building 2012 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Kittredge Magnet 2 Building 2012 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Entire Building C Deficiency is included in a CIP project
Kittredge Magnet 2 Building 2012 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Kittredge Magnet 2 Building 2020 Roofing Gutter Joint Repair Water Leaking C Deficiency is included in a CIP project
Kittredge Magnet 3 Building 2020 Roofing Gutter Replacement Damaged C Deficiency is included in a CIP project
Kittredge Magnet 3 Building 2010 Interior Access Is Not ADA Compliant Knobs Non-ADA C Deficiency is included in a CIP project
Kittredge Magnet 3 Building 2010 Interior Entry Door Does Not Have Power Assist Device Missing At Main Entrance C Deficiency is included in a CIP project
Kittredge Magnet 3 Building 2010 Conveyances Platform Lift Needed for Access Missing C Deficiency is included in a CIP project
Kittredge Magnet 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsLow (Modify Full)Missing
Counter C Deficiency is included in a CIP project
Lakeside High School 3 Building 5010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
Missing C Deficiency is included in a CIP project
Lakeside High School 3 Building 5012 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
Missing C Deficiency is included in a CIP project
Not Properly Draining, Water Runoff Floods
Laurel Ridge Elementary School 3 Site Site Requires Civil/Drainage Study C Deficiency is included in a CIP project
Covered Walkway
Laurel Ridge Elementary School 3 Site Concrete Walks Replacement Cracked Concrete C Deficiency is included in a CIP project
Laurel Ridge Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant All Interior Door Hardware Not Compliant C Deficiency is included in a CIP project
Laurel Ridge Elementary School 3 Building 2011 Interior Existing Door Hardware Is Not ADA Compliant All Interior Door Hardware Not Compliant C Deficiency is included in a CIP project
No ADA Compliant Stalls And Grab Bars In All
Laurel Ridge Elementary School 3 Building 2010 Interior Existing Toilet Stall Does Not Meet Minimum ADA Requirements C Deficiency is included in a CIP project
Of Building
Grab Bars Needed In Mens And Womens
Laurel Ridge Elementary School 3 Building 2010 Plumbing Restroom Grab Bars Are Not ADA Compliant Restrooms (Rooms 17.2 And 17.3, Or 20.1 C Deficiency is included in a CIP project
And 20.2)
No Restrooms Are Compliant, Remodel (2) 75
Laurel Ridge Elementary School 3 Building 2010 Plumbing Restroom Is Not ADA Compliant C Deficiency is included in a CIP project
Sf Single Use Restrooms
Laurel Ridge Elementary School 3 Building 2012 Interior Existing Door Hardware Is Not ADA Compliant All Interior Door Hardware Not Compliant C Deficiency is included in a CIP project
Power Assist Hardware And Exterior Button
Laurel Ridge Elementary School 3 Building 2010 Exterior Exterior Entry Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Needed
Lithonia High School 3 Building 5010 Roofing Built Up Roofing (Bur) Covering Has Blisters That Should Be Repaired C Deficiency is included in a CIP project
57 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Roof Shows Significant Cracking At
Membrane Flashing And Tapers Throughout,
And Interior Throughout Shows Significant
Signs Of Moisture Damage From Roof Leaks
Despite Noted Replacement Of Many Ceilings
Lithonia High School 2 Building 5010 Roofing Built-up Roofing Replacement C Deficiency is included in a CIP project
And Tiles. Ballasted Roof, Hard To Determine
Full Extent But Membrane At Parapets
Throughout Show Damage And Leaking Has
Been Reported As A Consistent And
Widespread Problem
Flashing At Roof Area Separation Points
Lithonia High School 2 Building 5010 Roofing Counter Flashing Replacement Rusting And Cracking. Replace Cap Flashing C Deficiency is included in a CIP project
And Seams.
Lithonia High School 3 Building 5010 Roofing Roof Drain Cleaning C Deficiency is included in a CIP project
Lithonia High School 3 Building 5010 Roofing Roof Operable Hatch Replacement Damaged And Rusting C Deficiency is included in a CIP project
Lithonia High School 3 Building 5010 Interior Existing Toilet Stall Does Not Meet Minimum ADA Requirements
Toilet Paper Roll Height C Deficiency is included in a CIP project
Lithonia High School 3 Building 5010 Plumbing Existing Lavatory/Sink Is Not ADA Compliant Missing Pipe Insulation C Deficiency is included in a CIP project
Lithonia High School 3 Building 5010 Site Curb Ramp Does Not Meet Minimum ADA Compliance Requirements
No Tactile Warning And Slope Too Steep C Deficiency is included in a CIP project
Lithonia High School 3 Building 5010 Site Car Accessible Parking Spaces Restiriping Worn C Deficiency is included in a CIP project
Lithonia High School 3 Building 5010 Site Van Accessible Parking Spaces Are Not Properly Striped Worn C Deficiency is included in a CIP project
Lithonia High School 3 Building 5010 Site Exterior Signage At Accessible Parking Area Does Not Meet ADA Requirements
Missing And Damaged C Deficiency is included in a CIP project
Lithonia Middle School 2 Building 4010 Conveyances Elevator Cab Replacement C Deficiency is included in a CIP project
Lithonia Middle School 3 Building 4010 Exterior Exterior Entry Door Threshold Exceeds The Maximum Threshold RoomHeight
625 C Deficiency is included in a CIP project
Livsey Elementary School 2 Building 2010 Mechanical Electric Unit Heater Replacement Beyond Useful Life C Deficiency is included in a CIP project
Livsey Elementary School 2 Building 2010 Mechanical Electric Unit Heater Replacement Beyond Useful Life C Deficiency is included in a CIP project
Livsey Elementary School 3 Building 2010 Mechanical Testing And Balancing Beyond Useful Life C Deficiency is included in a CIP project
Replace Asphalt At Kitchen Loading Dock.
Livsey Elementary School 3 Site Asphalt Driveway Replacement C Deficiency is included in a CIP project
Damaged, Cracked, Potholes.
Livsey Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant Not ADA C Deficiency is included in a CIP project
Livsey Elementary School 3 Building 2010 Conveyances Platform Lift Needed for Access No Ramp To Stage C Deficiency is included in a CIP project
Marbut Elementary School 2 Building 2010 Mechanical Boiler Replacement Beyond Useful Life C Deficiency is included in a CIP project
Marbut Elementary School 3 Building 2010 Mechanical Circulation Pump Replacement Beyond Useful Life C Deficiency is included in a CIP project
Marbut Elementary School 3 Building 2010 Mechanical Circulation Pump Replacement Beyond Useful Life C Deficiency is included in a CIP project
Marbut Elementary School 2 Building 2010 Mechanical Ductless Split System AC Replacement Beyond Useful Life C Deficiency is included in a CIP project
Marbut Elementary School 2 Building 2010 Mechanical Package DX Unit Replacement Beyond Useful Life C Deficiency is included in a CIP project
Marbut Elementary School 2 Building 2010 Mechanical Package DX Unit Replacement Beyond Useful Life C Deficiency is included in a CIP project
Marbut Elementary School 2 Building 2010 Mechanical Package DX Unit Replacement Beyond Useful Life C Deficiency is included in a CIP project
Marbut Elementary School 3 Building 2010 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Marbut Elementary School 3 Building 2010 Mechanical Energy Recovery Unit Replacement Beyond Useful Life C Deficiency is included in a CIP project
Marbut Elementary School 3 Building 2010 Mechanical Energy Recovery Unit Replacement Beyond Useful Life C Deficiency is included in a CIP project
Marbut Elementary School 3 Building 2010 Mechanical Energy Recovery Unit Replacement Beyond Useful Life C Deficiency is included in a CIP project
Marbut Elementary School 2 Building 2010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Beyond Useful Life C Deficiency is included in a CIP project
Marbut Elementary School 2 Building 2010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Beyond Useful Life C Deficiency is included in a CIP project
Marbut Elementary School 2 Building 2010 Mechanical Ductwork Replacement (SF Basis) C Deficiency is included in a CIP project
Marbut Elementary School 2 Building 2010 Mechanical HVAC VAV Box Replacement Beyond Useful Life C Deficiency is included in a CIP project
Marbut Elementary School 3 Building 2020 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Marbut Elementary School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsRoom (Modify
61 -Full)
Reception - No ADA Count C Deficiency is included in a CIP project
Marbut Elementary School 3 Building 2010 Site Curb Ramp Does Not Meet Minimum ADA Compliance Requirements Cracked C Deficiency is included in a CIP project
Marbut Elementary School 3 Building 2010 Site Car Accessible Parking Spaces Restiriping Faded C Deficiency is included in a CIP project
Marbut Elementary School 3 Building 2010 Site Van Accessible Parking Spaces Are Not Properly Striped Faded C Deficiency is included in a CIP project
Margaret Harris Comprehensive 3 Building 8010 Roofing Built Up Roofing (Bur) Covering Has Blisters That Should Be Repaired
Blisters And Above Room 18.2 C Deficiency is included in a CIP project
Margaret Harris Comprehensive 3 Building 8010 Roofing Roof Drain Cleaning Leaves And Various Locations C Deficiency is included in a CIP project
Margaret Harris Comprehensive 3 Building 8011 Roofing Roof Drain Cleaning Leaves And Various Locations C Deficiency is included in a CIP project
Margaret Harris Comprehensive 3 Building 8012 Roofing Roof Drain Cleaning Leaves And Various Locations C Deficiency is included in a CIP project
Margaret Harris Comprehensive 3 Building 8010 Interior Existing Door Hardware Is Not ADA Compliant Not ADA C Deficiency is included in a CIP project
Margaret Harris Comprehensive 3 Building 8010 Site Access Is Not ADA Compliant - ADA Compliant Ramp InstallationRamp Too Steep C Deficiency is included in a CIP project
Margaret Harris Comprehensive 3 Building 8011 Interior Existing Door Hardware Is Not ADA Compliant Not ADA C Deficiency is included in a CIP project
Margaret Harris Comprehensive 3 Building 8012 Interior Existing Door Hardware Is Not ADA Compliant Not ADA C Deficiency is included in a CIP project
58 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Replace All Door Awning Structures (Arched,
Martin Luther King, Jr. High School 2 Building 5010 Roofing Metal Roof Architectural Roof Covering Replacement Standing Seam). Rusted On Underside, C Deficiency is included in a CIP project
Deficient.
Significant Blistering. Repair It, Not Replacing
Martin Luther King, Jr. High School 3 Building 5010 Roofing Modified Covering Has Blisters That Should Be Repaired C Deficiency is included in a CIP project
Roof
Original Roof, Advise To Replace In Entirety -
Martin Luther King, Jr. High School 2 Building 5010 Roofing Modified Roof Covering Replacement C Deficiency is included in a CIP project
Leaking Issues.
Clean Gutters Along Gymnasium (316) And
Martin Luther King, Jr. High School 3 Building 5010 Roofing Debris In Gutter Removal C Deficiency is included in a CIP project
Auditorium (216) Standing Seam System.
Fascia Along South Wall Of 316 Gymnasium Is
Martin Luther King, Jr. High School 3 Building 5010 Roofing Gutter Replacement C Deficiency is included in a CIP project
Coming Off. Repair And Re-Fasten Caping.
Membrane + Lashing Requires Replacement
Martin Luther King, Jr. High School 3 Building 5010 Roofing Membrane Flashing At Parapet (>2') Repair C Deficiency is included in a CIP project
Along Entire East Wall
Not Working, East Roof Section, They Have A
Martin Luther King, Jr. High School 2 Building 5010 Mechanical Ductless Split System AC Replacement New Unit On The Roof But It Is Not C Deficiency is included in a CIP project
Connected
2 Damaged Above Kitchen And 4 Damaged
Martin Luther King, Jr. High School 3 Building 5010 Mechanical Small Diameter Exhausts/Hoods Replacement C Deficiency is included in a CIP project
On East Roof Section
Martin Luther King, Jr. High School 3 Building 5011 Roofing Modified Covering Has Blisters That Should Be Repaired Several Blisters, Repair C Deficiency is included in a CIP project
Martin Luther King, Jr. High School 2 Building 5011 Roofing Modified Membrane Has Holes That Should Be Repaired Leaks C Deficiency is included in a CIP project
Elevator Is Not Working Due To Electrical
And Security System Issues (Not Mech
Martin Luther King, Jr. High School 3 Building 5011 Conveyances Elevator is Not ADA Compliant C Deficiency is included in a CIP project
Issues) Check And Repair The Front Card
Access Panel.
Martin Luther King, Jr. High School 3 Building 5010 Electrical 2 X 4 Interior Fluorescent Lighting Replacement C Deficiency is included in a CIP project
Martin Luther King, Jr. High School 3 Building 5010 Electrical 2 X 4 Interior Fluorescent Lighting Replacement Old C Deficiency is included in a CIP project
Martin Luther King, Jr. High School 3 Building 5010 Electrical 2 X 4 Interior Fluorescent Lighting Replacement C Deficiency is included in a CIP project
Mary McLeod Bethune Middle School 3 Building 4010 Interior Entry Door Does Not Have Power Assist Device Currently No Power Assist C Deficiency is included in a CIP project
Mary McLeod Bethune Middle School 3 Building 4010 Plumbing Existing Lavatory/Sink Is Not ADA Compliant Wrong Faucet C Deficiency is included in a CIP project
Mary McLeod Bethune Middle School 3 Building 4010 Plumbing Restroom Grab Bars Are Not ADA Compliant C Deficiency is included in a CIP project
Aged And Deteriorated. Ponding, Exposed Tar
McLendon Elementary School 2 Building 2010 Roofing Built-up Roofing Replacement C Deficiency is included in a CIP project
Present.
McLendon Elementary School 3 Building 2010 Roofing Modified Covering Has Blisters That Should Be Repaired Front Awning C Deficiency is included in a CIP project
McLendon Elementary School 3 Building 2010 Roofing Gutter Replacement Gutter Is Crushed And Damaged. Replace C Deficiency is included in a CIP project
McLendon Elementary School 2 Building 2011 Roofing Built-up Roofing Replacement Deteriorated, Exposed Tar, Ponding C Deficiency is included in a CIP project
McLendon Elementary School 2 Building 2012 Roofing Built-up Roofing Replacement Deteriorated, Ponding, Exposed Tar C Deficiency is included in a CIP project
McLendon Elementary School 2 Building 2013 Roofing Built-up Roofing Replacement Deteriorated, Ponding, Exposed Tar C Deficiency is included in a CIP project
McLendon Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
McNair High School 2 Building 5010 Roofing Built-up Roofing Replacement Beyond Useful Life C Deficiency is included in a CIP project
McNair High School 2 Building 5011 Roofing Built-up Roofing Replacement Beyond Useful Life C Deficiency is included in a CIP project
McNair High School 2 Building 5012 Roofing Built-up Roofing Replacement Beyond Useful Life Ponding C Deficiency is included in a CIP project
McNair High School 3 Building 5013 Roofing Membrane Flashing At Parapet (>2') Repair Seal Flashing At Eifs And Brick Connection. C Deficiency is included in a CIP project
Beyond Useful Life - Leaking Roof Causing
McNair High School 2 Building 5020 Roofing Built-up Roofing Replacement C Deficiency is included in a CIP project
Water Damage On Interior Walls
McNair High School 3 Building 5020 Roofing Metal Downspout Replacement Damaged C Deficiency is included in a CIP project
No Elevator In Building. Currently There Is A
Stair Lift Which Does Not Work, Damaged
Midvale Elementary School 3 Conveyances Elevator is Not ADA Compliant C Deficiency is included in a CIP project
And Aged. Replace With New Chair Lift Or
Install Elevator. North West Egress Stairwell.
Stucco On School Is Damaged, Cracking And
Rusting - Needs To Be Repaired. Stucco On
Miller Grove High School 2 Building 5010 Exterior Stucco Exterior Wall Replacement (Bldg SF) C Deficiency is included in a CIP project
Building Is Rusting And Damaged And Needs
To Be Replaced In Many Locations
Miller Grove High School 3 Building 5010 Site Car Accessible Parking Spaces Restiriping Faded C Deficiency is included in a CIP project
59 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Miller Grove High School 3 Building 5011 Site Car Accessible Parking Spaces Restiriping Faded C Deficiency is included in a CIP project
Miller Grove High School 3 Building 5020 Site Car Accessible Parking Spaces Restiriping Faded C Deficiency is included in a CIP project
Miller Grove Middle School 3 Building 4010 Interior Entry Door Does Not Have Power Assist Device Missing At Main Door Exit C Deficiency is included in a CIP project
Miller Grove Middle School 3 Building 4010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsNo (Modify Full)Countertop Available
Low ADA C Deficiency is included in a CIP project
Miller Grove Middle School 3 Building 4010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
Missing C Deficiency is included in a CIP project
Montclair Elementary School 2 Building 2010 Mechanical Cast Iron Water Boiler Replacement C Deficiency is included in a CIP project
Montclair Elementary School 3 Building 2010 Mechanical Circulation Pump Replacement C Deficiency is included in a CIP project
Montclair Elementary School 2 Building 2010 Mechanical Ductless Split System AC Replacement C Deficiency is included in a CIP project
Fan Coil Above Ceiling Could Not Access,
Montclair Elementary School 2 Building 2010 Mechanical Fan Coil Unit Replacement Based On Outdoor Unit Condition The Fan C Deficiency is included in a CIP project
Coil Should Be Replaced
Montclair Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement C Deficiency is included in a CIP project
Montclair Elementary School 3 Building 2010 Mechanical Large Diameter Exhausts/Hoods Replacement C Deficiency is included in a CIP project
Montclair Elementary School 3 Building 2012 Mechanical Circulation Pump Replacement C Deficiency is included in a CIP project
Montclair Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Montclair Elementary School 3 Building 2010 Conveyances Platform Lift Needed for Access No Chairlift Or Ramp C Deficiency is included in a CIP project
Montclair Elementary School 3 Building 2011 Interior Existing Door Hardware Is Not ADA Compliant None Compliant C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2010 Exterior Brick Exterior Repointing Cracked C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2010 Roofing Modified Roof Covering Replacement Beyond Useful Life - Cracked And Blistered C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2010 Roofing Roof Drain Cleaning Debris C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2010 Mechanical Boiler Replacement Mech 307.1 C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2011 Roofing Modified Roof Covering Replacement Beyond Useful Life - Cracked And Blistered C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2011 Mechanical Boiler Replacement Mech Room 318.1 C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2011 Mechanical Circulation Pump Replacement Mech Room 318.1 C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2011 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2012 Exterior Brick Exterior Repointing Cracked C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2012 Roofing Modified Roof Covering Replacement Beyond Useful Life - Cracked And Blistered C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2013 Roofing Modified Roof Covering Replacement Beyond Useful Life - Cracked And Blistered C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2013 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Water Ponding C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2013 Electrical Electrical Transformer Replacement Old, Electrical C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Debris C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2020 Roofing Metal Downspout Replacement Damaged C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Site Asphalt Driveway Replacement Beyond Useful Life - Cracked C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Site Concrete Walks Replacement Cracked C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2011 Conveyances Platform Lift Needed for Access None Available C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2011 Plumbing Restroom Is Not ADA Compliant No ADA Rr In Building C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2012 Specialties Counter Heights Exceed Maximum ADA Height RequirementsNo (Modify Full)
ADA Access C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2012 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
Missing C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2012 Interior Entry Door Does Not Have Power Assist Device None Provided At Entrance Exit C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2011 Exterior Aluminum Storefront Exterior Door Replacement Beyond Useful Life C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2012 Exterior Aluminum Storefront Exterior Door Replacement Beyond Useful Life C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Beyond Useful Life C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2012 Exterior Aluminum Window Replacement Beyond Useful Life C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2011 Electrical Canopy Lighting Replacement Old C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2012 Electrical Canopy Lighting Replacement Old C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2013 Electrical Canopy Lighting Replacement Old C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement Old C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Old, Boiler Room C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Old, Boiler Room C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Old, Boiler Room C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2011 Electrical Electrical Transformer Replacement Old, Idf C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2011 Electrical Electrical Transformer Replacement Old, Electrical C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement Old C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2011 Electrical Exterior Mounted Building Lighting Replacement Old C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2012 Electrical Exterior Mounted Building Lighting Replacement Old C Deficiency is included in a CIP project
60 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Murphey Candler Elementary School 3 Building 2013 Electrical Exterior Mounted Building Lighting Replacement Old C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement Old C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement Old C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2011 Electrical Interior Power Wiring Replacement Old C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2012 Electrical Interior Power Wiring Replacement Old C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement Corridor And Cafeteria Is Led. Rest Is Old. C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2012 Electrical Lighting Fixtures Replacement Corridor = New Led. Rest Are Old. C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2013 Electrical Lighting Fixtures Replacement Old C Deficiency is included in a CIP project
Murphey Candler Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement Corridor Led. Rest Are Old. C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2010 Electrical Panelboard Replacement Old, Corridor And Boiler C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2010 Electrical Panelboard Replacement Old, Corridor C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2010 Electrical Panelboard Replacement Old, Boiler Room C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2011 Electrical Panelboard Replacement Old, Electrical C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2011 Electrical Panelboard Replacement Old, Kitchen And Stage C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2011 Electrical Panelboard Replacement Old, Kitchen C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2011 Electrical Panelboard Replacement Old, Kitchen, Electrical C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2012 Electrical Panelboard Replacement Old, Electrical C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2012 Electrical Panelboard Replacement Old, Electrical C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2011 Exterior Storefront/Curtain Wall Replacement (Bldg SF) Beyond Useful Life C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2012 Exterior Storefront/Curtain Wall Replacement (Bldg SF) Beyond Useful Life - Cracked Seals C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2010 Electrical Switchgear Replacement Old, Boiler Room C Deficiency is included in a CIP project
Murphey Candler Elementary School 2 Building 2011 Electrical Switchgear Replacement Old, Electrical C Deficiency is included in a CIP project
Nancy Creek Facility 3 Building 2010 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Nancy Creek Facility 2 Building 2010 Mechanical Ductwork Replacement (SF Basis) Beyond Useful Life C Deficiency is included in a CIP project
Nancy Creek Facility 2 Building 2010 Mechanical HVAC VAV Box Replacement Beyond Useful Life C Deficiency is included in a CIP project
Nancy Creek Facility 3 Building 2010 Electrical Interior Power Wiring Replacement Beyond Useful Life C Deficiency is included in a CIP project
Nancy Creek Facility 3 Site Asphalt Driveway Replacement Cracked C Deficiency is included in a CIP project
Nancy Creek Facility 3 Site Concrete Walks Replacement Cracked C Deficiency is included in a CIP project
Nancy Creek Facility 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant Not ADA C Deficiency is included in a CIP project
Nancy Creek Facility 3 Building 2010 Plumbing Existing Lavatory/Sink Is Not ADA Compliant Need Pipe Inside C Deficiency is included in a CIP project
Nancy Creek Facility 3 Building 2010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
No Ramp C Deficiency is included in a CIP project
Narvie Harris Elementary School 3 Building 2010 Plumbing Existing Lavatory/Skin Is Missing or Replace Pipe Cover C Deficiency is included in a CIP project
Narvie Harris Elementary School 3 Site Car Accessible Parking Spaces Do Not Meet ADA Requirements C Deficiency is included in a CIP project
Narvie Harris Elementary School 3 Site Van Accessible Parking Spaces Do Not Meet ADA Requirements C Deficiency is included in a CIP project
Narvie Harris Elementary School 3 Site Car Accessible Parking Spaces Restiriping C Deficiency is included in a CIP project
Narvie Harris Elementary School 3 Site Van Accessible Parking Spaces Are Not Properly Striped C Deficiency is included in a CIP project
Oak Grove Elementary School 3 Building 2010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
No Ramp C Deficiency is included in a CIP project
Oak View Elementary School 2 Building 2010 Roofing Built-up Roofing Replacement Leaks Throughout C Deficiency is included in a CIP project
Oak View Elementary School 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing C Deficiency is included in a CIP project
Oak View Elementary School 3 Building 2010 Roofing Membrane Flashing At Parapet (>2') Repair C Deficiency is included in a CIP project
Oak View Elementary School 3 Building 2010 Roofing Metal Downspout Replacement C Deficiency is included in a CIP project
Oak View Elementary School 3 Building 2010 Site Room Signage Is Not ADA Compliant With Raised Letters And Braille C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Site Asphalt Driveway Replacement Beyond Useful Life C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2010 Interior Entry Door Does Not Have Power Assist Device C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2010 Interior Access Is Not ADA Compliant C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2010 Interior Access Is Not ADA Compliant Stage Doorway And Access Not Compliant C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2010 Interior Entry Door Does Not Have Power Assist Device C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2020 Interior Entry Door Does Not Have Power Assist Device C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2010 Interior Existing Toilet Stall Does Not Meet Minimum ADA Requirements C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2010 Conveyances Elevator is Not ADA Compliant Not Furnished For Low Level Access C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2010 Conveyances Platform Lift Needed for Access Missing C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2010 Conveyances Platform Lift Needed for Access None Furnished C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2010 Plumbing Existing Lavatory/Sink Is Not ADA Compliant C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2010 Plumbing Restroom Grab Bars Are Not ADA Compliant C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2010 Plumbing Restroom Is Not ADA Compliant C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2010 Site Van Accessible Parking Spaces Are Not Properly Striped C Deficiency is included in a CIP project
61 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Oakcliff Elementary School 3 Building 2010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA
PlanRequirements
North Main Entrance C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2011 Interior Access Is Not ADA Compliant C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2011 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2012 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2012 Interior Existing Toilet Stall Does Not Meet Minimum ADA Requirements C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2012 Plumbing Existing Lavatory/Sink Is Not ADA Compliant No Covers Under Sinks C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2012 Plumbing Restroom Grab Bars Are Not ADA Compliant C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Building 2012 Plumbing Restroom Is Not ADA Compliant C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Site Curb Ramp Does Not Meet Minimum ADA Compliance Requirements C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Site Car Accessible Parking Spaces Do Not Meet ADA Requirements C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Site Van Accessible Parking Spaces Do Not Meet ADA Requirements C Deficiency is included in a CIP project
Oakcliff Elementary School 3 Site Van Accessible Parking Spaces Are Not Properly Striped C Deficiency is included in a CIP project
Old Rock Gym 2 Building 8010 Exterior Brick Exterior Replacement (Bldg SF) Beyond Useful Life C Deficiency is included in a CIP project
They Use What Looks Like Mod Bit For A
Old Rock Gym 2 Building 8010 Roofing Modified Roof Covering Replacement C Deficiency is included in a CIP project
Vaulted Roof
Old Rock Gym 3 Building 8010 Roofing Gutter Replacement Beyond Useful Life C Deficiency is included in a CIP project
Old Rock Gym 3 Building 8010 Roofing Metal Downspout Replacement Beyond Useful Life C Deficiency is included in a CIP project
Old Rock Gym 2 Building 8010 Mechanical Gas Piping Replacement (SF Basis) Gym And Basement C Deficiency is included in a CIP project
Old Rock Gym 3 Building 8010 Plumbing Gas Water Heater Replacement C Deficiency is included in a CIP project
Old Rock Gym 3 Building 8010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life
Basement C Deficiency is included in a CIP project
Old Rock Gym 3 Building 8010 Plumbing Toilet Replacement C Deficiency is included in a CIP project
Old Rock Gym 3 Building 8010 Plumbing Urinal Replacement C Deficiency is included in a CIP project
Old Rock Gym 3 Building 8010 Plumbing Sanitary Sewer Piping Replacement C Deficiency is included in a CIP project
Old Rock Gym 2 Building 8010 Mechanical Gas Unit Heater Replacement C Deficiency is included in a CIP project
Old Rock Gym 2 Building 8010 Mechanical Gas Unit Heater Replacement C Deficiency is included in a CIP project
Old Rock Gym 3 Building 8010 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Old Rock Gym 3 Building 8010 Electrical Interior Power Wiring Replacement C Deficiency is included in a CIP project
Old Rock Gym 2 Building 8010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Old Rock Gym 3 Building 8010 Interior Existing Toilet Stall Does Not Meet Minimum ADA RequirementsMissing C Deficiency is included in a CIP project
Old Rock Gym 3 Building 8010 Conveyances Platform Lift Needed for Access Missing C Deficiency is included in a CIP project
Old Rock Gym 3 Building 8010 Plumbing Existing Lavatory/Sink Is Not ADA Compliant Missing C Deficiency is included in a CIP project
Old Rock Gym 3 Building 8010 Plumbing Restroom Grab Bars Are Not ADA Compliant Missing C Deficiency is included in a CIP project
Old Rock Gym 3 Building 8010 Plumbing Restroom Is Not ADA Compliant Missing C Deficiency is included in a CIP project
Old Rock Gym 3 Building 8010 Site Car Accessible Parking Spaces Do Not Meet ADA Requirements Missing C Deficiency is included in a CIP project
Old Rock Gym 3 Building 8010 Site Van Accessible Parking Spaces Do Not Meet ADA Requirements Missing C Deficiency is included in a CIP project
Old Rock Gym 3 Building 8010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
Missing C Deficiency is included in a CIP project
Panola Way Elementary School 2 Building 2010 Mechanical Steam Heat Exchanger Replacement 200 GPM C Deficiency is included in a CIP project
Panola Way Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement R22 Factory Charged System C Deficiency is included in a CIP project
Panola Way Elementary School 2 Building 2011 Mechanical Heat Pump HVAC Component Replacement R22 Factory Charged C Deficiency is included in a CIP project
Panola Way Elementary School 2 Building 2011 Mechanical Thru Wall AC Replacement C Deficiency is included in a CIP project
Panola Way Elementary School 2 Building 2020 Mechanical Thru Wall AC Replacement 1.5 Ton C Deficiency is included in a CIP project
Panola Way Elementary School 3 Building 2011 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
Missing Sign At Room 205 C Deficiency is included in a CIP project
Panthersville Administrative 3 Building 8010 Plumbing Restroom Is Not ADA Compliant No ADA Stalls C Deficiency is included in a CIP project
Panthersville Administrative 3 Building 8010 Site Car Accessible Parking Spaces Restiriping Missing C Deficiency is included in a CIP project
Panthersville Administrative 3 Building 8010 Site Van Accessible Parking Spaces Are Not Properly Striped Missing C Deficiency is included in a CIP project
Panthersville Administrative 3 Building 8010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
Missing C Deficiency is included in a CIP project
Panthersville Administrative 3 Building 8010 Site Exterior Signage At Accessible Parking Area Does Not Meet ADA Requirements
Missing C Deficiency is included in a CIP project
Panthersville Administrative 3 Building 8040 Exterior Exterior Entry Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Panthersville Administrative 3 Building 8040 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
Missing C Deficiency is included in a CIP project
Pine Ridge Elementary School 2 Building 2010 Mechanical Infrared Electric Radiant Heater Replacement C Deficiency is included in a CIP project
Pine Ridge Elementary School 2 Building 2010 Mechanical Ductwork Replacement (SF Basis) C Deficiency is included in a CIP project
Pine Ridge Elementary School 3 Building 2010 Mechanical Large Diameter Exhausts/Hoods Replacement Beyond Useful Life C Deficiency is included in a CIP project
Pine Ridge Elementary School 3 Building 2010 Interior Entry Door Does Not Have Power Assist Device C Deficiency is included in a CIP project
Pine Ridge Elementary School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height Requirements (Modify Full) C Deficiency is included in a CIP project
Princeton Elementary School 3 Building 2010 Plumbing Existing Lavatory/Sink Is Not ADA Compliant Add Insulation To Pipes C Deficiency is included in a CIP project
Princeton Elementary School 3 Building 2010 Site Car Accessible Parking Spaces Restiriping C Deficiency is included in a CIP project
Rainbow Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant All Interior Door Hardware Not Compliant C Deficiency is included in a CIP project
Rainbow Elementary School 3 Building 2011 Interior Existing Door Hardware Is Not ADA Compliant All Interior Door Hardware Not Compliant C Deficiency is included in a CIP project
Rainbow Elementary School 3 Site Exterior Ramp Replacement Not Existing, Install C Deficiency is included in a CIP project
62 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Rainbow Elementary School 3 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
Not Existing C Deficiency is included in a CIP project
Redan Elementary School 3 Building 2020 Interior Entry Door Does Not Have Power Assist Device C Deficiency is included in a CIP project
Redan Elementary School 3 Building 2011 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Redan Elementary School 3 Building 2021 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Redan Elementary School 3 Building 2020 Conveyances Platform Lift Needed for Access No Lift And ADA Access To Stage C Deficiency is included in a CIP project
Redan Elementary School 3 Building 2020 Plumbing Existing Lavatory/Sink Is Not ADA Compliant Add Pipe Insulation C Deficiency is included in a CIP project
Redan Elementary School 3 Building 2020 Plumbing Existing Lavatory/Sink Pipe Insulation Replacement Add Pipe Insulation At ADA Restroom Sink. C Deficiency is included in a CIP project
Redan Elementary School 3 Building 2020 Plumbing Restroom Grab Bars Are Not ADA Compliant Add Vertical Grab Bars C Deficiency is included in a CIP project
Redan Elementary School 3 Building 2020 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
No Ramp C Deficiency is included in a CIP project
Add Sink Pipe Insulation Small Office
Redan High School 3 Building 5010 Plumbing Existing Lavatory/Sink Pipe Insulation Replacement Restrooms And Gym Locker And Shower C Deficiency is included in a CIP project
Restrooms
Redan High School 3 Building 5010 Plumbing Restroom Is Not ADA Compliant Office Restrooms C Deficiency is included in a CIP project
Redan High School 3 Building 5010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsReplace
(ModifyAnd
Full)Add ADA Height C Deficiency is included in a CIP project
Redan High School 3 Building 5010 Specialties Seating is not ADA Compliant None Provided For Wheelchair C Deficiency is included in a CIP project
Redan High School 3 Building 5012 Plumbing Restroom Grab Bars Are Not ADA Compliant Ambulatory Stall Lvl1 Womens C Deficiency is included in a CIP project
Redan High School 3 Building 5012 Site Curb Ramp Does Not Meet Minimum ADA Compliance Requirements
No Ramp Provided And North End C Deficiency is included in a CIP project
Redan High School 3 Site Car Accessible Parking Spaces Restiriping North Lot And Aged C Deficiency is included in a CIP project
Redan High School 3 Site Van Accessible Parking Spaces Are Not Properly Striped North Lot And Aged C Deficiency is included in a CIP project
Redan Middle School 3 Building 4010 Interior Rubber Flooring Replacement Very Old; The Original C Deficiency is included in a CIP project
Redan Middle School 2 Building 4010 Mechanical Electric Unit Heater Replacement Broken C Deficiency is included in a CIP project
Redan Middle School 2 Building 4010 Mechanical Ductless Split System AC Replacement Beyond Useful Life C Deficiency is included in a CIP project
Redan Middle School 3 Building 4010 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Some Work Orders Have Been Submitted For
Redan Middle School 3 Building 4010 Electrical Canopy Lighting Replacement C Deficiency is included in a CIP project
Canopy Lights Replacement
Redan Middle School 3 Site Asphalt Driveway Replacement Bad Cracking, Pothole C Deficiency is included in a CIP project
Redan Middle School 3 Building 4010 Interior Entry Door Does Not Have Power Assist Device No Power Assist C Deficiency is included in a CIP project
Redan Middle School 3 Building 4010 Plumbing Existing Lavatory/Sink Pipe Insulation Replacement C Deficiency is included in a CIP project
Redan Middle School 3 Site Curb Ramp Does Not Meet Minimum ADA Compliance Requirements C Deficiency is included in a CIP project
Redan Middle School 3 Site Car Accessible Parking Spaces Do Not Meet ADA Requirements Non Compliant C Deficiency is included in a CIP project
Redan Middle School 3 Site Van Accessible Parking Spaces Do Not Meet ADA Requirements Non Compliant C Deficiency is included in a CIP project
Redan Middle School 3 Site Car Accessible Parking Spaces Restiriping C Deficiency is included in a CIP project
Redan Middle School 3 Site Van Accessible Parking Spaces Are Not Properly Striped C Deficiency is included in a CIP project
Redan Middle School 3 Site Exterior Signage At Accessible Parking Area Does Not Meet ADA Requirements
Poles Are Leaning C Deficiency is included in a CIP project
Robert Shaw Theme 3 Building 2010 Exterior Exterior Entry Door Hardware Is Not ADA Compliant Install Power Assist Hardware And Button. C Deficiency is included in a CIP project
115.1 - Boys Restroom - ADA Stall Has
Robert Shaw Theme 3 Building 2010 Interior Existing Toilet Stall Does Not Meet Minimum ADA RequirementsUneven Floor Next To Toilet. Rebuild Flat C Deficiency is included in a CIP project
Approx. 50Sf Floor Tile.
Powered Lift Exists, But Deficient. Repair,
Robert Shaw Theme 3 Building 2010 Conveyances Platform Lift Needed for Access C Deficiency is included in a CIP project
Replace Or Build Ramp ADA25.
Install ADA Sign At North-East And Main
Robert Shaw Theme 3 Building 2010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements C Deficiency is included in a CIP project
Entry.
Robert Shaw Theme 3 Building 2020 Exterior Exterior Entry Door Hardware Is Not ADA Compliant Add Power Assist Hardware. C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2010 Roofing Gutter Replacement Plan North C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2010 Roofing Roof Drain Cleaning C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2010 Mechanical Boiler Replacement Beyond Useful Life C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2010 Mechanical Circulation Pump Replacement Beyond Useful Life C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2010 Mechanical Exterior Metal Cooling Tower Replacement Beyond Useful Life C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life Water Source Heat Pumps C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2010 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2010 Mechanical Large Diameter Exhausts/Hoods Replacement Beyond Useful Life C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2010 Electrical Switchgear Replacement Beyond Useful Life Elec 6.2 C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement Old Wiring C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
63 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Rock Chapel Elementary School 2 Building 2010 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2011 Roofing Debris In Gutter Removal C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2011 Mechanical Electric Unit Heater Replacement C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2011 Mechanical Package DX Unit Replacement C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2011 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2011 Mechanical Thru Wall AC Replacement C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2011 Mechanical Large Diameter Exhausts/Hoods Replacement C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2011 Electrical Interior Power Wiring Replacement Old Wiring C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2011 Electrical Electrical Transformer Replacement C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2011 Electrical Electrical Transformer Replacement Kitchen Storage C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2011 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2011 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2011 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2011 Electrical Panelboard Replacement Kitchen C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2011 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2011 Electrical Panelboard Replacement Kitchen C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2012 Exterior Brick Exterior Repair Plan West Exit Door Arch. C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2012 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2012 Mechanical Electric Unit Heater Replacement C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2012 Mechanical Package DX Unit Replacement C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2012 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2012 Mechanical Large Diameter Exhausts/Hoods Replacement C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2012 Electrical Interior Power Wiring Replacement Old Wiring C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2012 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2012 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2012 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2013 Roofing Modified Covering Has Blisters That Should Be Repaired C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2013 Roofing Membrane Flashing At Parapet (>2') Repair Paint Peeling Off. C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2013 Roofing Metal Downspout Replacement Rusting Plan West C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2013 Mechanical Package DX Unit Replacement Actual Is 4 Ton C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2013 Mechanical Package DX Unit Replacement C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2013 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2020 Roofing Debris In Gutter Removal C Deficiency is included in a CIP project
Repair Inside The Gym Floor Seems Are
Rock Chapel Elementary School 3 Building 2020 Interior Athletic Sport Flooring Replacement C Deficiency is included in a CIP project
Falling Apart
Rock Chapel Elementary School 3 Building 2020 Plumbing Water Heater Repair Repair Relief Valve C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Building 2020 Mechanical Radiant Heater (Ceiling Panel) Replacement Beyond Useful Life C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Electrical Pole Lighting Repair Damaged Lens Cover C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Site Concrete Walks Replacement C Deficiency is included in a CIP project
Rock Chapel Elementary School 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility
Plan South And North C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2010 Interior Entry Door Does Not Have Power Assist Device C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2010 Plumbing Restroom Grab Bars Are Not ADA Compliant Room 3,4,5 C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsClassrooms
(Modify Full) C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2011 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2011 Conveyances Platform Lift Needed for Access C Deficiency is included in a CIP project
No Covers Under Sinks Rooms 97.9, 97.1,
Rock Chapel Elementary School 3 Building 2011 Plumbing Existing Lavatory/Sink Is Not ADA Compliant C Deficiency is included in a CIP project
97.10
Rock Chapel Elementary School 3 Building 2011 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2012 Interior Existing Door Hardware Is Not ADA Compliant Non-ADA Hardware C Deficiency is included in a CIP project
No Covers Under Sinks Room 16.1, 16.2,
Rock Chapel Elementary School 3 Building 2012 Plumbing Existing Lavatory/Sink Is Not ADA Compliant C Deficiency is included in a CIP project
97.10, 97.9, 97.1
Rock Chapel Elementary School 3 Building 2013 Plumbing Existing Lavatory/Sink Is Not ADA Compliant No Covers Under Sinks C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Building 2013 Specialties Counter Heights Exceed Maximum ADA Height RequirementsNon-ADA(Modify Full)
Counter Tops C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Site Car Accessible Parking Spaces Restiriping C Deficiency is included in a CIP project
Rock Chapel Elementary School 3 Site Van Accessible Parking Spaces Are Not Properly Striped C Deficiency is included in a CIP project
Toilet Paper Behind And Toilet - No Turning
Rowland Elementary School 3 Building 2010 Interior Existing Toilet Stall Does Not Meet Minimum ADA Requirements C Deficiency is included in a CIP project
Circle Space
Rowland Elementary School 3 Building 2010 Plumbing Existing Lavatory/Sink Pipe Insulation Replacement No Pipe Insulation - 15 Sinks C Deficiency is included in a CIP project
Rowland Elementary School 3 Building 2010 Plumbing Restroom Is Not ADA Compliant Too Small And No ADA C Deficiency is included in a CIP project
Rowland Elementary School 3 Site Curb Ramp Does Not Meet Minimum ADA Compliance Requirements Too Steep C Deficiency is included in a CIP project
64 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Rowland Elementary School 3 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
None Provided C Deficiency is included in a CIP project
Rowland Elementary School 3 Site Van Accessible Parking Spaces Are Not Properly Striped Damaged C Deficiency is included in a CIP project
Parking Signage Not Compliant - Not Provided
Rowland Elementary School 3 Site Exterior Signage At Accessible Parking Area Does Not Meet ADA Requirements C Deficiency is included in a CIP project
In Parking Lots - Install Parking Signage
Sagamore Hills Elementary School 3 Building 2010 Plumbing Existing Lavatory/Sink Is Not ADA Compliant Missing Pipe Insulation On Sinks C Deficiency is included in a CIP project
Sagamore Hills Elementary School 3 Building 2010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
Not Existing For Stage C Deficiency is included in a CIP project
Cracks And Blisters In Several Areas, Inspect
Salem Middle School 3 Building 4010 Roofing Modified Covering Has Blisters That Should Be Repaired C Deficiency is included in a CIP project
Closely, Areas Close To Drains
Salem Middle School 2 Building 4010 Roofing Modified Membrane Has Holes That Should Be Repaired Leaks In The South And Middle Wings C Deficiency is included in a CIP project
See Note On Roof Holes (Leaks In The South
Salem Middle School 3 Building 4010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
And Middle Wings) Ponding Is Related To C Deficiency is included in a CIP project
Specified Reems.
Salem Middle School 3 Building 4010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding Related To Specified Rooms C Deficiency is included in a CIP project
Salem Middle School 2 Building 4010 Mechanical Electric Unit Heater Replacement Damaged C Deficiency is included in a CIP project
Salem Middle School 2 Building 4010 Mechanical Exterior Metal Cooling Tower Replacement Damaged C Deficiency is included in a CIP project
Salem Middle School 2 Building 4010 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility
Cracked And Peeling C Deficiency is included in a CIP project
Cracks And Blisters In Several Areas, Inspect
Salem Middle School 3 Building 4011 Roofing Modified Covering Has Blisters That Should Be Repaired C Deficiency is included in a CIP project
Close To Drains
Salem Middle School 2 Building 4011 Roofing Modified Membrane Has Holes That Should Be Repaired Leaks In North And South Wings C Deficiency is included in a CIP project
Ponding Is Contributing To Holes And Leaks.
Cracks And Blisters In Several Areas, Inspect
Salem Middle School 3 Building 4011 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing C Deficiency is included in a CIP project
Close To Drains. Leaks In Both North And
South Wings Contributing To Holes And Leaks
Repair Flashing At Standing Seam Mtl System,
Salem Middle School 3 Building 4011 Roofing Membrane Flashing At Parapet (>2') Repair C Deficiency is included in a CIP project
Above Restrooms
Salem Middle School 3 Site Concrete Walks Replacement Damaged C Deficiency is included in a CIP project
Salem Middle School 3 Building 4010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsCounter
(ModifyToo
Full)Tall C Deficiency is included in a CIP project
Salem Middle School 3 Building 4010 Site Curb Ramp Does Not Meet Minimum ADA Compliance Requirements
Repaint Sidewalk Ramp With ADA Symbol C Deficiency is included in a CIP project
Salem Middle School 3 Building 4010 Site Van Accessible Parking Spaces Do Not Meet ADA Requirements Signs Are Faded, Not Visible C Deficiency is included in a CIP project
Salem Middle School 3 Building 4010 Site Car Accessible Parking Spaces Restiriping C Deficiency is included in a CIP project
Salem Middle School 3 Building 4010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
No Signage At Entry - Need To Install C Deficiency is included in a CIP project
Salem Middle School 3 Building 4010 Exterior Exterior Entry Door Hardware Is Not ADA Compliant Add Power Assist C Deficiency is included in a CIP project
Sam Moss Service Center 3 Site Car Accessible Parking Spaces Restiriping Beyond Useful Life C Deficiency is included in a CIP project
Sam Moss Service Center 3 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4010 Interior Interior Door Hardware Replacement Broken C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4012 Interior Interior Door Hardware Replacement Closers At Back Of Building C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4011 Interior Interior Door Hardware Replacement Door Closers C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4010 Exterior Exterior Metal Door Repainting Rusted C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4011 Exterior Exterior Metal Door Repainting Rusted C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4012 Exterior Exterior Metal Door Repainting Rusted C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4010 Exterior Metal Exterior Door Repair Rusted C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4011 Exterior Metal Exterior Door Repair Rusted C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4012 Exterior Metal Exterior Door Repair Rusted C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4010 Exterior Metal Exterior Door Replacement Rusted C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4011 Exterior Metal Exterior Door Replacement Rusted C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4012 Exterior Metal Exterior Door Replacement Rusted C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4040 Exterior Metal Exterior Door Replacement Rusted C Deficiency is included in a CIP project
Beyond Useful Life - Roof Leaks In Many
Sequoyah Middle School 2 Building 4010 Roofing Modified Roof Covering Replacement Places, Does Not Slope To Roof Drains And C Deficiency is included in a CIP project
Has Blisters In Many Locations
Sequoyah Middle School 3 Building 4010 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4010 Electrical Switchgear Replacement Failing FPE C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4010 Electrical Interior Power Wiring Replacement Beyond Useful Life C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4010 Electrical Canopy Lighting Replacement Not Working C Deficiency is included in a CIP project
Beyond Useful Life - Not Working And
Sequoyah Middle School 3 Building 4010 Electrical Canopy Lighting Replacement C Deficiency is included in a CIP project
Exterior
Sequoyah Middle School 2 Building 4010 Electrical Electrical Transformer Replacement Failing FPE C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4010 Electrical Electrical Transformer Replacement Failing FPE C Deficiency is included in a CIP project
65 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Sequoyah Middle School 2 Building 4010 Electrical Electrical Transformer Replacement Failing FPE C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4010 Electrical Electrical Transformer Replacement Failing FPE C Deficiency is included in a CIP project
Beyond Useful Life - Not Working And
Sequoyah Middle School 3 Building 4010 Electrical Exterior Mounted Building Lighting Replacement C Deficiency is included in a CIP project
Exterior
Sequoyah Middle School 2 Building 4010 Electrical Distribution Panel Replacement Failing FPE C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4010 Electrical Panelboard Replacement FPE C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4010 Electrical Panelboard Replacement Failing FPE C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4010 Electrical Panelboard Replacement FPE C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4010 Electrical Panelboard Replacement Failing FPE C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4010 Electrical Electrical Receptacle Replacement Receptacle Missing C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life C Deficiency is included in a CIP project
Beyond Useful Life - Roof Leaks In Many
Sequoyah Middle School 2 Building 4011 Roofing Modified Roof Covering Replacement Places, Does Not Slope To Roof Drains And C Deficiency is included in a CIP project
Has Blisters In Many Locations
Sequoyah Middle School 3 Building 4011 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4011 Electrical Interior Power Wiring Replacement Beyond Useful Life C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4011 Electrical Canopy Lighting Replacement Beyond Useful Life - Not Working C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4011 Electrical Electrical Transformer Replacement Beyond Useful Life C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4011 Electrical Electrical Transformer Replacement Beyond Useful Life C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4011 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life - Not Working C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4011 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4011 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4011 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4011 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life C Deficiency is included in a CIP project
Beyond Useful Life - Roof Leaks In Many
Sequoyah Middle School 2 Building 4012 Roofing Modified Roof Covering Replacement Places; Does Not Slope To Roof Drains; C Deficiency is included in a CIP project
Blisters In Many Locations
Gym Floor Is Too Thin Due To Sanding Many
Sequoyah Middle School 3 Building 4012 Interior Athletic Sport Flooring Replacement Times, Replace Both Levels, Replace Laminate C Deficiency is included in a CIP project
Flooring At Gym Balcony
Sequoyah Middle School 3 Building 4012 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4012 Electrical Interior Power Wiring Replacement Beyond Useful Life C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4012 Electrical Canopy Lighting Replacement Beyond Useful Life C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4012 Electrical Electrical Transformer Replacement Fpe And Beyond Useful Life C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4012 Electrical Electrical Transformer Replacement Beyond Useful Life C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4012 Electrical Electrical Transformer Replacement Beyond Useful Life C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4012 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4012 Electrical Panelboard Replacement Fpe And Beyond Useful Life C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4012 Electrical Panelboard Replacement Beyond Useful Life - Fpe C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4012 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Sequoyah Middle School 2 Building 4012 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4012 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4040 Electrical Electrical Receptacle Replacement Missing Wp Cover C Deficiency is included in a CIP project
Beyond Useful Life - Several Potholes And
Sequoyah Middle School 3 Site Asphalt Driveway Replacement C Deficiency is included in a CIP project
Raised Asphalt
Replace Cracked Sidewalk At 10 Locations;
Sequoyah Middle School 3 Site Concrete Walks Replacement C Deficiency is included in a CIP project
Repair 30' Of Damaged CMU Block
Sequoyah Middle School 3 Site Site Sanitary Sewer Piping Replacement C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4010 Interior Entry Door Does Not Have Power Assist Device Power Assist Not Working At Bathroom Doors C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4011 Interior Entry Door Does Not Have Power Assist Device Power Assist Not Working At Bathroom Doors C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4012 Interior Entry Door Does Not Have Power Assist Device Power Assist Not Working At Bathroom Doors C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4010 Plumbing Existing Lavatory/Sink Is Not ADA Compliant Need Sink Drain Insulation C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4010 Electrical Lightning Protection System Installation Not Installed C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
No Ramp To Stage C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4011 Plumbing Existing Lavatory/Sink Is Not ADA Compliant Need Sink Drain Insulation C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4011 Electrical Lightning Protection System Installation Not Installed C Deficiency is included in a CIP project
66 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Sequoyah Middle School 3 Building 4012 Plumbing Existing Lavatory/Sink Is Not ADA Compliant Need Sink Drain Insulation C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4012 Electrical Lightning Protection System Installation Not Installed C Deficiency is included in a CIP project
Sequoyah Middle School 3 Building 4012 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
No Ramp C Deficiency is included in a CIP project
Shadow Rock Elementary School 2 Building 2010 Mechanical Boiler Replacement Beyond Useful Life 1500 Mbh C Deficiency is included in a CIP project
Shadow Rock Elementary School 3 Building 2010 Mechanical Testing And Balancing Test C Deficiency is included in a CIP project
No Roof Access Assessment Done Using
Silver Hill Facility 2 Building 2010 Roofing Built-up Roofing Replacement C Deficiency is included in a CIP project
Google Earth.
Silver Hill Facility 2 Building 2010 Mechanical Gas Piping Replacement (SF Basis) Throughout C Deficiency is included in a CIP project
Silver Hill Facility 3 Building 2010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life
Throughout C Deficiency is included in a CIP project
Silver Hill Facility 3 Building 2010 Plumbing Sanitary Sewer Piping Replacement Throughout C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2010 Mechanical Boiler Replacement Mech Room C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2010 Mechanical Infrared Electric Radiant Heater Replacement Throughout C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2010 Mechanical Air Cooled Condenser Replacement Roof - No Access C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2010 Mechanical Ductless Split System AC Replacement Stage Storage C Deficiency is included in a CIP project
Silver Hill Facility 3 Building 2010 Mechanical Testing And Balancing Throughout C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2010 Mechanical Thru Wall AC Replacement Lower Level C Deficiency is included in a CIP project
Silver Hill Facility 3 Building 2010 Mechanical Kitchen Exhaust Hood Replacement Kitchen C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Throughout C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2010 Mechanical Ductwork Replacement (SF Basis) Throughout C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2010 Mechanical HVAC VAV Box Replacement Throughout C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2010 Mechanical Package Roof Top Unit Replacement Roof - No Access C Deficiency is included in a CIP project
Silver Hill Facility 3 Building 2010 Mechanical Large Diameter Exhausts/Hoods Replacement Roof - No Access C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2010 Electrical Switchgear Replacement Old, Elec Room C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2010 Electrical Electrical Transformer Replacement Old, Elec Room C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2010 Electrical Electrical Transformer Replacement Old, Elec Room C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2010 Electrical Motor Control Center Replacement Old, Elec Room C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2010 Electrical Panelboard Replacement Old, Elec Room C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2010 Electrical Panelboard Replacement Old, Elec Room C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2011 Roofing Built-up Roofing Replacement C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2011 Mechanical Gas Piping Replacement (SF Basis) Throughout C Deficiency is included in a CIP project
Silver Hill Facility 3 Building 2011 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life
Throughout C Deficiency is included in a CIP project
Silver Hill Facility 3 Building 2011 Plumbing Sanitary Sewer Piping Replacement Throughout C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2011 Mechanical Infrared Electric Radiant Heater Replacement Corridor C Deficiency is included in a CIP project
Silver Hill Facility 3 Building 2011 Mechanical Testing And Balancing Throughout C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2011 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Throughout C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2011 Mechanical Ductwork Replacement (SF Basis) Throughout C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2011 Mechanical HVAC VAV Box Replacement Throughout C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2011 Mechanical Package Roof Top Unit Replacement Roof - No Access C Deficiency is included in a CIP project
Silver Hill Facility 3 Building 2011 Mechanical Large Diameter Exhausts/Hoods Replacement Roof - No Access C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2011 Electrical Panelboard Replacement Old, Elec Room C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2011 Electrical Panelboard Replacement Old, Elec Room C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2020 Plumbing Water Heater Replacement Custodial C Deficiency is included in a CIP project
Silver Hill Facility 2 Building 2020 Mechanical Thru Wall AC Replacement Coach's Office C Deficiency is included in a CIP project
Silver Hill Facility 3 Site Asphalt Driveway Replacement Beyond Useful Life C Deficiency is included in a CIP project
Silver Hill Facility 3 Site Asphalt Walks Replacement Beyond Useful Life C Deficiency is included in a CIP project
Silver Hill Facility 3 Site Concrete Walks Replacement Worn Out C Deficiency is included in a CIP project
Silver Hill Facility 3 Site Wood Covered Walkways Replacement Beyond Useful Life C Deficiency is included in a CIP project
Silver Hill Facility 3 Building 2010 Interior Access Is Not ADA Compliant Door Knob Non-ADA C Deficiency is included in a CIP project
Silver Hill Facility 3 Building 2010 Interior Entry Door Does Not Have Power Assist Device Missing At Main Door Exit C Deficiency is included in a CIP project
Silver Hill Facility 3 Building 2010 Conveyances Platform Lift Needed for Access Missing C Deficiency is included in a CIP project
Silver Hill Facility 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsLacks (Modify
LowFull)
Countertop C Deficiency is included in a CIP project
Silver Hill Facility 3 Building 2010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
Missing C Deficiency is included in a CIP project
Snapfinger Elementary School 3 Site Asphalt Walks Replacement Damaged, Courtyard C Deficiency is included in a CIP project
Snapfinger Elementary School 3 Building 2010 Interior Entry Door Does Not Have Power Assist Device At ADA Entry C Deficiency is included in a CIP project
Snapfinger Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Snapfinger Elementary School 3 Building 2010 Conveyances Platform Lift Needed for Access Install Chair Lift C Deficiency is included in a CIP project
Snapfinger Elementary School 3 Building 2010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements C Deficiency is included in a CIP project
Snapfinger Elementary School 3 Building 2011 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Snapfinger Elementary School 3 Site Car Accessible Parking Spaces Restiriping C Deficiency is included in a CIP project
Toilet Flushes Wrong Side. Add Vertical Grab
Southwest DeKalb High School 3 Building 5030 Interior Existing Toilet Stall Does Not Meet Minimum ADA Requirements C Deficiency is included in a CIP project
Bar.
67 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Southwest DeKalb High School 3 Building 5040 Interior Existing Toilet Stall Does Not Meet Minimum ADA RequirementsFlush Valve On Wrong Side C Deficiency is included in a CIP project
Southwest DeKalb High School 3 Building 5040 Plumbing Restroom Grab Bars Are Not ADA Compliant Missing Vertical Grab Bar C Deficiency is included in a CIP project
Southwest DeKalb High School 3 Site Curb Ramp Does Not Meet Minimum ADA Compliance Requirements Missing Yellow Strip C Deficiency is included in a CIP project
Southwest DeKalb High School 3 Site Car Accessible Parking Spaces Restiriping Faded Lines C Deficiency is included in a CIP project
Southwest DeKalb High School 3 Site Van Accessible Parking Spaces Are Not Properly Striped Faded Lines C Deficiency is included in a CIP project
Stephenson High School 2 Building 5010 Mechanical Boiler Replacement C Deficiency is included in a CIP project
Stephenson High School 2 Building 5010 Mechanical Boiler Replacement C Deficiency is included in a CIP project
Stephenson High School 2 Building 5010 Mechanical Gas Furnace HVAC Component Replacement C Deficiency is included in a CIP project
Stephenson High School 3 Building 5010 Mechanical Circulation Pump Replacement C Deficiency is included in a CIP project
Stephenson High School 3 Building 5010 Mechanical Circulation Pump Replacement C Deficiency is included in a CIP project
Stephenson High School 2 Building 5010 Mechanical Electric Unit Heater Replacement C Deficiency is included in a CIP project
Stephenson High School 2 Building 5010 Mechanical Electric Unit Heater Replacement C Deficiency is included in a CIP project
Stephenson High School 2 Building 5010 Mechanical Gas Unit Heater Replacement C Deficiency is included in a CIP project
Stephenson High School 2 Building 5010 Mechanical Exterior Metal Cooling Tower Replacement C Deficiency is included in a CIP project
Stephenson High School 2 Building 5010 Mechanical Air Cooled Condenser Replacement C Deficiency is included in a CIP project
Stephenson High School 3 Building 5010 Mechanical Computer Room A/C Replacement C Deficiency is included in a CIP project
Stephenson High School 2 Building 5010 Mechanical Ductless Split System AC Replacement C Deficiency is included in a CIP project
Stephenson High School 2 Building 5010 Mechanical Fan Coil Unit Replacement C Deficiency is included in a CIP project
Stephenson High School 2 Building 5010 Mechanical Heat Pump HVAC Component Replacement C Deficiency is included in a CIP project
Stephenson High School 2 Building 5010 Mechanical Heat Pump HVAC Component Replacement C Deficiency is included in a CIP project
Stephenson High School 2 Building 5010 Mechanical Heat Pump HVAC Component Replacement C Deficiency is included in a CIP project
Stephenson High School 2 Building 5010 Mechanical Heat Pump HVAC Component Replacement C Deficiency is included in a CIP project
Stephenson High School 2 Building 5010 Mechanical Heat Pump HVAC Component Replacement C Deficiency is included in a CIP project
Stephenson High School 3 Building 5010 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Stephenson High School 3 Building 5010 Mechanical Energy Recovery Unit Replacement C Deficiency is included in a CIP project
Stephenson High School 3 Building 5010 Mechanical Make Up Air Equipment Replacement C Deficiency is included in a CIP project
Stephenson High School 3 Building 5010 Mechanical Kitchen Exhaust Hood Replacement C Deficiency is included in a CIP project
Stephenson High School 3 Building 5010 Mechanical Kitchen Exhaust Hood Replacement Roof Mounted Ventilator C Deficiency is included in a CIP project
Stephenson High School 2 Building 5010 Mechanical Air Handler HVAC Component Replacement C Deficiency is included in a CIP project
Stephenson High School 2 Building 5010 Mechanical Package Roof Top Unit Replacement C Deficiency is included in a CIP project
Stephenson High School 2 Building 5010 Mechanical Package Roof Top Unit Replacement C Deficiency is included in a CIP project
Stephenson High School 2 Building 5010 Mechanical Package Roof Top Unit Replacement C Deficiency is included in a CIP project
Stephenson High School 3 Building 5010 Mechanical Large Diameter Exhausts/Hoods Replacement C Deficiency is included in a CIP project
Stephenson High School 3 Building 5011 Mechanical Energy Recovery Unit Replacement Roof C Deficiency is included in a CIP project
Stephenson High School 2 Building 5020 Mechanical Electric Unit Heater Replacement C Deficiency is included in a CIP project
Stephenson High School 2 Building 5040 Mechanical Electric Unit Heater Replacement C Deficiency is included in a CIP project
Stephenson High School 2 Building 5050 Mechanical Electric Unit Heater Replacement C Deficiency is included in a CIP project
Stephenson High School 3 Building 5010 Interior Entry Door Does Not Have Power Assist Device C Deficiency is included in a CIP project
Stephenson Middle School 2 Building 4010 Mechanical Boiler Replacement C Deficiency is included in a CIP project
Stephenson Middle School 3 Building 4010 Mechanical Circulation Pump Replacement C Deficiency is included in a CIP project
Stephenson Middle School 3 Building 4010 Mechanical Circulation Pump Replacement C Deficiency is included in a CIP project
Stephenson Middle School 2 Building 4010 Mechanical Unit Ventilator Replacement C Deficiency is included in a CIP project
Stephenson Middle School 2 Building 4010 Mechanical Air Cooled Condenser Replacement C Deficiency is included in a CIP project
Stephenson Middle School 2 Building 4010 Mechanical Ductless Split System AC Replacement C Deficiency is included in a CIP project
Stephenson Middle School 2 Building 4010 Mechanical Fan Coil (Chilled Water) HVAC Component Replacement C Deficiency is included in a CIP project
Stephenson Middle School 2 Building 4010 Mechanical Fan Coil (Chilled Water) HVAC Component Replacement C Deficiency is included in a CIP project
Stephenson Middle School 3 Building 4010 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Stephenson Middle School 3 Building 4010 Mechanical Energy Recovery Unit Replacement C Deficiency is included in a CIP project
Stephenson Middle School 2 Building 4010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life C Deficiency is included in a CIP project
Stephenson Middle School 2 Building 4010 Mechanical Ductwork Replacement (SF Basis) C Deficiency is included in a CIP project
Stephenson Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement C Deficiency is included in a CIP project
Stephenson Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement C Deficiency is included in a CIP project
Stephenson Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement C Deficiency is included in a CIP project
Stephenson Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement C Deficiency is included in a CIP project
Stephenson Middle School 3 Building 4010 Mechanical Large Diameter Exhausts/Hoods Replacement C Deficiency is included in a CIP project
Stephenson Middle School 2 Building 4011 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life C Deficiency is included in a CIP project
Stephenson Middle School 2 Building 4011 Mechanical Ductwork Replacement (SF Basis) C Deficiency is included in a CIP project
Stephenson Middle School 3 Building 4010 Interior Entry Door Does Not Have Power Assist Device C Deficiency is included in a CIP project
Stephenson Middle School 3 Building 4010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation C Deficiency is included in a CIP project
Stone Mill Elementary School 3 Building 2010 Interior Existing Toilet Stall Does Not Meet Minimum ADA RequirementsNot ADA C Deficiency is included in a CIP project
Stone Mill Elementary School 3 Building 2010 Conveyances Platform Lift Needed for Access No Ramp At Stage C Deficiency is included in a CIP project
68 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Stone Mill Elementary School 3 Building 2010 Plumbing Existing Lavatory/Sink Pipe Insulation Replacement 8 Each C Deficiency is included in a CIP project
Stone Mill Elementary School 3 Building 2010 Plumbing Restroom Grab Bars Are Not ADA Compliant Not ADA C Deficiency is included in a CIP project
Stone Mill Elementary School 3 Building 2011 Plumbing Existing Lavatory/Sink Pipe Insulation Replacement 8 Each C Deficiency is included in a CIP project
Stone Mill Elementary School 3 Building 2012 Plumbing Existing Lavatory/Sink Pipe Insulation Replacement 8 Each C Deficiency is included in a CIP project
Stone Mill Elementary School 3 Site Car Accessible Parking Spaces Restiriping Resurface Asphalt And Paint C Deficiency is included in a CIP project
Stone Mountain Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant All Interior Door Hardware Not Compliant C Deficiency is included in a CIP project
Stone Mountain Elementary School 3 Building 2011 Interior Existing Door Hardware Is Not ADA Compliant All Interior Door Hardware Not Compliant C Deficiency is included in a CIP project
Stone Mountain Elementary School 3 Building 2010 Specialties (Modify
Counter Heights Exceed Maximum ADA Height RequirementsHeight Full)
Not ADA Compliant C Deficiency is included in a CIP project
Stone Mountain Elementary School 3 Building 2010 Site Car Accessible Parking Spaces Do Not Meet ADA Requirements
Add Compliant Spaces For Size Of Building C Deficiency is included in a CIP project
Stone Mountain Elementary School 3 Building 2010 Site Van Accessible Parking Spaces Are Not Properly Striped No ADA Signage C Deficiency is included in a CIP project
Stone Mountain Elementary School 3 Building 2012 Interior Existing Door Hardware Is Not ADA Compliant All Interior Door Hardware Not Compliant C Deficiency is included in a CIP project
Stone Mountain Elementary School 3 Building 2013 Interior Existing Door Hardware Is Not ADA Compliant All Interior Door Hardware Not Compliant C Deficiency is included in a CIP project
Stone Mountain Elementary School 3 Building 2010 Exterior Exterior Entry Door Hardware Is Not ADA Compliant Add Power Assist Hardware C Deficiency is included in a CIP project
Stone Mountain Elementary School 3 Building 2013 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
Not Present For Stage Access C Deficiency is included in a CIP project
Stone Mountain Elementary School 3 Building 2020 Exterior Exterior Entry Door Hardware Is Not ADA Compliant No Power Assist At Entry Doors C Deficiency is included in a CIP project
Stone Mountain Elementary School 3 Building 2020 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
No Signage At Building C Deficiency is included in a CIP project
Stone Mountain High School 3 Building 5010 Interior Entry Door Does Not Have Power Assist Device Missing C Deficiency is included in a CIP project
Stone Mountain High School 3 Building 5010 Specialties Seating is not ADA Compliant Include 7; Missing C Deficiency is included in a CIP project
Stone Mountain High School 3 Building 5010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
Missing C Deficiency is included in a CIP project
Stone Mountain Middle School 3 Building 4010 Interior Entry Door Does Not Have Power Assist Device Include 1; Missing C Deficiency is included in a CIP project
Stone Mountain Middle School 3 Building 4010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
Missing C Deficiency is included in a CIP project
Stoneview Elementary School 2 Building 2010 Roofing Modified Roof Covering Replacement Leaking Roof C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2010 Roofing Debris In Gutter Removal C Deficiency is included in a CIP project
Stoneview Elementary School 2 Building 2010 Roofing Gutter Joint Repair C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2010 Roofing Membrane Flashing At Parapet (>2') Repair C Deficiency is included in a CIP project
Stoneview Elementary School 2 Building 2010 Roofing Skylight Replacement Cracked And Taped C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2010 Interior Rubber Flooring Replacement Cracking And Lifting C Deficiency is included in a CIP project
Stoneview Elementary School 2 Building 2010 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility C Deficiency is included in a CIP project
Stoneview Elementary School 2 Building 2011 Roofing Modified Roof Covering Replacement Beyond Useful Life - Leaking Roof C Deficiency is included in a CIP project
Stoneview Elementary School 2 Building 2012 Roofing Modified Roof Covering Replacement Leaking Roof C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2012 Roofing Debris In Gutter Removal C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2012 Roofing Membrane Flashing At Parapet (>2') Repair C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2012 Interior Interior Brick/Stone Replacement (Bldg SF) Cracked CMU Wall C Deficiency is included in a CIP project
Stoneview Elementary School 2 Building 2013 Roofing Modified Roof Covering Replacement Beyond Useful Life- Leaking Roof C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2013 Roofing Debris In Gutter Removal C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2013 Roofing Membrane Flashing At Parapet (>2') Repair C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Foliage Growing C Deficiency is included in a CIP project
Stoneview Elementary School 2 Building 2020 Roofing Gutter Joint Repair Leaking C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2020 Roofing Metal Downspout Replacement C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2020 Interior Athletic Sport Flooring Replacement Worn And Separating C Deficiency is included in a CIP project
Stoneview Elementary School 3 Site Asphalt Driveway Replacement Beyond Useful Life C Deficiency is included in a CIP project
Stoneview Elementary School 3 Site Asphalt Walks Replacement C Deficiency is included in a CIP project
Stoneview Elementary School 3 Site Concrete Walks Replacement C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2010 Site Exterior Ramp Replacement C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2010 Interior Access Is Not ADA Compliant C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2010 Interior Access Is Not ADA Compliant C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2010 Interior Entry Door Does Not Have Power Assist Device C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2010 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2010 Interior Existing Toilet Stall Does Not Meet Minimum ADA Requirements C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2010 Conveyances Platform Lift Needed for Access C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2010 Plumbing Restroom Is Not ADA Compliant C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height Requirements (Modify Full) C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2010 Site Curb Ramp Does Not Meet Minimum ADA Compliance Requirements C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2010 Site Car Accessible Parking Spaces Restiriping C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2010 Site Van Accessible Parking Spaces Are Not Properly Striped C Deficiency is included in a CIP project
69 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Stoneview Elementary School 3 Building 2010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2010 Site Exterior Signage At Accessible Parking Area Does Not Meet ADA Requirements
Faded Sign C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2011 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2012 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2013 Interior Existing Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2013 Plumbing Existing Lavatory/Sink Pipe Insulation Replacement C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2020 Plumbing Existing Lavatory/Sink Pipe Insulation Replacement C Deficiency is included in a CIP project
Beyond Useful Life - Caulking Worn And
Stoneview Elementary School 2 Building 2010 Exterior Aluminum Window Replacement C Deficiency is included in a CIP project
Cracking
Beyond Useful Life - Caulking Worn And
Stoneview Elementary School 2 Building 2010 Exterior Aluminum Window Replacement C Deficiency is included in a CIP project
Cracking
Beyond Useful Life - Caulking Worn And
Stoneview Elementary School 2 Building 2010 Exterior Aluminum Window Replacement C Deficiency is included in a CIP project
Cracking
Stoneview Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Beyond Useful Life C Deficiency is included in a CIP project
Stoneview Elementary School 2 Building 2012 Exterior Aluminum Window Replacement Beyond Useful Life C Deficiency is included in a CIP project
Stoneview Elementary School 3 Electrical Area Lighting Installation C Deficiency is included in a CIP project
Stoneview Elementary School 3 Building 2013 Interior Interior Door Hardware Replacement C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2010 Roofing Modified Covering Has Blisters That Should Be Repaired Large Blisters Throughout C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2010 Roofing Debris In Gutter Removal Debris C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2010 Roofing Membrane Flashing At Parapet (>2') Repair Gaps C Deficiency is included in a CIP project
Cabinet Heaters In Girls 21.3 And Boys 22.1,
Toney Elementary School 2 Building 2010 Mechanical Electric Unit Heater Replacement C Deficiency is included in a CIP project
Corridor
Toney Elementary School 2 Building 2010 Mechanical Ductless Split System AC Replacement Janitor - 21 C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement Janitor - 21 C Deficiency is included in a CIP project
Water Source Heat Pumps - Throughout
Toney Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement C Deficiency is included in a CIP project
Building
Water Source Heat Pumps - Throughout
Toney Elementary School 2 Building 2010 Mechanical Package DX Unit Replacement C Deficiency is included in a CIP project
Building
Toney Elementary School 3 Building 2010 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2010 Mechanical Kitchen Exhaust Hood Replacement C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement Old Building, Wiring C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life - 50A C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2010 Electrical Panelboard Replacement 50A C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2010 Electrical Panelboard Replacement 70A, Beyond Useful Life - Stage C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life - Kitchen C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2010 Electrical Panelboard Replacement 200A, Beyond Useful Life - Stage C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2010 Electrical Panelboard Replacement 200A, Beyond Useful Life - Kitchen C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2011 Roofing Modified Roof Covering Replacement Large Blisters Throughout C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2011 Roofing Debris In Gutter Removal Debris C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2011 Roofing Membrane Flashing At Parapet (>2') Repair Gaps C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2011 Mechanical Electric Unit Heater Replacement Boys - 6.1, Girls - 6.2, Corridor. C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2011 Mechanical Package DX Unit Replacement Throughout - Water Source Heat Pumps C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2011 Mechanical Package DX Unit Replacement Throughout - Water Source Heat Pumps. C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2011 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2011 Electrical Interior Power Wiring Replacement Old Wiring C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2012 Exterior Brick Exterior Replacement (Bldg SF) Infill Louver Panel Opening C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2012 Roofing Modified Roof Covering Replacement Large Blisters C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2012 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2012 Roofing Debris In Gutter Removal Debris C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2012 Roofing Membrane Flashing At Parapet (>2') Repair Gaps C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2012 Mechanical Boiler Replacement Mech 36.1 C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2012 Mechanical Heat Exchanger Replacement 480 Gpm - Mech 36.1 C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2012 Mechanical Circulation Pump Replacement Mech 36.1 C Deficiency is included in a CIP project
70 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Toney Elementary School 3 Building 2012 Mechanical Circulation Pump Replacement Mech 36.1 C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2012 Mechanical Electric Unit Heater Replacement Corridor C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2012 Mechanical Package DX Unit Replacement Throughout - Water Source Heat Pumps C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2012 Mechanical Package DX Unit Replacement Throughout - Water Source Heat Pumps C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2012 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2012 Electrical Interior Power Wiring Replacement Old Wiring C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2012 Electrical Panelboard Replacement C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2012 Electrical Panelboard Replacement Mech 36.1 C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2012 Electrical Panelboard Replacement Mech 36.1 C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2020 Roofing Metal Roof Architectural Roof Covering Replacement Visible Signs Of Roof Leaks C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2020 Roofing Debris In Gutter Removal Debris C Deficiency is included in a CIP project
Toney Elementary School 2 Building 2020 Roofing Gutter Joint Repair Water Leaking Thru C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2020 Roofing Gutter Replacement Damaged C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2020 Roofing Roof Drain Cleaning Clogged - Down Spouts C Deficiency is included in a CIP project
Toney Elementary School 3 Site Asphalt Driveway Replacement Beyond Useful Life C Deficiency is included in a CIP project
Toney Elementary School 3 Site Asphalt Walks Replacement Beyond Useful Life Cracked C Deficiency is included in a CIP project
Toney Elementary School 3 Site Concrete Walks Replacement Beyond Useful Life Cracked C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2010 Interior Access Is Not ADA Compliant Door Knobs Non-Compliant C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2010 Interior Entry Door Does Not Have Power Assist Device Missing At Main Door Exit C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2010 Conveyances Platform Lift Needed for Access None Available C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsNo (Modify Full) Available.
Low Counter C Deficiency is included in a CIP project
Toney Elementary School 3 Building 2010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
Missing C Deficiency is included in a CIP project
Elevator Has Been Out Of Commission 3+
Towers High School 2 Building 5011 Conveyances Elevator Cab Replacement C Deficiency is included in a CIP project
Years.
Towers High School 3 Building 5010 Conveyances Platform Lift Needed for Access Beyond Useful Life C Deficiency is included in a CIP project
Towers High School 3 Building 5010 Plumbing Existing Lavatory/Sink Is Not ADA Compliant Insulation Covered Need For Sinks C Deficiency is included in a CIP project
Towers High School 3 Building 5010 Site Car Accessible Parking Spaces Restiriping Faded Paint C Deficiency is included in a CIP project
Towers High School 3 Building 5013 Plumbing Existing Lavatory/Sink Is Not ADA Compliant Insulation Covers Needed For Sink C Deficiency is included in a CIP project
Vanderlyn Elementary School 3 Building 2010 Interior Existing Toilet Stall Does Not Meet Minimum ADA RequirementsStall Not Compliant C Deficiency is included in a CIP project
Vanderlyn Elementary School 3 Building 2010 Plumbing Existing Lavatory/Sink Is Not ADA Compliant Add Pipe Insulation Under Sinks C Deficiency is included in a CIP project
Vanderlyn Elementary School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsAdmin (Modify Full) C Deficiency is included in a CIP project
Vanderlyn Elementary School 3 Site Car Accessible Parking Spaces Restiriping Faded Paint Stripe C Deficiency is included in a CIP project
Wadsworth Magnet School 3 Building 2010 Interior Entry Door Does Not Have Power Assist Device Not At Entry, North C Deficiency is included in a CIP project
Wadsworth Magnet School 3 Building 2020 Interior Entry Door Does Not Have Power Assist Device Add Power Door To Gym C Deficiency is included in a CIP project
Wadsworth Magnet School 3 Building 2010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsNo (Modify Full)
ADA Counter, Install. C Deficiency is included in a CIP project
Wadsworth Magnet School 3 Building 2010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
No ADA Access To Stage C Deficiency is included in a CIP project
Wadsworth Magnet School 3 Building 2010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
No Sign At Main Entry (North) C Deficiency is included in a CIP project
Wadsworth Magnet School 3 Building 2010 Exterior Exterior Entry Door Hardware Is Not ADA Compliant C Deficiency is included in a CIP project
Wadsworth Magnet School 3 Building 2020 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA
ADARequirements
Sign To Gym C Deficiency is included in a CIP project
Warren Technical Chamblee 3 Building 4010 Specialties Counter Heights Exceed Maximum ADA Height RequirementsMain (Modify Full)
Office C Deficiency is included in a CIP project
Warren Technical Chamblee 3 Building 4010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
Lift Provided I.L.O. Ramp C Deficiency is included in a CIP project
Warren Technical Chamblee 3 Building 4010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
No Signage C Deficiency is included in a CIP project
Warren Technical Chamblee 3 Building 4011 Specialties Counter Heights Exceed Maximum ADA Height Requirements (Modify Full) C Deficiency is included in a CIP project
William Bradley Bryant Technology Center 3 Building 8010 Plumbing Restroom Grab Bars Are Not ADA Compliant Missing Vertical Grab Bars C Deficiency is included in a CIP project
Needs Insulation Under Coverings On Pipes
William Bradley Bryant Technology Center 3 Building 8011 Plumbing Existing Lavatory/Sink Is Not ADA Compliant C Deficiency is included in a CIP project
Under Sinks
William Buck Godfrey Stadium 3 Building 8010 Interior Access Is Not ADA Compliant Change Knobs C Deficiency is included in a CIP project
William Buck Godfrey Stadium 3 Building 8010 Interior Existing Door Hardware Is Not ADA Compliant Door Knobs To Restrooms C Deficiency is included in a CIP project
William Buck Godfrey Stadium 3 Building 8010 Specialties Counter Heights Exceed Maximum ADA Height Requirements (Modify Full) C Deficiency is included in a CIP project
William Buck Godfrey Stadium 3 Building 8010 Specialties Seating is not ADA Compliant Missing C Deficiency is included in a CIP project
William Buck Godfrey Stadium 3 Building 8010 Site Exterior Entry Signage At The Building Entry Does Not Meet ADA Requirements
Missing C Deficiency is included in a CIP project
Woodward Elementary School 2 Building 2010 Mechanical Steam/Hot Water Radiant Heater Replacement Beyond Useful Life C Deficiency is included in a CIP project
Woodward Elementary School 3 Building 2010 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Woodward Elementary School 3 Building 2010 Mechanical Kitchen Exhaust Hood Replacement Beyond Useful Life C Deficiency is included in a CIP project
Woodward Elementary School 2 Building 2010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Beyond Useful Life C Deficiency is included in a CIP project
Woodward Elementary School 2 Building 2010 Mechanical Ductwork Replacement (SF Basis) C Deficiency is included in a CIP project
Woodward Elementary School 3 Building 2011 Mechanical Testing And Balancing Beyond Useful Life C Deficiency is included in a CIP project
Woodward Elementary School 2 Building 2011 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Beyond Useful Life C Deficiency is included in a CIP project
Woodward Elementary School 2 Building 2011 Mechanical Ductwork Replacement (SF Basis) Beyond Useful Life C Deficiency is included in a CIP project
Woodward Elementary School 3 Building 2012 Mechanical Testing And Balancing C Deficiency is included in a CIP project
Woodward Elementary School 3 Building 2020 Mechanical Testing And Balancing Beyond Useful Life C Deficiency is included in a CIP project
71 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Woodward Elementary School 3 Building 2010 Site Access Is Not ADA Compliant - ADA Compliant Ramp Installation
No Ramp C Deficiency is included in a CIP project
Wynbrooke Elementary School 3 Building 2010 Site Car Accessible Parking Spaces Restiriping Lines Faded C Deficiency is included in a CIP project
Adams Stadium 3 Building 8010 Electrical Interior Power Wiring Replacement Beyond Useful Life - Stadium D Deficiency supports new CIP project
Adams Stadium 2 Building 8010 Electrical Panelboard Replacement Beyond Useful Life - Storage D Deficiency supports new CIP project
Adams Stadium 2 Building 8010 Electrical Panelboard Replacement Beyond Useful Life - Boiler Room D Deficiency supports new CIP project
Adams Stadium 2 Building 8010 Electrical Panelboard Replacement Beyond Useful Life - Storage D Deficiency supports new CIP project
Adams Stadium 2 Building 8010 Mechanical Boiler Replacement Beyond Useful Life - Boiler Room D Deficiency supports new CIP project
Adams Stadium 2 Building 8010 Mechanical Electric Unit Heater Replacement Beyond Useful Life D Deficiency supports new CIP project
Adams Stadium 2 Building 8010 Mechanical Infrared Electric Radiant Heater Replacement Beyond Useful Life - Stadium D Deficiency supports new CIP project
Adams Stadium 3 Building 8010 Plumbing Toilet Replacement Beyond Useful Life - Stadium D Deficiency supports new CIP project
Adams Stadium 3 Building 8010 Plumbing Urinal Replacement Beyond Useful Life - Stadium D Deficiency supports new CIP project
Administrative and Instructional Complex (AIC) 2 Building 9010 Electrical Distribution Panel Replacement E412 D Deficiency supports new CIP project
Administrative and Instructional Complex (AIC) 2 Building 9010 Electrical Panelboard Replacement Old Elec Room By 01 D Deficiency supports new CIP project
Administrative and Instructional Complex (AIC) 2 Building 9010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Administrative and Instructional Complex (AIC) 2 Building 9010 Electrical Panelboard Replacement Old Elec J-115 And Mdf D Deficiency supports new CIP project
Administrative and Instructional Complex (AIC) 2 Building 9010 Electrical Switchgear Replacement D Deficiency supports new CIP project
Administrative and Instructional Complex (AIC) 2 Building 9012 Mechanical Ductless Split System AC Replacement Beyond Useful Life D Deficiency supports new CIP project
1 Making Noise And The Other One Is Missing
Administrative and Instructional Complex (AIC) 3 Building 9012 Mechanical Large Diameter Exhausts/Hoods Replacement D Deficiency supports new CIP project
Top Section.
Administrative and Instructional Complex (AIC) 2 Building 9010 Mechanical Package Roof Top Unit Replacement D Deficiency supports new CIP project
Administrative and Instructional Complex (AIC) 2 Building 9010 Mechanical Package Roof Top Unit Replacement D Deficiency supports new CIP project
Administrative and Instructional Complex (AIC) 2 Building 9011 Mechanical Package Roof Top Unit Replacement D Deficiency supports new CIP project
Administrative and Instructional Complex (AIC) 2 Building 9012 Mechanical Package Roof Top Unit Replacement Replace, Corrosion, Noise D Deficiency supports new CIP project
Administrative and Instructional Complex (AIC) 2 Building 9012 Mechanical Package Roof Top Unit Replacement D Deficiency supports new CIP project
Administrative and Instructional Complex (AIC) 2 Building 9012 Mechanical Package Roof Top Unit Replacement Replace Roof, Rls, R22 D Deficiency supports new CIP project
Administrative and Instructional Complex (AIC) 2 Building 9010 Roofing Metal Roof Architectural Roof Covering Replacement Repair Column Flashing D Deficiency supports new CIP project
Administrative and Instructional Complex (AIC) 2 Building 9010 Roofing Modified Roof Covering Replacement Water Ponding At Edge D Deficiency supports new CIP project
Avondale Elementary School 3 Building 2012 Mechanical Energy Recovery Unit Replacement Beyond Useful Life D Deficiency supports new CIP project
Avondale Elementary School 2 Building 2010 Mechanical Gas Piping Replacement (SF Basis) D Deficiency supports new CIP project
Avondale Elementary School 3 Building 2010 Mechanical Testing And Balancing Test D Deficiency supports new CIP project
Avondale Elementary School 3 Building 2011 Mechanical Testing And Balancing Test D Deficiency supports new CIP project
Avondale Elementary School 3 Building 2012 Mechanical Testing And Balancing D Deficiency supports new CIP project
Avondale Elementary School 3 Building 2014 Mechanical Testing And Balancing Test D Deficiency supports new CIP project
Avondale Elementary School 3 Building 2020 Mechanical Testing And Balancing Test D Deficiency supports new CIP project
Avondale Elementary School 3 Building 2010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life D Deficiency supports new CIP project
Avondale High DSA 2 Building 5010 Electrical Distribution Panel Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5011 Electrical Distribution Panel Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5010 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5011 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
Avondale High DSA 3 Building 5010 Electrical Interior Power Wiring Replacement Old Wiring D Deficiency supports new CIP project
Avondale High DSA 3 Building 5011 Electrical Interior Power Wiring Replacement Old Wiring D Deficiency supports new CIP project
Avondale High DSA 3 Building 5020 Electrical Interior Power Wiring Replacement Old Wiring - Exposed Wiring In Cr 311 D Deficiency supports new CIP project
Avondale High DSA 3 Building 5021 Electrical Interior Power Wiring Replacement Old Wiring D Deficiency supports new CIP project
Avondale High DSA 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Avondale High DSA 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Avondale High DSA 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Avondale High DSA 2 Building 5010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Avondale High DSA 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Avondale High DSA 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Avondale High DSA 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Avondale High DSA 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Avondale High DSA 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Avondale High DSA 2 Building 5010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Avondale High DSA 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Avondale High DSA 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Avondale High DSA 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Avondale High DSA 2 Building 5010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5010 Electrical Panelboard Replacement D Deficiency supports new CIP project
72 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Avondale High DSA 2 Building 5011 Electrical Panelboard Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5011 Electrical Panelboard Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5011 Electrical Panelboard Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5011 Electrical Panelboard Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5011 Electrical Panelboard Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5011 Electrical Panelboard Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5011 Electrical Panelboard Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5011 Electrical Panelboard Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5011 Electrical Panelboard Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5011 Electrical Panelboard Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5011 Electrical Panelboard Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5011 Electrical Panelboard Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5020 Electrical Panelboard Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5020 Electrical Panelboard Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5020 Electrical Panelboard Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5020 Electrical Panelboard Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5021 Electrical Panelboard Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5022 Electrical Panelboard Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5010 Mechanical Electric Unit Heater Replacement D Deficiency supports new CIP project
Avondale High DSA 2 Building 5020 Mechanical Electric Unit Heater Replacement Replace D Deficiency supports new CIP project
Avondale High DSA 3 Building 5011 Plumbing Shower Replacement Replace Fixtures D Deficiency supports new CIP project
Avondale High DSA 3 Building 5011 Plumbing Toilet Replacement Replace Fixtures D Deficiency supports new CIP project
Avondale High DSA 3 Building 5011 Plumbing Urinal Replacement Replace Fixtures D Deficiency supports new CIP project
Avondale High DSA 2 Building 5010 Roofing Built-up Roofing Replacement Beyond Useful Life D Deficiency supports new CIP project
Avondale High DSA 2 Building 5011 Roofing Built-up Roofing Replacement Beyond Useful Life D Deficiency supports new CIP project
Avondale High DSA 2 Building 5020 Roofing Built-up Roofing Replacement Beyond Useful Life D Deficiency supports new CIP project
Avondale High DSA 3 Building 5022 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing D Deficiency supports new CIP project
Avondale High DSA 3 Site Concrete Walks Replacement Cracked D Deficiency supports new CIP project
Avondale High DSA 3 Site Wood Covered Walkways Replacement Beyond Useful Life D Deficiency supports new CIP project
Avondale Stadium 2 Building 8010 Electrical Panelboard Replacement Concessions D Deficiency supports new CIP project
Avondale Stadium 2 Building 8010 Electrical Panelboard Replacement Storage D Deficiency supports new CIP project
Avondale Stadium 2 Building 8010 Electrical Switchgear Replacement D Deficiency supports new CIP project
Avondale Stadium 2 Building 8010 Mechanical Cast Iron Water Boiler Replacement Boiler Room D Deficiency supports new CIP project
Avondale Stadium 2 Building 8010 Mechanical Copper Tube Boiler Replacement Boiler Room D Deficiency supports new CIP project
Avondale Stadium 2 Building 8010 Mechanical Infrared Electric Radiant Heater Replacement Throughout D Deficiency supports new CIP project
Avondale Stadium 2 Building 8010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Throughout D Deficiency supports new CIP project
Avondale Stadium 2 Building 8010 Mechanical Steam/HW Unit Heater Replacement Concessions D Deficiency supports new CIP project
Avondale Stadium 2 Building 8010 Mechanical Steam/HW Unit Heater Replacement Throughout D Deficiency supports new CIP project
Avondale Stadium 3 Building 8010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life
Throughout D Deficiency supports new CIP project
Avondale Stadium 3 Building 8010 Plumbing Sanitary Sewer Piping Replacement Throughout D Deficiency supports new CIP project
Avondale Stadium 3 Site Concrete Driveways Replacement Cracked D Deficiency supports new CIP project
Avondale Stadium 3 Site Concrete Walks Replacement Cracked D Deficiency supports new CIP project
Driveway Cracked And Deficient Throughout.
Bob Mathis Elementary School 3 Site Asphalt Driveway Replacement D Deficiency supports new CIP project
Replace.
Brockett Elementary School 2 Building 2010 Mechanical Electric Unit Heater Replacement Boys And Girls Restrooms, Storage D Deficiency supports new CIP project
Brockett Elementary School 3 Building 2010 Mechanical Kitchen Air/Exhaust Installation D Deficiency supports new CIP project
Brockett Elementary School 3 Building 2010 Mechanical Large Diameter Exhausts/Hoods Replacement Stage D Deficiency supports new CIP project
Brockett Elementary School 3 Building 2012 Mechanical Large Diameter Exhausts/Hoods Replacement D Deficiency supports new CIP project
Brockett Elementary School 3 Building 2012 Mechanical Small Diameter Exhausts/Hoods Replacement Other 24.1 D Deficiency supports new CIP project
Brockett Elementary School 3 Building 2010 Mechanical Testing And Balancing D Deficiency supports new CIP project
Brockett Elementary School 3 Building 2012 Mechanical Testing And Balancing D Deficiency supports new CIP project
Brockett Elementary School 2 Building 2020 Mechanical Thru Wall AC Replacement Office D Deficiency supports new CIP project
Brockett Elementary School 3 Site Asphalt Driveway Replacement Cracked D Deficiency supports new CIP project
Brockett Elementary School 3 Site Asphalt Walks Replacement Cracked D Deficiency supports new CIP project
Browns Mill Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Mech Room 920 D Deficiency supports new CIP project
Browns Mill Elementary School 2 Building 2020 Electrical Exterior Dry Type Transformer Replacement D Deficiency supports new CIP project
Browns Mill Elementary School 2 Building 2010 Exterior EIFS Exterior Replacement (Bldg SF) Old, Moisture, Water Damage D Deficiency supports new CIP project
All Athletic Flooring - Bubbling And Cracked
Browns Mill Elementary School 3 Building 2020 Interior Athletic Sport Flooring Replacement D Deficiency supports new CIP project
In Many Parts
Browns Mill Elementary School 3 Site Asphalt Driveway Replacement Damaged D Deficiency supports new CIP project
73 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Canby Lane Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
Canby Lane Elementary School 2 Building 2011 Electrical Electrical Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
Canby Lane Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement Beyond Useful Life D Deficiency supports new CIP project
Canby Lane Elementary School 3 Building 2011 Electrical Interior Power Wiring Replacement D Deficiency supports new CIP project
Canby Lane Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Canby Lane Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Canby Lane Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Canby Lane Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Canby Lane Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Canby Lane Elementary School 2 Building 2011 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Canby Lane Elementary School 2 Building 2011 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Canby Lane Elementary School 2 Building 2010 Mechanical Air Cooled Condenser Replacement Beyond Useful Life D Deficiency supports new CIP project
Canby Lane Elementary School 2 Building 2010 Mechanical Ductless Split System AC Replacement Beyond Useful Life D Deficiency supports new CIP project
Canby Lane Elementary School 2 Building 2020 Mechanical Ductwork Replacement (SF Basis) D Deficiency supports new CIP project
Canby Lane Elementary School 2 Building 2010 Mechanical Gas Piping Replacement (SF Basis) Beyond Useful Life D Deficiency supports new CIP project
Canby Lane Elementary School 2 Building 2011 Mechanical Gas Piping Replacement (SF Basis) D Deficiency supports new CIP project
Canby Lane Elementary School 3 Building 2010 Mechanical Large Diameter Exhausts/Hoods Replacement Beyond Useful Life D Deficiency supports new CIP project
Canby Lane Elementary School 2 Building 2010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Beyond Useful Life D Deficiency supports new CIP project
Canby Lane Elementary School 2 Building 2011 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Beyond Useful Life D Deficiency supports new CIP project
Canby Lane Elementary School 2 Building 2030 Mechanical Thru Wall AC Replacement Beyond Useful Life D Deficiency supports new CIP project
Canby Lane Elementary School 3 Building 2010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life D Deficiency supports new CIP project
Canby Lane Elementary School 3 Building 2011 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life D Deficiency supports new CIP project
Canby Lane Elementary School 3 Building 2010 Plumbing Sanitary Sewer Piping Replacement D Deficiency supports new CIP project
Canby Lane Elementary School 3 Building 2011 Plumbing Sanitary Sewer Piping Replacement D Deficiency supports new CIP project
Canby Lane Elementary School 2 Building 2030 Plumbing Water Heater Replacement Beyond Useful Life D Deficiency supports new CIP project
Canby Lane Elementary School 2 Building 2030 Roofing Metal Roof Architectural Roof Covering Replacement Possible Signs Of Roof Leaks D Deficiency supports new CIP project
Roofing Over Cafeteria Was Not Replaced
With The Rest Of The Roofing. Roof Step
Canby Lane Elementary School 2 Building 2010 Roofing Modified Roof Covering Replacement Down From Cafeteria To Corridor Presents D Deficiency supports new CIP project
Several Roof Leaks At Joints (Metal Flashing
And Roof Overhang And Gutter Connection)
Beyond Useful Life - Water Damaged Ceiling
Canby Lane Elementary School 2 Building 2020 Roofing Modified Roof Covering Replacement D Deficiency supports new CIP project
And Flooring Due To Roofing Failure
Canby Lane Elementary School 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Water Ponding Issues. D Deficiency supports new CIP project
Canby Lane Elementary School 3 Building 2020 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Water Ponding Issue D Deficiency supports new CIP project
Canby Lane Elementary School 3 Site Concrete Walks Replacement Cracked D Deficiency supports new CIP project
Cedar Grove Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Old D Deficiency supports new CIP project
Cedar Grove Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Old D Deficiency supports new CIP project
Cedar Grove Elementary School 2 Building 2011 Electrical Electrical Transformer Replacement Old D Deficiency supports new CIP project
Cedar Grove Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement Old D Deficiency supports new CIP project
Cedar Grove Elementary School 3 Building 2011 Electrical Interior Power Wiring Replacement Old D Deficiency supports new CIP project
Cedar Grove Elementary School 2 Building 2010 Electrical Panelboard Replacement Old D Deficiency supports new CIP project
Cedar Grove Elementary School 2 Building 2010 Electrical Panelboard Replacement Old D Deficiency supports new CIP project
Cedar Grove Elementary School 2 Building 2010 Electrical Panelboard Replacement Old D Deficiency supports new CIP project
Cedar Grove Elementary School 2 Building 2010 Electrical Panelboard Replacement Old D Deficiency supports new CIP project
Cedar Grove Elementary School 2 Building 2011 Electrical Panelboard Replacement Old D Deficiency supports new CIP project
Cedar Grove Elementary School 2 Building 2011 Electrical Panelboard Replacement Old D Deficiency supports new CIP project
Cedar Grove Elementary School 2 Building 2011 Electrical Panelboard Replacement Old D Deficiency supports new CIP project
Cedar Grove Elementary School 2 Building 2012 Electrical Panelboard Replacement D Deficiency supports new CIP project
Cedar Grove Elementary School 2 Building 2012 Electrical Panelboard Replacement D Deficiency supports new CIP project
Cedar Grove Elementary School 2 Building 2012 Electrical Panelboard Replacement D Deficiency supports new CIP project
Cedar Grove Elementary School 2 Building 2010 Electrical Switchgear Replacement 1000 Amps. Old D Deficiency supports new CIP project
Cedar Grove Elementary School 2 Building 2010 Mechanical Gas Piping Replacement (SF Basis) D Deficiency supports new CIP project
Cedar Grove Elementary School 3 Building 2010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life D Deficiency supports new CIP project
Cedar Grove Elementary School 3 Building 2011 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life D Deficiency supports new CIP project
Cedar Grove Elementary School 3 Site Asphalt Driveway Replacement D Deficiency supports new CIP project
Cedar Grove Elementary School 3 Site Asphalt Walks Replacement Crumbling D Deficiency supports new CIP project
Cedar Grove Elementary School 3 Site Concrete Walks Replacement Cracked And Crumbling D Deficiency supports new CIP project
74 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Gym Down Spouts Dump Water At Rear
Cedar Grove Elementary School 3 Site Site Requires Civil/Drainage Study D Deficiency supports new CIP project
Playground And Causing Water Ponding
Cedar Grove High School 2 Building 5010 Electrical Distribution Panel Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5012 Electrical Distribution Panel Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5010 Electrical Electrical Transformer Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5010 Electrical Electrical Transformer Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5010 Electrical Electrical Transformer Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5011 Electrical Electrical Transformer Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5011 Electrical Electrical Transformer Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5012 Electrical Electrical Transformer Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5012 Electrical Electrical Transformer Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 3 Building 5010 Electrical Interior Power Wiring Replacement All Wiring Is Original To Building And Aged D Deficiency supports new CIP project
Cedar Grove High School 3 Building 5011 Electrical Interior Power Wiring Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5010 Electrical Panelboard Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5010 Electrical Panelboard Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5010 Electrical Panelboard Replacement Aged And Obsolete. D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5010 Electrical Panelboard Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5010 Electrical Panelboard Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5010 Electrical Panelboard Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5010 Electrical Panelboard Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5010 Electrical Panelboard Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5011 Electrical Panelboard Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5011 Electrical Panelboard Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5011 Electrical Panelboard Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5012 Electrical Panelboard Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5012 Electrical Panelboard Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5012 Electrical Panelboard Replacement Aged And Obsolete D Deficiency supports new CIP project
Cedar Grove High School 2 Building 5012 Electrical Panelboard Replacement Aged And Obsolete D Deficiency supports new CIP project
Roof Is Extensively Blistered Throughout To
Cedar Grove High School 2 Building 5012 Roofing Modified Roof Covering Replacement The Extent That Blisters Are Too Numerous D Deficiency supports new CIP project
To Count.
Cedar Grove Middle School 2 Building 4010 Electrical Motor Control Center Replacement Old D Deficiency supports new CIP project
Cedar Grove Middle School 3 Building 4010 Interior Athletic Sport Flooring Replacement Beyond Useful Life - Shrunk D Deficiency supports new CIP project
Cedar Grove Middle School 2 Building 4010 Mechanical Air Cooled Condenser Replacement D Deficiency supports new CIP project
Cedar Grove Middle School 2 Building 4010 Mechanical Air Cooled Condenser Replacement 1 Ton D Deficiency supports new CIP project
Cedar Grove Middle School 2 Building 4010 Mechanical Boiler Replacement D Deficiency supports new CIP project
Cedar Grove Middle School 3 Building 4010 Mechanical Circulation Pump Replacement D Deficiency supports new CIP project
Cedar Grove Middle School 3 Building 4010 Mechanical Circulation Pump Replacement D Deficiency supports new CIP project
Cedar Grove Middle School 2 Building 4010 Mechanical Ductless Split System AC Replacement D Deficiency supports new CIP project
Cedar Grove Middle School 2 Building 4010 Mechanical Ductless Split System AC Replacement D Deficiency supports new CIP project
Cedar Grove Middle School 2 Building 4010 Mechanical Electric Unit Heater Replacement D Deficiency supports new CIP project
Cedar Grove Middle School 2 Building 4010 Mechanical Electric Unit Heater Replacement D Deficiency supports new CIP project
Cedar Grove Middle School 3 Building 4010 Mechanical Energy Recovery Unit Replacement D Deficiency supports new CIP project
Cedar Grove Middle School 3 Building 4010 Mechanical Expansion Tank Replacement 100 Gallon Tank, Replace 1 D Deficiency supports new CIP project
Cedar Grove Middle School 2 Building 4010 Mechanical Exterior Metal Cooling Tower Replacement D Deficiency supports new CIP project
Cedar Grove Middle School 2 Building 4010 Mechanical Heat Exchanger Replacement D Deficiency supports new CIP project
Cedar Grove Middle School 2 Building 4010 Mechanical Heat Pump HVAC Component Replacement D Deficiency supports new CIP project
Cedar Grove Middle School 2 Building 4010 Mechanical Heat Pump HVAC Component Replacement D Deficiency supports new CIP project
Cedar Grove Middle School 2 Building 4010 Mechanical Heat Pump HVAC Component Replacement D Deficiency supports new CIP project
Cedar Grove Middle School 2 Building 4010 Mechanical Heat Pump HVAC Component Replacement D Deficiency supports new CIP project
Cedar Grove Middle School 2 Building 4010 Mechanical Heat Pump HVAC Component Replacement D Deficiency supports new CIP project
Cedar Grove Middle School 2 Building 4010 Mechanical Heat Pump HVAC Component Replacement D Deficiency supports new CIP project
Cedar Grove Middle School 3 Building 4010 Mechanical Large Diameter Exhausts/Hoods Replacement D Deficiency supports new CIP project
Roof Top Unit Over Admin Area: The Rtu's
Cedar Grove Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement D Deficiency supports new CIP project
Access Panel Is Not Installed - 4 Ton
Cedar Grove Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement D Deficiency supports new CIP project
Cedar Grove Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement D Deficiency supports new CIP project
Cedar Grove Middle School 3 Building 4010 Mechanical Testing And Balancing D Deficiency supports new CIP project
Cedar Grove Middle School 3 Building 4010 Plumbing Gas Water Heater Replacement D Deficiency supports new CIP project
75 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Cedar Grove Middle School 2 Building 4010 Plumbing Water Heater Replacement D Deficiency supports new CIP project
Cedar Grove Middle School 2 Building 4010 Plumbing Water Heater Replacement D Deficiency supports new CIP project
Cedar Grove Middle School 2 Building 4010 Plumbing Water Heater Replacement D Deficiency supports new CIP project
Cedar Grove Middle School 3 Site Asphalt Driveway Replacement Resurface, Rather Than Replace; Cracked D Deficiency supports new CIP project
Chamblee Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement Beyond Useful Life - Rtu 5 D Deficiency supports new CIP project
Chamblee Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement Beyond Useful Life - Roof Rtu 1 And 3 D Deficiency supports new CIP project
Chamblee Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement Beyond Useful Life - Rtu 6 And 7 D Deficiency supports new CIP project
Chamblee Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement Beyond Useful Life - Rtu 2 And 4 D Deficiency supports new CIP project
Chamblee Middle School 3 Building 4010 Mechanical Testing And Balancing D Deficiency supports new CIP project
Chamblee Middle School 3 Site Asphalt Driveway Replacement Repair Potholes At Front Of School. D Deficiency supports new CIP project
Chapel Hill Elementary School 2 Building 2010 Mechanical Air Cooled Condenser Replacement Roof D Deficiency supports new CIP project
Chapel Hill Elementary School 2 Building 2010 Mechanical Boiler Replacement Mech Room D Deficiency supports new CIP project
Chapel Hill Elementary School 2 Building 2010 Mechanical Ductwork Replacement (SF Basis) Throughout D Deficiency supports new CIP project
Chapel Hill Elementary School 2 Building 2011 Mechanical Ductwork Replacement (SF Basis) Throughout D Deficiency supports new CIP project
Chapel Hill Elementary School 2 Building 2012 Mechanical Ductwork Replacement (SF Basis) Throughout D Deficiency supports new CIP project
Chapel Hill Elementary School 2 Building 2013 Mechanical Ductwork Replacement (SF Basis) Throughout D Deficiency supports new CIP project
Chapel Hill Elementary School 2 Building 2010 Mechanical Fan Coil (Chilled Water) HVAC Component Replacement Throughout D Deficiency supports new CIP project
Chapel Hill Elementary School 2 Building 2011 Mechanical Fan Coil (Chilled Water) HVAC Component Replacement Throughout D Deficiency supports new CIP project
Chapel Hill Elementary School 2 Building 2012 Mechanical Fan Coil (Chilled Water) HVAC Component Replacement Throughout D Deficiency supports new CIP project
Chapel Hill Elementary School 2 Building 2013 Mechanical Fan Coil (Chilled Water) HVAC Component Replacement Throughout D Deficiency supports new CIP project
Chapel Hill Elementary School 2 Building 2010 Mechanical Fan Coil Unit Replacement Stage Storage D Deficiency supports new CIP project
Chapel Hill Elementary School 2 Building 2010 Mechanical Fan Coil Unit Replacement Media Center D Deficiency supports new CIP project
Chapel Hill Elementary School 2 Building 2010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Throughout D Deficiency supports new CIP project
Chapel Hill Elementary School 2 Building 2011 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Throughout D Deficiency supports new CIP project
Chapel Hill Elementary School 2 Building 2012 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Throughout D Deficiency supports new CIP project
Chapel Hill Elementary School 2 Building 2013 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Throughout D Deficiency supports new CIP project
Chapel Hill Elementary School 2 Building 2011 Mechanical Package Roof Top Unit Replacement Roof D Deficiency supports new CIP project
Chapel Hill Elementary School 3 Building 2010 Mechanical Replace Water Cooled Condenser Roof D Deficiency supports new CIP project
Chapel Hill Elementary School 3 Building 2010 Mechanical Testing And Balancing Throughout D Deficiency supports new CIP project
Chapel Hill Elementary School 3 Building 2011 Mechanical Testing And Balancing Throughout D Deficiency supports new CIP project
Chapel Hill Elementary School 3 Building 2012 Mechanical Testing And Balancing Throughout D Deficiency supports new CIP project
Chapel Hill Elementary School 3 Building 2013 Mechanical Testing And Balancing Throughout D Deficiency supports new CIP project
Chapel Hill Elementary School 2 Building 2011 Plumbing Water Heater Replacement Janitor Closet 117.3 D Deficiency supports new CIP project
Chapel Hill Elementary School 2 Building 2010 Roofing Built-up Roofing Replacement Beyond Useful Life D Deficiency supports new CIP project
Chapel Hill Elementary School 2 Building 2011 Roofing Built-up Roofing Replacement Beyond Useful Life D Deficiency supports new CIP project
Chapel Hill Elementary School 2 Building 2012 Roofing Built-up Roofing Replacement Beyond Useful Life D Deficiency supports new CIP project
Chapel Hill Elementary School 2 Building 2013 Roofing Built-up Roofing Replacement Beyond Useful Life D Deficiency supports new CIP project
Chapel Hill Elementary School 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding D Deficiency supports new CIP project
Chapel Hill Elementary School 3 Site Asphalt Driveway Replacement Beyond Useful Life D Deficiency supports new CIP project
Chapel Hill Elementary School 3 Site Asphalt Walks Replacement Beyond Useful Life D Deficiency supports new CIP project
Chapel Hill Middle School 2 Building 4010 Exterior EIFS Exterior Replacement (Bldg SF) Beyond Useful Life - Cracked D Deficiency supports new CIP project
Chapel Hill Middle School 3 Building 4010 Plumbing Toilet Replacement Throughout D Deficiency supports new CIP project
Chapel Hill Middle School 2 Building 4010 Plumbing Water Heater Replacement Concession 301.1 D Deficiency supports new CIP project
Chapel Hill Middle School 3 Building 4010 Plumbing Water Storage Tank Replacement Mech Room 98.14 D Deficiency supports new CIP project
Chapel Hill Middle School 3 Site Asphalt Driveway Replacement Beyond Useful Life - Cracked D Deficiency supports new CIP project
Chapel Hill Middle School 3 Site Concrete Walks Replacement Cracked D Deficiency supports new CIP project
Chesnut Elementary School 3 Site Asphalt Walks Replacement Cracked Asphalt D Deficiency supports new CIP project
Chesnut Elementary School 3 Site Concrete Walks Replacement Cracked Sidewalk D Deficiency supports new CIP project
Clarkston High School 3 Building 5012 Electrical Mounted Building Lighting Installation Not Existing D Deficiency supports new CIP project
Clarkston High School 2 Building 5013 Mechanical Electric Unit Heater Replacement Damaged D Deficiency supports new CIP project
Clarkston High School 2 Building 5012 Roofing Modified Roof Covering Replacement D Deficiency supports new CIP project
Ponding Due To Lack Of Drains And Roof
Clarkston High School 3 Building 5012 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing D Deficiency supports new CIP project
Tapering
Clarkston High School 3 Site Concrete Walks Replacement Damaged D Deficiency supports new CIP project
Columbia High School 2 Building 5010 Electrical Electrical Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5010 Electrical Electrical Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5011 Electrical Electrical Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5011 Electrical Electrical Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5011 Electrical Electrical Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5012 Electrical Electrical Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
76 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Columbia High School 2 Building 5010 Electrical Generator Replacement Beyond Useful Life - Actual 80KW D Deficiency supports new CIP project
Columbia High School 3 Building 5010 Electrical Interior Power Wiring Replacement Very Old Wiring D Deficiency supports new CIP project
Columbia High School 3 Building 5011 Electrical Interior Power Wiring Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 3 Building 5013 Electrical Interior Power Wiring Replacement Old Wiring D Deficiency supports new CIP project
Columbia High School 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life - Actual 277 And 480 125A D Deficiency supports new CIP project
Columbia High School 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life - Actual 120 And 208 300A D Deficiency supports new CIP project
Columbia High School 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5011 Electrical Panelboard Replacement Beyond Useful Life - Actual 120 And 208 30A D Deficiency supports new CIP project
Columbia High School 2 Building 5011 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5011 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5011 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5011 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5012 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5012 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5012 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5013 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5013 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5011 Electrical Switchgear Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 3 Building 5011 Electrical Transfer Switch Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5011 Mechanical Boiler Replacement Beyond Useful Life - Actual 1750 Mbh D Deficiency supports new CIP project
Columbia High School 2 Building 5011 Mechanical Ductwork Replacement (SF Basis) D Deficiency supports new CIP project
Columbia High School 2 Building 5010 Mechanical Gas Piping Replacement (SF Basis) Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5011 Mechanical Gas Piping Replacement (SF Basis) Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5012 Mechanical Gas Piping Replacement (SF Basis) Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 2 Building 5013 Mechanical Gas Piping Replacement (SF Basis) Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 3 Building 5010 Mechanical Testing And Balancing D Deficiency supports new CIP project
Columbia High School 3 Building 5012 Mechanical Testing And Balancing D Deficiency supports new CIP project
Columbia High School 3 Building 5013 Mechanical Testing And Balancing D Deficiency supports new CIP project
Columbia High School 3 Building 5010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Useful Life
Beyond D Deficiency supports new CIP project
Columbia High School 3 Building 5011 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Useful Life
Beyond D Deficiency supports new CIP project
Columbia High School 3 Building 5012 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Useful Life
Beyond D Deficiency supports new CIP project
Columbia High School 3 Building 5013 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Useful Life
Beyond D Deficiency supports new CIP project
Columbia High School 3 Building 5010 Plumbing Sanitary Sewer Piping Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 3 Building 5011 Plumbing Sanitary Sewer Piping Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 3 Building 5012 Plumbing Sanitary Sewer Piping Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia High School 3 Building 5013 Plumbing Sanitary Sewer Piping Replacement Beyond Useful Life D Deficiency supports new CIP project
Beyond Useful Life - Ponding Issues And
Columbia High School 2 Building 5010 Roofing Modified Roof Covering Replacement D Deficiency supports new CIP project
Leaks
Beyond Useful Life - 650 Sf Canopy Has Major
Columbia High School 2 Building 5011 Roofing Modified Roof Covering Replacement D Deficiency supports new CIP project
Ponding Issues
Columbia High School 2 Building 5012 Roofing Modified Roof Covering Replacement Water Ponding Issue D Deficiency supports new CIP project
Columbia High School 2 Building 5013 Roofing Modified Roof Covering Replacement Water Ponding Issues And Leaks D Deficiency supports new CIP project
Columbia High School 3 Site Concrete Walks Replacement Cracked D Deficiency supports new CIP project
Columbia Middle School 2 Building 4010 Mechanical Boiler Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia Middle School 3 Building 4010 Mechanical Circulation Pump Replacement Beyond Useful Life - 30HP D Deficiency supports new CIP project
Columbia Middle School 3 Building 4010 Mechanical Circulation Pump Replacement Beyond Useful Life - 15HP D Deficiency supports new CIP project
Columbia Middle School 2 Building 4010 Mechanical Exterior Metal Cooling Tower Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia Middle School 2 Building 4010 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia Middle School 2 Building 4010 Mechanical Heat Pump HVAC Component Replacement D Deficiency supports new CIP project
Columbia Middle School 2 Building 4010 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia Middle School 2 Building 4010 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life D Deficiency supports new CIP project
Columbia Middle School 3 Building 4010 Mechanical Large Diameter Exhausts/Hoods Replacement D Deficiency supports new CIP project
Columbia Middle School 3 Building 4010 Mechanical Make Up Air Equipment Replacement D Deficiency supports new CIP project
77 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Columbia Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement D Deficiency supports new CIP project
Columbia Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement D Deficiency supports new CIP project
Columbia Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement 7.5 Ton D Deficiency supports new CIP project
Columbia Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement D Deficiency supports new CIP project
Columbia Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement 6 Ton D Deficiency supports new CIP project
Columbia Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement (2) 1.5 Ton, (1) 3 Ton, (2) 4 Ton D Deficiency supports new CIP project
Columbia Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement 30 Ton D Deficiency supports new CIP project
Columbia Middle School 2 Building 4010 Mechanical Steam Condensate Receiver Replacement D Deficiency supports new CIP project
Columbia Middle School 3 Building 4010 Mechanical Testing And Balancing D Deficiency supports new CIP project
Columbia Middle School 3 Building 4010 Plumbing Gas Water Heater Replacement D Deficiency supports new CIP project
Columbia Middle School 2 Building 4010 Plumbing Water Heater Replacement D Deficiency supports new CIP project
Columbia Middle School 2 Building 4010 Plumbing Water Heater Replacement D Deficiency supports new CIP project
Columbia Middle School 2 Building 4010 Plumbing Water Heater Replacement D Deficiency supports new CIP project
Columbia Middle School 2 Building 4010 Plumbing Water Heater Replacement D Deficiency supports new CIP project
Columbia Middle School 3 Site Concrete Walks Replacement D Deficiency supports new CIP project
Coralwood Education 3 Building 2010 Mechanical Testing And Balancing D Deficiency supports new CIP project
Coralwood Education 3 Building 2011 Mechanical Testing And Balancing D Deficiency supports new CIP project
DeKalb High of Technology, South Campus 3 Site Concrete Walks Replacement Cracked And Spalling D Deficiency supports new CIP project
Doraville Administrative 3 Building 8010 Electrical Power Service Upgrade Only Two (2) Panels In The Building D Deficiency supports new CIP project
Doraville Administrative 2 Building 8010 Mechanical Electric Unit Heater Replacement Beyond Useful Life D Deficiency supports new CIP project
Doraville Administrative 2 Building 8010 Mechanical Thru Wall AC Replacement Beyond Useful Life D Deficiency supports new CIP project
Doraville Administrative 3 Building 8010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Useful Life
Beyond D Deficiency supports new CIP project
Doraville Administrative 3 Building 8010 Plumbing Sanitary Sewer Piping Replacement Beyond Useful Life D Deficiency supports new CIP project
Druid Hills Middle School 3 Site Concrete Walks Replacement D Deficiency supports new CIP project
Dunaire Elementary School 2 Building 2012 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Dunaire Elementary School 3 Building 2011 Exterior Brick Exterior Repointing Cracked, Weathered D Deficiency supports new CIP project
Dunaire Elementary School 2 Building 2011 Mechanical Ductwork Replacement (SF Basis) Beyond Useful Life D Deficiency supports new CIP project
Dunaire Elementary School 2 Building 2020 Mechanical Gas Unit Heater Replacement Beyond Useful Life D Deficiency supports new CIP project
Dunaire Elementary School 2 Building 2011 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life D Deficiency supports new CIP project
Dunaire Elementary School 2 Building 2012 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life D Deficiency supports new CIP project
Dunaire Elementary School 3 Building 2011 Mechanical Large Diameter Exhausts/Hoods Replacement Beyond Useful Life D Deficiency supports new CIP project
Dunaire Elementary School 3 Building 2012 Mechanical Large Diameter Exhausts/Hoods Replacement Beyond Useful Life D Deficiency supports new CIP project
Dunaire Elementary School 2 Building 2011 Mechanical Package Roof Top Unit Repair D Deficiency supports new CIP project
Dunaire Elementary School 2 Building 2011 Mechanical Package Roof Top Unit Replacement Beyond Useful Life D Deficiency supports new CIP project
Dunaire Elementary School 2 Building 2012 Mechanical Package Roof Top Unit Replacement Beyond Useful Life D Deficiency supports new CIP project
Dunaire Elementary School 2 Building 2012 Mechanical Package Roof Top Unit Replacement Beyond Useful Life D Deficiency supports new CIP project
Dunaire Elementary School 2 Building 2012 Mechanical Thru Wall AC Replacement Beyond Useful Life D Deficiency supports new CIP project
Dunaire Elementary School 3 Building 2010 Plumbing Gas Water Heater Replacement Beyond Useful Life D Deficiency supports new CIP project
Dunaire Elementary School 3 Building 2020 Plumbing Gas Water Heater Replacement Missing D Deficiency supports new CIP project
Dunaire Elementary School 3 Building 2011 Plumbing Sanitary Sewer Piping Replacement Beyond Useful Life D Deficiency supports new CIP project
Dunaire Elementary School 3 Building 2010 Plumbing Toilet Replacement Beyond Useful Life D Deficiency supports new CIP project
Dunaire Elementary School 3 Building 2011 Plumbing Toilet Replacement Beyond Useful Life D Deficiency supports new CIP project
Dunaire Elementary School 3 Building 2012 Plumbing Toilet Replacement Beyond Useful Life D Deficiency supports new CIP project
Dunaire Elementary School 3 Building 2020 Plumbing Toilet Replacement Beyond Useful Life D Deficiency supports new CIP project
Dunaire Elementary School 3 Building 2010 Plumbing Urinal Replacement Beyond Useful Life D Deficiency supports new CIP project
Dunaire Elementary School 3 Building 2011 Plumbing Urinal Replacement Beyond Useful Life D Deficiency supports new CIP project
Dunaire Elementary School 2 Building 2010 Plumbing Water Heater Replacement Beyond Useful Life D Deficiency supports new CIP project
Dunaire Elementary School 2 Building 2011 Plumbing Water Heater Replacement Beyond Useful Life D Deficiency supports new CIP project
Dunaire Elementary School 2 Building 2012 Plumbing Water Heater Replacement Beyond Useful Life D Deficiency supports new CIP project
Dunwoody High School 2 Building 5011 Electrical Distribution Panel Replacement Aged And Obsolete. D Deficiency supports new CIP project
Dunwoody High School 2 Building 5011 Electrical Electrical Transformer Replacement Aged And Obsolete. D Deficiency supports new CIP project
Dunwoody High School 2 Building 5010 Electrical Panelboard Replacement Aged And Obsolete. D Deficiency supports new CIP project
Dunwoody High School 2 Building 5010 Electrical Panelboard Replacement Aged And Obsolete. D Deficiency supports new CIP project
Panel L Is Broken. Replace. Additionally
Dunwoody High School 2 Building 5011 Electrical Panelboard Replacement D Deficiency supports new CIP project
Replace Kitchen Panel.
Dunwoody High School 2 Building 5011 Electrical Panelboard Replacement Aged And Obsolete. D Deficiency supports new CIP project
Dunwoody High School 2 Building 5011 Mechanical Ductless Split System AC Replacement Aged And Obsolete. D Deficiency supports new CIP project
Dunwoody High School 2 Building 5012 Mechanical Ductless Split System AC Replacement Aged And Obsolete. D Deficiency supports new CIP project
Package Unit For Gym Is At The Beyond
Dunwoody High School 2 Building 5012 Mechanical Package DX Unit Replacement D Deficiency supports new CIP project
Useful Life
78 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Showers Are Aged And Beyond Useful Life.
Dunwoody High School 3 Building 5010 Plumbing Shower Replacement D Deficiency supports new CIP project
Replace
Showers Are Aged And Beyond Useful Life.
Dunwoody High School 3 Building 5012 Plumbing Shower Replacement D Deficiency supports new CIP project
Replace
Dunwoody High School 2 Building 5013 Plumbing Water Heater Replacement D Deficiency supports new CIP project
Eagle Woods Academy 3 Building 8030 Electrical Interior Power Wiring Replacement D Deficiency supports new CIP project
Eagle Woods Academy 3 Building 8030 Electrical Mounted Building Lighting Installation D Deficiency supports new CIP project
Eagle Woods Academy 2 Building 8010 Electrical Panelboard Replacement Replace, Old D Deficiency supports new CIP project
Eagle Woods Academy 2 Building 8030 Electrical Panelboard Replacement Inside 8030 Old D Deficiency supports new CIP project
Eagle Woods Academy 3 Building 8030 Exterior Wood Window Repair Old, Deficient. Boarded Up. Replace. D Deficiency supports new CIP project
Early Learning Academy 3 Building 2012 Plumbing Restroom Group Wash Fountain Replacement Beyond Useful Life D Deficiency supports new CIP project
East Campus #1 DeKalb Alternative 2 Building 8010 Electrical Panelboard Replacement D Deficiency supports new CIP project
East Campus #1 DeKalb Alternative 2 Building 8010 Electrical Panelboard Replacement D Deficiency supports new CIP project
East Campus #1 DeKalb Alternative 3 Building 8010 Mechanical Testing And Balancing D Deficiency supports new CIP project
East Campus #1 DeKalb Alternative 3 Building 8020 Mechanical Testing And Balancing D Deficiency supports new CIP project
East Campus #1 DeKalb Alternative 3 Building 8010 Plumbing Gas Water Heater Replacement D Deficiency supports new CIP project
East Campus #2 Transportation 2 Building 8020 Exterior Composite Exterior Siding Replacement (Bldg SF) D Deficiency supports new CIP project
East Campus #2 Transportation 2 Building 8010 Mechanical Air Cooled Condenser Replacement Roof Serves Data Room D Deficiency supports new CIP project
East Campus #2 Transportation 2 Building 8010 Mechanical Ductless Split System AC Replacement D Deficiency supports new CIP project
Ductwork Was Installed In 1979 Has Been
East Campus #2 Transportation 2 Building 8010 Mechanical Ductwork Replacement (SF Basis) D Deficiency supports new CIP project
Maintained But Beyond Useful Life
East Campus #2 Transportation 2 Building 8010 Mechanical Steam Condensate Receiver Replacement 1.6 Gallons - Data Room D Deficiency supports new CIP project
East Campus #2 Transportation 3 Building 8010 Mechanical Testing And Balancing D Deficiency supports new CIP project
East Campus #2 Transportation 2 Building 8020 Roofing Asphalt Shingle Roof Covering Replacement D Deficiency supports new CIP project
East Campus #2 Transportation 2 Building 8030 Roofing Asphalt Shingle Roof Covering Replacement D Deficiency supports new CIP project
East Campus #2 Transportation 3 Site Asphalt Driveway Replacement East Driveway D Deficiency supports new CIP project
East Campus #2 Transportation 3 Site Concrete Walks Replacement D Deficiency supports new CIP project
Teacher's Lounge Power Wiring Needs
Edward L. Bouie, Sr. Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement D Deficiency supports new CIP project
Replacement.
Install 3 Exterior Building Mounted Lights,
Edward L. Bouie, Sr. Elementary School 3 Building 2010 Electrical Mounted Building Lighting Installation One On Each Side Of The Gym (Back And 2 D Deficiency supports new CIP project
Sides, Not Front)
Evansdale Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
Evansdale Elementary School 2 Building 2020 Electrical Electrical Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
Evansdale Elementary School 2 Building 2010 Mechanical Electric Unit Heater Replacement Beyond Useful Life D Deficiency supports new CIP project
Evansdale Elementary School 2 Building 2020 Mechanical Gas Unit Heater Replacement Beyond Useful Life D Deficiency supports new CIP project
Evansdale Elementary School 3 Building 2020 Roofing Batt Insulation Under Metal Roof Deck Ripped And Damaged D Deficiency supports new CIP project
Fernbank Science Center 2 Building 8010 Mechanical Air Cooled Condenser Replacement Aerospace - 209 D Deficiency supports new CIP project
Fernbank Science Center 2 Building 8010 Mechanical Air Cooled Condenser Replacement D Deficiency supports new CIP project
Fernbank Science Center 2 Building 8010 Mechanical Air Handler HVAC Component Replacement Mech Room D Deficiency supports new CIP project
Fernbank Science Center 2 Building 8010 Mechanical Air Handler HVAC Component Replacement Mech Room D Deficiency supports new CIP project
Fernbank Science Center 2 Building 8010 Mechanical Air Handler HVAC Component Replacement Mech Room D Deficiency supports new CIP project
Fernbank Science Center 2 Building 8010 Mechanical Boiler Replacement Boiler Room D Deficiency supports new CIP project
Fernbank Science Center 2 Building 8010 Mechanical Fan Coil Unit Replacement Aerospace - 209 D Deficiency supports new CIP project
Fernbank Science Center 2 Building 8010 Mechanical Fan Coil Unit Replacement Aerospace - 209 D Deficiency supports new CIP project
Fernbank Science Center 2 Building 8010 Mechanical Mechanical / HVAC Piping / System Is Beyond Its Useful Life Boiler And Mech Room D Deficiency supports new CIP project
Fernbank Science Center 3 Building 8010 Mechanical Testing And Balancing Entire Building D Deficiency supports new CIP project
Fernbank Science Center 2 Building 8020 Roofing Asphalt Shingle Roof Covering Replacement Hole On The Roof D Deficiency supports new CIP project
Replace Roof Asap Because The Entire Roof Is
Fernbank Science Center 2 Building 8010 Roofing Modified Roof Covering Replacement D Deficiency supports new CIP project
Falling Apart On The Observatory.
Fernbank Science Center 3 Site Asphalt Walks Replacement Cracked And Damaged D Deficiency supports new CIP project
Fernbank Science Center 3 Site Concrete Walks Replacement Cracked And Damaged D Deficiency supports new CIP project
Flat Rock Elementary School 3 Site Asphalt Driveway Replacement Cracked D Deficiency supports new CIP project
Flat Shoals Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement Beyond Useful Life D Deficiency supports new CIP project
Flat Shoals Elementary School 2 Building 2020 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life D Deficiency supports new CIP project
Flat Shoals Elementary School 2 Building 2030 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life D Deficiency supports new CIP project
Flat Shoals Elementary School 3 Building 2010 Mechanical Testing And Balancing D Deficiency supports new CIP project
Flat Shoals Elementary School 3 Building 2011 Mechanical Testing And Balancing D Deficiency supports new CIP project
Flat Shoals Elementary School 3 Building 2040 Mechanical Testing And Balancing D Deficiency supports new CIP project
79 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Freedom Middle School 2 Building 4010 Mechanical Package DX Unit Replacement Beyond Useful Life 25 Ton D Deficiency supports new CIP project
Freedom Middle School 2 Building 4010 Mechanical Package DX Unit Replacement Beyond Useful Life D Deficiency supports new CIP project
Freedom Middle School 3 Site Asphalt Driveway Replacement Cracked And Potholes D Deficiency supports new CIP project
Sidewalks Cracked At Various Locations.
Freedom Middle School 3 Site Concrete Walks Replacement Repair Or Replace Cracked Curb At Front D Deficiency supports new CIP project
Entrance Of Building
Beyond Useful Life - Concessions And
Hallford, James R. Stadium 2 Building 8010 Mechanical Electric Unit Heater Replacement D Deficiency supports new CIP project
Restrooms
Hallford, James R. Stadium 2 Building 8010 Plumbing Water Heater Replacement Beyond Useful Life - West Concession D Deficiency supports new CIP project
Concrete Driveway North Of Stadium Cracked
Hallford, James R. Stadium 3 Site Concrete Driveways Replacement D Deficiency supports new CIP project
In 2 Areas. Replace
Concrete Sidewalks At East Parking Lot Have
Hallford, James R. Stadium 3 Site Concrete Walks Replacement D Deficiency supports new CIP project
Several Cracked Segments. Replace.
Hambrick Elementary School 3 Site Asphalt Walks Replacement Beyond Useful Life Cracked D Deficiency supports new CIP project
Hambrick Elementary School 3 Site Concrete Walks Replacement Cracked D Deficiency supports new CIP project
Insufficient Exit Lighting - Install More Light
Hatton Dr Warehouse 3 Electrical Area Lighting Installation D Deficiency supports new CIP project
Poles.
Hatton Dr Warehouse 2 Building 8010 Electrical Panelboard Replacement Old, Elec Room D Deficiency supports new CIP project
Hatton Dr Warehouse 2 Building 8010 Electrical Panelboard Replacement Old, Replace Elec Room D Deficiency supports new CIP project
Hatton Dr Warehouse 2 Building 8010 Electrical Panelboard Replacement Old, Replace Workshop D Deficiency supports new CIP project
Hatton Dr Warehouse 3 Building 8010 Plumbing Shower Replacement Beyond Useful Life - No Plans D Deficiency supports new CIP project
Hatton Dr Warehouse 3 Building 8010 Plumbing Toilet Replacement Beyond Useful Life - No Plans D Deficiency supports new CIP project
Hatton Dr Warehouse 3 Building 8010 Plumbing Urinal Replacement Beyond Useful Life - No Plans D Deficiency supports new CIP project
Hatton Dr Warehouse 3 Site Asphalt Driveway Replacement Old, Deficient D Deficiency supports new CIP project
Hatton Dr Warehouse 3 Site Concrete Walks Replacement Cracked, Old. Replace. See ADA06 D Deficiency supports new CIP project
Not Visible, But Likely Needs Replacement
Hatton Dr Warehouse 2 Site Existing Sidewalk Is Cracked And Poses A Hazard To Accessibility D Deficiency supports new CIP project
Along North And East Sides
Henderson Middle School 3 Building 4011 Mechanical Testing And Balancing D Deficiency supports new CIP project
Henderson Middle School 3 Building 4012 Mechanical Testing And Balancing D Deficiency supports new CIP project
Henderson Middle School 3 Building 4013 Mechanical Testing And Balancing D Deficiency supports new CIP project
Henderson Middle School 3 Building 4014 Mechanical Testing And Balancing D Deficiency supports new CIP project
Huntley Hills Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Aged And Obsolete. D Deficiency supports new CIP project
Huntley Hills Elementary School 2 Building 2010 Electrical Panelboard Replacement Aged And Obsolete. D Deficiency supports new CIP project
Huntley Hills Elementary School 2 Building 2010 Electrical Panelboard Replacement Aged And Obsolete. D Deficiency supports new CIP project
Huntley Hills Elementary School 2 Building 2010 Electrical Panelboard Replacement Aged And Obsolete. D Deficiency supports new CIP project
Huntley Hills Elementary School 2 Building 2011 Electrical Panelboard Replacement Aged And Obsolete. D Deficiency supports new CIP project
Huntley Hills Elementary School 2 Building 2011 Electrical Panelboard Replacement Aged And Obsolete. D Deficiency supports new CIP project
Huntley Hills Elementary School 2 Building 2012 Electrical Panelboard Replacement Aged And Obsolete. D Deficiency supports new CIP project
Huntley Hills Elementary School 2 Building 2012 Electrical Panelboard Replacement Aged And Obsolete. D Deficiency supports new CIP project
Zones And Rooms Throughout The Building
Huntley Hills Elementary School 3 Building 2010 Mechanical Testing And Balancing Are Often Very Warm Or Cold. Perform Test D Deficiency supports new CIP project
And Balancing
Huntley Hills Elementary School 3 Building 2011 Mechanical Testing And Balancing D Deficiency supports new CIP project
Huntley Hills Elementary School 3 Building 2012 Mechanical Testing And Balancing D Deficiency supports new CIP project
Huntley Hills Elementary School 2 Building 2010 Mechanical Unit Ventilator Replacement D Deficiency supports new CIP project
Drives Are Deteriorated And Significant
Huntley Hills Elementary School 3 Site Asphalt Driveway Replacement D Deficiency supports new CIP project
Potholes Are Present
Kelley Lake Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
Kelley Lake Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Kelley Lake Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Kelley Lake Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Kelley Lake Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Kelley Lake Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Kelley Lake Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Kelley Lake Elementary School 2 Building 2011 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Kelley Lake Elementary School 3 Site Site Sanitary Sewer Piping Replacement D Deficiency supports new CIP project
Lakeside High School 2 Building 5010 Electrical Electrical Transformer Replacement Mech Room 1Q403 D Deficiency supports new CIP project
Lakeside High School 2 Building 5010 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
Lakeside High School 2 Building 5011 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
80 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Lakeside High School 3 Building 5011 Electrical Interior Power Wiring Replacement D Deficiency supports new CIP project
Lakeside High School 3 Building 5012 Electrical Interior Power Wiring Replacement D Deficiency supports new CIP project
Lakeside High School 3 Building 5013 Electrical Interior Power Wiring Replacement D Deficiency supports new CIP project
Lakeside High School 2 Building 5010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lakeside High School 2 Building 5010 Electrical Panelboard Replacement Mech Room 1403 D Deficiency supports new CIP project
Lakeside High School 2 Building 5010 Electrical Panelboard Replacement Mech Room 1403 D Deficiency supports new CIP project
Lakeside High School 2 Building 5011 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lakeside High School 2 Building 5011 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lakeside High School 2 Building 5013 Electrical Panelboard Replacement Pool D Deficiency supports new CIP project
Lakeside High School 2 Building 5013 Electrical Panelboard Replacement Pool D Deficiency supports new CIP project
Lakeside High School 2 Building 5013 Mechanical Cast Iron Water Boiler Replacement Mech Room D Deficiency supports new CIP project
Lakeside High School 2 Building 5010 Mechanical Ductless Split System AC Replacement 2300 Storage It And Data D Deficiency supports new CIP project
Lakeside High School 3 Building 5010 Mechanical Large Diameter Exhausts/Hoods Replacement Roof D Deficiency supports new CIP project
Lakeside High School 3 Building 5012 Mechanical Large Diameter Exhausts/Hoods Replacement Roof D Deficiency supports new CIP project
Lakeside High School 3 Building 5013 Mechanical Large Diameter Exhausts/Hoods Replacement Roof D Deficiency supports new CIP project
Lakeside High School 2 Building 5010 Mechanical Package Roof Top Unit Replacement Roof D Deficiency supports new CIP project
Lakeside High School 2 Building 5012 Mechanical Package Roof Top Unit Replacement Roof D Deficiency supports new CIP project
Lakeside High School 2 Building 5012 Roofing Modified Roof Covering Replacement Gable Roof D Deficiency supports new CIP project
Lakeside High School 3 Building 5010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing D Deficiency supports new CIP project
Lakeside High School 3 Building 5011 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing D Deficiency supports new CIP project
Lakeside High School 3 Building 5012 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Throughout D Deficiency supports new CIP project
Lakeside High School 3 Building 5014 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing D Deficiency supports new CIP project
Lakeside High School 3 Site Asphalt Driveway Replacement Front Driveway D Deficiency supports new CIP project
Lakeside High School 3 Site Concrete Walks Replacement Cracked Throughout D Deficiency supports new CIP project
Lithonia High School 3 Building 5020 Electrical Interior Power Wiring Replacement Bad Shape D Deficiency supports new CIP project
For Security; No Exterior Lighting On
Lithonia High School 3 Building 5020 Electrical Mounted Building Lighting Installation D Deficiency supports new CIP project
Concessions Building
Lithonia High School 2 Building 5020 Electrical Panelboard Replacement Bad Shape D Deficiency supports new CIP project
Lithonia High School 3 Building 5010 Interior Athletic Sport Flooring Replacement D Deficiency supports new CIP project
Lithonia High School 2 Building 5010 Mechanical Air Cooled Condenser Replacement D Deficiency supports new CIP project
Lithonia High School 2 Building 5010 Mechanical Ductless Split System AC Replacement D Deficiency supports new CIP project
Lithonia High School 3 Building 5010 Mechanical Energy Recovery Unit Replacement D Deficiency supports new CIP project
Lithonia High School 3 Building 5010 Mechanical Energy Recovery Unit Replacement D Deficiency supports new CIP project
Lithonia High School 3 Building 5010 Mechanical Energy Recovery Unit Replacement D Deficiency supports new CIP project
Lithonia High School 3 Building 5010 Mechanical Energy Recovery Unit Replacement D Deficiency supports new CIP project
Lithonia High School 3 Building 5010 Mechanical Energy Recovery Unit Replacement D Deficiency supports new CIP project
Lithonia High School 2 Building 5010 Mechanical Exterior Metal Cooling Tower Replacement D Deficiency supports new CIP project
Lithonia High School 2 Building 5010 Mechanical Heat Pump HVAC Component Replacement D Deficiency supports new CIP project
Lithonia High School 3 Building 5010 Mechanical Kitchen Exhaust Hood Replacement D Deficiency supports new CIP project
Lithonia High School 3 Building 5010 Mechanical Large Diameter Exhausts/Hoods Replacement D Deficiency supports new CIP project
Lithonia High School 2 Building 5010 Mechanical Package Roof Top Unit Replacement D Deficiency supports new CIP project
Lithonia High School 2 Building 5010 Mechanical Package Roof Top Unit Replacement D Deficiency supports new CIP project
Lithonia High School 2 Building 5010 Mechanical Package Roof Top Unit Replacement D Deficiency supports new CIP project
Lithonia High School 2 Building 5010 Mechanical Package Roof Top Unit Replacement D Deficiency supports new CIP project
Lithonia High School 2 Building 5010 Mechanical Package Roof Top Unit Replacement D Deficiency supports new CIP project
Lithonia High School 2 Building 5010 Mechanical Package Roof Top Unit Replacement D Deficiency supports new CIP project
Lithonia High School 2 Building 5010 Mechanical Package Roof Top Unit Replacement D Deficiency supports new CIP project
Lithonia High School 3 Building 5010 Mechanical Testing And Balancing D Deficiency supports new CIP project
Lithonia High School 2 Building 5010 Plumbing Water Heater Replacement D Deficiency supports new CIP project
Lithonia High School 3 Site Asphalt Driveway Replacement Damaged D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
Lithonia Middle School 3 Building 4010 Electrical Interior Power Wiring Replacement Old Wiring In Building D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
81 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Lithonia Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Lithonia Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Replace All Rooftops - Common Areas -
Lithonia Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement Cafeteria, Kitchen, Gym, Media Ctr, D Deficiency supports new CIP project
Administration Area.
Replace All Rooftops - Common Areas -
Lithonia Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement Cafeteria, Kitchen, Gym, Media Ctr, D Deficiency supports new CIP project
Administration Area.
Replace All Rooftops - Common Areas -
Lithonia Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement Cafeteria, Kitchen, Gym, Media Ctr, D Deficiency supports new CIP project
Administration Area.
Replace All Rooftops - Common Areas -
Lithonia Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement Cafeteria, Kitchen, Gym, Media Ctr, D Deficiency supports new CIP project
Administration Area.
Replace All Rooftops - Common Areas -
Lithonia Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement Cafeteria, Kitchen, Gym, Media Ctr, D Deficiency supports new CIP project
Administration Area.
Replace All Rooftops - Common Areas -
Lithonia Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement Cafeteria, Kitchen, Gym, Media Ctr, D Deficiency supports new CIP project
Administration Area.
Replace All Rooftops - Common Areas -
Lithonia Middle School 2 Building 4010 Mechanical Package Roof Top Unit Replacement Cafeteria, Kitchen, Gym, Media Ctr, D Deficiency supports new CIP project
Administration Area.
Lithonia Middle School 3 Building 4010 Mechanical Testing And Balancing D Deficiency supports new CIP project
Lithonia Middle School 3 Site Aluminum Covered Walkways Replacement Outside 905 And 533 D Deficiency supports new CIP project
Lithonia Middle School 3 Site Concrete Walks Replacement Behind Gym And Throughout D Deficiency supports new CIP project
Marbut Elementary School 3 Building 2010 Plumbing Gas Water Heater Replacement Beyond Useful Life D Deficiency supports new CIP project
Marbut Elementary School 3 Building 2020 Plumbing Gas Water Heater Replacement Beyond Useful Life D Deficiency supports new CIP project
Marbut Elementary School 3 Building 2010 Plumbing Toilet Replacement Beyond Useful Life D Deficiency supports new CIP project
Marbut Elementary School 3 Building 2020 Plumbing Toilet Replacement Beyond Useful Life D Deficiency supports new CIP project
Marbut Elementary School 3 Building 2010 Plumbing Urinal Replacement Beyond Useful Life D Deficiency supports new CIP project
Marbut Elementary School 2 Building 2010 Plumbing Water Heater Replacement Beyond Useful Life D Deficiency supports new CIP project
Marbut Elementary School 2 Building 2010 Plumbing Water Heater Replacement Beyond Useful Life D Deficiency supports new CIP project
Marbut Elementary School 2 Building 2010 Roofing Modified Roof Covering Replacement Beyond Useful Life - Installed 1995 D Deficiency supports new CIP project
Marbut Elementary School 3 Site Asphalt Driveway Replacement Cracked D Deficiency supports new CIP project
Marbut Elementary School 3 Site Concrete Walks Replacement Cracked Curbs D Deficiency supports new CIP project
Margaret Harris Comprehensive 2 Building 8010 Electrical Distribution Panel Replacement D Deficiency supports new CIP project
Margaret Harris Comprehensive 2 Building 8010 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
Margaret Harris Comprehensive 2 Building 8010 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
Margaret Harris Comprehensive 2 Building 8010 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
Margaret Harris Comprehensive 3 Building 8010 Electrical Interior Power Wiring Replacement D Deficiency supports new CIP project
Margaret Harris Comprehensive 2 Building 8010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Margaret Harris Comprehensive 2 Building 8010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Margaret Harris Comprehensive 2 Building 8010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Margaret Harris Comprehensive 2 Building 8010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Margaret Harris Comprehensive 2 Building 8010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Margaret Harris Comprehensive 2 Building 8010 Electrical Switchgear Replacement D Deficiency supports new CIP project
82 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Margaret Harris Comprehensive 2 Building 8010 Mechanical HVAC VAV Box Replacement D Deficiency supports new CIP project
Margaret Harris Comprehensive 3 Building 8010 Mechanical Testing And Balancing Beyond Useful Life D Deficiency supports new CIP project
Margaret Harris Comprehensive 3 Building 8011 Mechanical Testing And Balancing Beyond Useful Life D Deficiency supports new CIP project
Margaret Harris Comprehensive 3 Building 8012 Mechanical Testing And Balancing D Deficiency supports new CIP project
Margaret Harris Comprehensive 3 Building 8010 Plumbing Gas Water Heater Replacement Beyond Useful Life D Deficiency supports new CIP project
Margaret Harris Comprehensive 3 Site Concrete Walks Replacement Cracked And Front D Deficiency supports new CIP project
Martin Luther King, Jr. High School 3 Building 5011 Electrical Ground Mounted Lighting Installation Install Behind Room 164 D Deficiency supports new CIP project
Martin Luther King, Jr. High School 3 Building 5010 Electrical Interior Power Wiring Replacement Replace Power Wiring D Deficiency supports new CIP project
Martin Luther King, Jr. High School 3 Building 5010 Electrical Mounted Building Lighting Installation Install Lights Behind Building D Deficiency supports new CIP project
Install New Light In The Area Outside New
Martin Luther King, Jr. High School 3 Building 5011 Electrical Mounted Building Lighting Installation D Deficiency supports new CIP project
Dining Commons
Martin Luther King, Jr. High School 3 Building 5010 Interior Athletic Sport Flooring Replacement D Deficiency supports new CIP project
Martin Luther King, Jr. High School 3 Building 5010 Interior Rubber Flooring Replacement D Deficiency supports new CIP project
Repave Driveway Starting Directly North-
Martin Luther King, Jr. High School 3 Site Asphalt Driveway Replacement West Of Teams Courts, All The Way To South D Deficiency supports new CIP project
Parking Lot.
Martin Luther King, Jr. High School 3 Site Concrete Walks Replacement D Deficiency supports new CIP project
Mary McLeod Bethune Middle School 3 Building 4010 Mechanical Testing And Balancing D Deficiency supports new CIP project
Mary McLeod Bethune Middle School 2 Building 4010 Plumbing Water Heater Replacement D Deficiency supports new CIP project
McLendon Elementary School 3 Building 2012 Electrical Interior Power Wiring Replacement Original And Beyond Useful Life D Deficiency supports new CIP project
McLendon Elementary School 2 Building 2010 Electrical Panelboard Replacement Aged And Obsolete. D Deficiency supports new CIP project
McLendon Elementary School 2 Building 2010 Electrical Panelboard Replacement Aged And Obsolete. D Deficiency supports new CIP project
McLendon Elementary School 2 Building 2012 Electrical Panelboard Replacement Aged And Obsolete. D Deficiency supports new CIP project
McNair Elementary School 2 Building 2020 Mechanical Package Roof Top Unit Replacement D Deficiency supports new CIP project
McNair Elementary School 3 Building 2020 Mechanical Testing And Balancing D Deficiency supports new CIP project
McNair Elementary School 2 Building 2020 Mechanical Thru Wall AC Replacement D Deficiency supports new CIP project
McNair Elementary School 2 Building 2020 Plumbing Water Heater Replacement Beyond Useful Life D Deficiency supports new CIP project
McNair High School 2 Building 5010 Electrical Electrical Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
McNair High School 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
McNair High School 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
McNair High School 2 Building 5013 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
McNair High School 3 Building 5010 Interior Rubber Flooring Replacement Beyond Useful Life D Deficiency supports new CIP project
McNair High School 3 Building 5010 Mechanical Circulation Pump Replacement Beyond Useful Life D Deficiency supports new CIP project
McNair High School 3 Building 5010 Mechanical Circulation Pump Replacement Beyond Useful Life D Deficiency supports new CIP project
McNair High School 2 Building 5010 Mechanical Ductwork Replacement (SF Basis) Beyond Useful Life D Deficiency supports new CIP project
McNair High School 2 Building 5020 Mechanical Ductwork Replacement (SF Basis) D Deficiency supports new CIP project
McNair High School 2 Building 5010 Mechanical Gas Piping Replacement (SF Basis) Beyond Useful Life D Deficiency supports new CIP project
McNair High School 2 Building 5020 Mechanical HVAC VAV Box Replacement D Deficiency supports new CIP project
McNair High School 2 Building 5020 Mechanical Package Roof Top Unit Replacement D Deficiency supports new CIP project
McNair High School 3 Building 5020 Mechanical Testing And Balancing D Deficiency supports new CIP project
McNair High School 3 Building 5010 Plumbing Gas Water Heater Replacement Beyond Useful Life D Deficiency supports new CIP project
McNair High School 3 Building 5020 Plumbing Gas Water Heater Replacement Beyond Useful Life D Deficiency supports new CIP project
McNair High School 3 Building 5010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Useful Life
Beyond D Deficiency supports new CIP project
McNair High School 3 Building 5011 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Useful Life
Beyond D Deficiency supports new CIP project
McNair High School 3 Building 5012 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life D Deficiency supports new CIP project
McNair High School 3 Building 5010 Plumbing Sanitary Sewer Piping Replacement Beyond Useful Life D Deficiency supports new CIP project
McNair High School 3 Building 5011 Plumbing Sanitary Sewer Piping Replacement Beyond Useful Life D Deficiency supports new CIP project
McNair High School 3 Building 5012 Plumbing Sanitary Sewer Piping Replacement D Deficiency supports new CIP project
McNair High School 3 Site Concrete Walks Replacement Cracked D Deficiency supports new CIP project
Miller Grove High School 3 Building 5010 Mechanical Testing And Balancing D Deficiency supports new CIP project
Asphalt In Very Bad Condition At Back
Driveway At Cafeteria Doors. Replace And
Miller Grove High School 3 Site Asphalt Driveway Replacement Repair Asphalt At Baseball Concession Stand D Deficiency supports new CIP project
Where Water Pipe Is Under Asphalt. Encase
Water Pipe In Steel Pipe Before Backfilling.
Miller Grove Middle School 2 Building 4010 Mechanical Gas Unit Heater Replacement Mech Room D Deficiency supports new CIP project
Miller Grove Middle School 2 Building 4011 Plumbing Water Heater Replacement Custodian D Deficiency supports new CIP project
Miller Grove Middle School 3 Site Asphalt Driveway Replacement Beyond Useful Life Cracked D Deficiency supports new CIP project
Montclair Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
83 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Estimated Based Upon Existing Devices And
Montclair Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement D Deficiency supports new CIP project
Conduit
Montclair Elementary School 2 Building 2011 Roofing Modified Roof Covering Replacement Age And Wear D Deficiency supports new CIP project
Montclair Elementary School 3 Site Asphalt Driveway Replacement D Deficiency supports new CIP project
Montgomery Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
Montgomery Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement Old Building Wiring. D Deficiency supports new CIP project
Montgomery Elementary School 3 Building 2011 Electrical Interior Power Wiring Replacement Old Wiring D Deficiency supports new CIP project
Montgomery Elementary School 3 Building 2012 Electrical Interior Power Wiring Replacement Old Wiring In Building D Deficiency supports new CIP project
Montgomery Elementary School 3 Building 2013 Electrical Interior Power Wiring Replacement Old Wiring In Building D Deficiency supports new CIP project
Montgomery Elementary School 2 Building 2010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Montgomery Elementary School 2 Building 2010 Electrical Panelboard Replacement Stage 48.3 D Deficiency supports new CIP project
Montgomery Elementary School 2 Building 2010 Electrical Panelboard Replacement Kitchen D Deficiency supports new CIP project
Montgomery Elementary School 2 Building 2010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Montgomery Elementary School 2 Building 2010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Montgomery Elementary School 2 Building 2011 Electrical Panelboard Replacement D Deficiency supports new CIP project
Montgomery Elementary School 2 Building 2011 Electrical Panelboard Replacement D Deficiency supports new CIP project
Montgomery Elementary School 2 Building 2011 Electrical Panelboard Replacement D Deficiency supports new CIP project
Montgomery Elementary School 2 Building 2012 Electrical Panelboard Replacement Exposed Wiring Inside Panel. D Deficiency supports new CIP project
Montgomery Elementary School 2 Building 2012 Electrical Panelboard Replacement D Deficiency supports new CIP project
Montgomery Elementary School 2 Building 2013 Electrical Panelboard Replacement D Deficiency supports new CIP project
Montgomery Elementary School 2 Building 2013 Electrical Panelboard Replacement D Deficiency supports new CIP project
Roof Leaks Near The Main Entrance And
Montgomery Elementary School 2 Building 2010 Roofing Modified Roof Covering Replacement D Deficiency supports new CIP project
Outside The Cafeteria Hall.
Montgomery Elementary School 2 Building 2012 Roofing Modified Roof Covering Replacement Roof Leaks In Classroom 25 D Deficiency supports new CIP project
Montgomery Elementary School 3 Site Concrete Walks Replacement Cracked D Deficiency supports new CIP project
Narvie Harris Elementary School 3 Building 2010 Interior Athletic Sport Flooring Replacement Lifting And Splitting Gym D Deficiency supports new CIP project
Narvie Harris Elementary School 3 Building 2010 Interior Rubber Flooring Replacement Breaking And Holes D Deficiency supports new CIP project
Narvie Harris Elementary School 2 Building 2010 Roofing Metal Roof Architectural Roof Covering Replacement Leaks In Various Locations D Deficiency supports new CIP project
Narvie Harris Elementary School 3 Building 2010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing D Deficiency supports new CIP project
Narvie Harris Elementary School 3 Site Asphalt Driveway Replacement Cracking And Pot Holes D Deficiency supports new CIP project
Narvie Harris Elementary School 3 Site Asphalt Walks Replacement Cracking And Crumbling D Deficiency supports new CIP project
North DeKalb Stadium 3 Building 8010 Electrical Interior Power Wiring Replacement Old Wiring D Deficiency supports new CIP project
North DeKalb Stadium 2 Building 8010 Electrical Panelboard Replacement Boiler Room D Deficiency supports new CIP project
North DeKalb Stadium 2 Building 8010 Electrical Panelboard Replacement Storage Room D Deficiency supports new CIP project
North DeKalb Stadium 2 Building 8010 Electrical Panelboard Replacement Elec Room D Deficiency supports new CIP project
North DeKalb Stadium 2 Building 8020 Electrical Panelboard Replacement Ticket Booth D Deficiency supports new CIP project
North DeKalb Stadium 2 Building 8030 Electrical Panelboard Replacement D Deficiency supports new CIP project
North DeKalb Stadium 2 Building 8010 Electrical Switchgear Replacement Elec Room D Deficiency supports new CIP project
North DeKalb Stadium 2 Building 8010 Mechanical Electric Unit Heater Replacement Storage D Deficiency supports new CIP project
North DeKalb Stadium 2 Building 8010 Mechanical Steam/HW Unit Heater Replacement Home Locker Room D Deficiency supports new CIP project
North DeKalb Stadium 3 Site Concrete Driveways Replacement Cracked D Deficiency supports new CIP project
North DeKalb Stadium 3 Site Concrete Walks Replacement Cracked D Deficiency supports new CIP project
Oak Grove Elementary School 2 Building 2010 Mechanical Cast Iron Water Boiler Replacement Replace D Deficiency supports new CIP project
Oak Grove Elementary School 3 Building 2010 Mechanical Testing And Balancing D Deficiency supports new CIP project
Oak Grove Elementary School 3 Building 2011 Mechanical Testing And Balancing D Deficiency supports new CIP project
Oak Grove Elementary School 3 Building 2012 Mechanical Testing And Balancing D Deficiency supports new CIP project
Oak Grove Elementary School 3 Building 2020 Mechanical Testing And Balancing D Deficiency supports new CIP project
Oakcliff Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Panola Way Elementary School 3 Building 2011 Plumbing Toilet Replacement Cracked In Room 214 D Deficiency supports new CIP project
Panola Way Elementary School 3 Building 2020 Plumbing Urinal Replacement D Deficiency supports new CIP project
Panola Way Elementary School 3 Site Asphalt Driveway Replacement D Deficiency supports new CIP project
Panola Way Elementary School 3 Site Concrete Walks Replacement D Deficiency supports new CIP project
Panthersville Administrative 3 Building 8030 Electrical Interior Power Wiring Replacement D Deficiency supports new CIP project
Panthersville Administrative 3 Building 8040 Electrical Interior Power Wiring Replacement D Deficiency supports new CIP project
Panthersville Administrative 2 Building 8010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Panthersville Administrative 2 Building 8010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Panthersville Administrative 2 Building 8020 Electrical Panelboard Replacement D Deficiency supports new CIP project
Panthersville Administrative 2 Building 8030 Electrical Panelboard Replacement D Deficiency supports new CIP project
Panthersville Administrative 2 Building 8040 Electrical Panelboard Replacement D Deficiency supports new CIP project
Panthersville Administrative 2 Building 8020 Exterior Composite Exterior Siding Replacement (Bldg SF) Beyond Useful Life D Deficiency supports new CIP project
Panthersville Administrative 2 Building 8010 Mechanical Ductwork Replacement (SF Basis) D Deficiency supports new CIP project
84 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Panthersville Administrative 2 Building 8010 Mechanical Infrared Electric Radiant Heater Replacement D Deficiency supports new CIP project
Panthersville Administrative 2 Building 8010 Mechanical Package Roof Top Unit Replacement D Deficiency supports new CIP project
Panthersville Administrative 3 Building 8010 Mechanical Testing And Balancing D Deficiency supports new CIP project
Panthersville Administrative 2 Building 8010 Mechanical Thru Wall AC Replacement Instructors D Deficiency supports new CIP project
Panthersville Administrative 2 Building 8020 Roofing Asphalt Shingle Roof Covering Replacement Beyond Useful Life D Deficiency supports new CIP project
Pine Ridge Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
Pine Ridge Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
Pine Ridge Elementary School 2 Building 2010 Electrical Generator Replacement Beyond Useful Life - Actual 60KW D Deficiency supports new CIP project
Pine Ridge Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement Beyond Useful Life D Deficiency supports new CIP project
Pine Ridge Elementary School 2 Building 2010 Electrical Panelboard Replacement Actual 120 And 208 And 60A D Deficiency supports new CIP project
Pine Ridge Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Pine Ridge Elementary School 2 Building 2010 Electrical Panelboard Replacement Actual 120 And 208 150A D Deficiency supports new CIP project
Pine Ridge Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Pine Ridge Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Pine Ridge Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Pine Ridge Elementary School 2 Building 2010 Electrical Switchgear Replacement Beyond Useful Life D Deficiency supports new CIP project
Princeton Elementary School 2 Building 2010 Mechanical Exterior Metal Cooling Tower Replacement D Deficiency supports new CIP project
Princeton Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement RLT, Original Units D Deficiency supports new CIP project
Princeton Elementary School 2 Building 2010 Mechanical Package Roof Top Unit Replacement Not Working D Deficiency supports new CIP project
Princeton Elementary School 3 Building 2010 Mechanical Testing And Balancing D Deficiency supports new CIP project
Rainbow Elementary School 3 Building 2010 Mechanical Testing And Balancing Test D Deficiency supports new CIP project
Rainbow Elementary School 3 Building 2011 Mechanical Testing And Balancing Test D Deficiency supports new CIP project
Rainbow Elementary School 3 Building 2012 Mechanical Testing And Balancing Test D Deficiency supports new CIP project
Rainbow Elementary School 2 Building 2012 Roofing Modified Roof Covering Replacement Beyond Useful Life D Deficiency supports new CIP project
Redan Elementary School 2 Building 2010 Electrical Distribution Panel Replacement D Deficiency supports new CIP project
Redan Elementary School 2 Building 2020 Electrical Distribution Panel Replacement D Deficiency supports new CIP project
Redan Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
Redan Elementary School 2 Building 2020 Electrical Electrical Transformer Replacement 50 Kva D Deficiency supports new CIP project
Redan Elementary School 2 Building 2030 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
Redan Elementary School 2 Building 2040 Electrical Exterior Dry Type Transformer Replacement D Deficiency supports new CIP project
Redan Elementary School 2 Building 2010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Redan Elementary School 2 Building 2010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Redan Elementary School 2 Building 2010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Redan Elementary School 2 Building 2020 Electrical Panelboard Replacement Panel 2A D Deficiency supports new CIP project
Redan Elementary School 2 Building 2020 Electrical Panelboard Replacement Panel 3 D Deficiency supports new CIP project
Redan Elementary School 2 Building 2020 Electrical Panelboard Replacement 266 And 460V, Old D Deficiency supports new CIP project
Redan Elementary School 2 Building 2020 Electrical Panelboard Replacement Old, Hmp D Deficiency supports new CIP project
Redan Elementary School 2 Building 2030 Mechanical Electric Unit Heater Replacement Aged D Deficiency supports new CIP project
Redan Elementary School 2 Building 2020 Mechanical Fin Tube Water Radiant Heater Replacement Age D Deficiency supports new CIP project
Redan Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life D Deficiency supports new CIP project
Redan Elementary School 2 Building 2011 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life D Deficiency supports new CIP project
Redan Elementary School 3 Building 2020 Mechanical Small Diameter Exhausts/Hoods Replacement Old And Damaged D Deficiency supports new CIP project
Redan Elementary School 3 Building 2010 Mechanical Testing And Balancing D Deficiency supports new CIP project
Redan Elementary School 3 Building 2011 Mechanical Testing And Balancing D Deficiency supports new CIP project
Redan Elementary School 3 Building 2030 Mechanical Testing And Balancing D Deficiency supports new CIP project
Redan Elementary School 3 Building 2021 Plumbing Toilet Replacement Age D Deficiency supports new CIP project
Redan Elementary School 2 Building 2030 Plumbing Water Heater Replacement Aged D Deficiency supports new CIP project
East And South Parking Lot Asphalt
Redan Elementary School 3 Site Asphalt Driveway Replacement Driveways, Front Of School, Back Paving Near D Deficiency supports new CIP project
Playground
Redan Elementary School 3 Site Concrete Walks Replacement D Deficiency supports new CIP project
Redan High School 2 Building 5010 Electrical Distribution Panel Replacement Old Elec Room D Deficiency supports new CIP project
Majority Of Branch Circuit Wiring Is Original
Redan High School 3 Building 5010 Electrical Interior Power Wiring Replacement D Deficiency supports new CIP project
To Building - 1976 Install.
Redan High School 2 Building 5010 Electrical Panelboard Replacement Old Elec Room D Deficiency supports new CIP project
Redan High School 2 Building 5010 Electrical Panelboard Replacement Old Hallways D Deficiency supports new CIP project
Redan High School 2 Building 5010 Electrical Panelboard Replacement Old Elec Room D Deficiency supports new CIP project
Redan High School 2 Building 5010 Electrical Panelboard Replacement Old Elec Room D Deficiency supports new CIP project
Redan High School 2 Building 5010 Electrical Panelboard Replacement Old Elec Room D Deficiency supports new CIP project
Redan High School 2 Building 5010 Electrical Panelboard Replacement Old Hallways D Deficiency supports new CIP project
Redan High School 2 Building 5010 Mechanical Exterior Chiller Replacement D Deficiency supports new CIP project
85 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Redan High School 3 Building 5010 Plumbing Instant Water Heater Replacement Mech Room B20 D Deficiency supports new CIP project
Redan High School 3 Building 5010 Plumbing Shower Replacement Locker Rooms At Gym D Deficiency supports new CIP project
Redan High School 3 Building 5010 Plumbing Toilet Replacement A424.1, A412.1, A412.2 D Deficiency supports new CIP project
Redan High School 3 Building 5010 Plumbing Urinal Replacement A424.2, A401.4 D Deficiency supports new CIP project
Redan High School 3 Site Asphalt Driveway Replacement Damaged And Aged D Deficiency supports new CIP project
Redan High School 3 Site Concrete Walks Replacement To Tennis Court And Damaged D Deficiency supports new CIP project
Concrete Sidewalk From Street To Entry
Robert Shaw Theme 3 Site Concrete Walks Replacement D Deficiency supports new CIP project
(Main) Cracked. Replace.
Rowland Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
Rowland Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
Rowland Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement Old 1967 Wiring D Deficiency supports new CIP project
Rowland Elementary School 3 Building 2011 Electrical Interior Power Wiring Replacement Old 1969 Wiring D Deficiency supports new CIP project
Rowland Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Rowland Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Rowland Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Rowland Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Rowland Elementary School 2 Building 2010 Mechanical Air Cooled Condenser Replacement 1.5 Tons, No Roof Access D Deficiency supports new CIP project
Rowland Elementary School 2 Building 2010 Mechanical Ductless Split System AC Replacement 1.5 Ton D Deficiency supports new CIP project
Rowland Elementary School 2 Building 2010 Mechanical Ductwork Replacement (SF Basis) D Deficiency supports new CIP project
Rowland Elementary School 2 Building 2011 Mechanical Ductwork Replacement (SF Basis) D Deficiency supports new CIP project
Rowland Elementary School 2 Building 2010 Mechanical Gas Piping Replacement (SF Basis) D Deficiency supports new CIP project
Rowland Elementary School 2 Building 2011 Mechanical Gas Piping Replacement (SF Basis) D Deficiency supports new CIP project
Rowland Elementary School 3 Building 2010 Mechanical Large Diameter Exhausts/Hoods Replacement No Roof Access D Deficiency supports new CIP project
Rowland Elementary School 2 Building 2010 Mechanical Package DX Unit Replacement D Deficiency supports new CIP project
Rowland Elementary School 2 Building 2011 Mechanical Package DX Unit Replacement D Deficiency supports new CIP project
Rowland Elementary School 2 Building 2012 Mechanical Package DX Unit Replacement 4 Ton D Deficiency supports new CIP project
Rowland Elementary School 2 Building 2010 Mechanical Package Roof Top Unit Replacement No Roof Access D Deficiency supports new CIP project
Rowland Elementary School 2 Building 2010 Mechanical Package Roof Top Unit Replacement 3 Ton, No Roof Access D Deficiency supports new CIP project
Rowland Elementary School 2 Building 2010 Mechanical Package Roof Top Unit Replacement No Roof Access D Deficiency supports new CIP project
Rowland Elementary School 2 Building 2011 Mechanical Package Roof Top Unit Replacement 3 Ton, No Roof Access D Deficiency supports new CIP project
Rowland Elementary School 2 Building 2012 Mechanical Package Roof Top Unit Replacement No Roof Access D Deficiency supports new CIP project
Rowland Elementary School 3 Building 2010 Mechanical Testing And Balancing D Deficiency supports new CIP project
Rowland Elementary School 3 Building 2011 Mechanical Testing And Balancing D Deficiency supports new CIP project
Rowland Elementary School 3 Building 2012 Mechanical Testing And Balancing D Deficiency supports new CIP project
Rowland Elementary School 3 Building 2010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life D Deficiency supports new CIP project
Rowland Elementary School 3 Building 2011 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life D Deficiency supports new CIP project
Rowland Elementary School 3 Building 2010 Plumbing Sanitary Sewer Piping Replacement D Deficiency supports new CIP project
Rowland Elementary School 3 Building 2011 Plumbing Sanitary Sewer Piping Replacement D Deficiency supports new CIP project
Beyond Useful Life - No Roof Access But Roof
Rowland Elementary School 2 Building 2010 Roofing Modified Roof Covering Replacement Is Beyond Useful Life Based On Interview D Deficiency supports new CIP project
With The Principal And Images
Rowland Elementary School 3 Site Aluminum Covered Walkways Replacement Significant Damage D Deficiency supports new CIP project
Rowland Elementary School 3 Site Asphalt Driveway Replacement Cracked And Aged D Deficiency supports new CIP project
Rowland Elementary School 3 Site Concrete Walks Replacement Damaged D Deficiency supports new CIP project
Sagamore Hills Elementary School 3 Building 2010 Mechanical Testing And Balancing Test D Deficiency supports new CIP project
Sagamore Hills Elementary School 3 Building 2011 Mechanical Testing And Balancing Test D Deficiency supports new CIP project
Sagamore Hills Elementary School 3 Building 2020 Mechanical Testing And Balancing Test D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8040 Electrical Distribution Panel Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8010 Electrical Electrical Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8010 Electrical Electrical Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8010 Electrical Electrical Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8030 Electrical Electrical Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8040 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8050 Electrical Electrical Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8020 Electrical Exterior Dry Type Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8010 Electrical Generator Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8010 Electrical Interior Power Wiring Replacement D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8030 Electrical Interior Power Wiring Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8040 Electrical Interior Power Wiring Replacement D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8050 Electrical Interior Power Wiring Replacement Beyond Useful Life D Deficiency supports new CIP project
86 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Sam Moss Service Center 2 Building 8010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8020 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8020 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8030 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8030 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8030 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8040 Electrical Panelboard Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8040 Electrical Panelboard Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8040 Electrical Panelboard Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8040 Electrical Panelboard Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8050 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8050 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8060 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8010 Electrical Transfer Switch Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8040 Exterior Metal Panel Exterior Replacement (Bldg SF) Insulated Panel D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8020 Mechanical Air Compressor Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8030 Mechanical Air Compressor Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8010 Mechanical Air Cooled Condenser Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8030 Mechanical Air Cooled Condenser Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8040 Mechanical Air Handler HVAC Component Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8040 Mechanical Air Handler HVAC Component Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8010 Mechanical Ductless Split System AC Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8030 Mechanical Ductwork Replacement (SF Basis) D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8040 Mechanical Ductwork Replacement (SF Basis) D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8010 Mechanical Electric Unit Heater Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8010 Mechanical Exterior Metal Cooling Tower Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8040 Mechanical Fan Coil Unit Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8010 Mechanical Gas Furnace HVAC Component Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8030 Mechanical Gas Furnace HVAC Component Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8010 Mechanical Gas Piping Replacement (SF Basis) D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8040 Mechanical Gas Piping Replacement (SF Basis) D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8050 Mechanical Gas Piping Replacement (SF Basis) D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8060 Mechanical Gas Piping Replacement (SF Basis) D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8010 Mechanical Gas Unit Heater Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8020 Mechanical Gas Unit Heater Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8030 Mechanical Gas Unit Heater Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8040 Mechanical Gas Unit Heater Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8040 Mechanical Gas Unit Heater Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8050 Mechanical Gas Unit Heater Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8060 Mechanical Gas Unit Heater Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8010 Mechanical Heat Pump HVAC Component Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8040 Mechanical Heat Pump HVAC Component Replacement D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8010 Mechanical Large Diameter Exhausts/Hoods Replacement D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8040 Mechanical Large Diameter Exhausts/Hoods Replacement D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8050 Mechanical Large Diameter Exhausts/Hoods Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8010 Mechanical Package Roof Top Unit Replacement 5 Ton D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8010 Mechanical Package Roof Top Unit Replacement 4 Ton D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8010 Mechanical Package Roof Top Unit Replacement 6 Tons (2 Ea.) 7.5 Tons (3 Ea.) D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8010 Mechanical Package Roof Top Unit Replacement D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8030 Mechanical Small Diameter Exhausts/Hoods Replacement D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8040 Mechanical Small Diameter Exhausts/Hoods Replacement D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8050 Mechanical Small Diameter Exhausts/Hoods Replacement D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8060 Mechanical Thru Wall AC Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8010 Mechanical Unit Ventilator Replacement D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life D Deficiency supports new CIP project
87 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Sam Moss Service Center 3 Building 8020 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8030 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8040 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8050 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8060 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8040 Plumbing Shower Replacement D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8030 Plumbing Toilet Replacement D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8040 Plumbing Toilet Replacement D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8050 Plumbing Toilet Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8040 Plumbing Urinal Replacement D Deficiency supports new CIP project
Sam Moss Service Center 3 Building 8050 Plumbing Urinal Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 2 Building 8050 Plumbing Water Heater Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 3 Site Asphalt Driveway Replacement Beyond Useful Life D Deficiency supports new CIP project
Sam Moss Service Center 3 Site Concrete Walks Replacement D Deficiency supports new CIP project
Snapfinger Elementary School 2 Building 2010 Electrical Distribution Panel Replacement D Deficiency supports new CIP project
Snapfinger Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
Snapfinger Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
Band Room, Boiler Room And Janitorial
Snapfinger Elementary School 3 Building 2012 Electrical Lighting Fixtures Replacement Closet Need Immediate Replacement Of D Deficiency supports new CIP project
Lights.
Snapfinger Elementary School 2 Building 2010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Snapfinger Elementary School 2 Building 2010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Snapfinger Elementary School 2 Building 2010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Snapfinger Elementary School 2 Building 2011 Electrical Panelboard Replacement D Deficiency supports new CIP project
Snapfinger Elementary School 2 Building 2011 Electrical Panelboard Replacement D Deficiency supports new CIP project
Snapfinger Elementary School 2 Building 2011 Electrical Panelboard Replacement D Deficiency supports new CIP project
Snapfinger Elementary School 2 Building 2011 Electrical Panelboard Replacement Need Replacement. Lower Level Storage D Deficiency supports new CIP project
Snapfinger Elementary School 2 Building 2012 Electrical Panelboard Replacement D Deficiency supports new CIP project
Snapfinger Elementary School 2 Building 2012 Electrical Panelboard Replacement D Deficiency supports new CIP project
Snapfinger Elementary School 2 Building 2012 Electrical Panelboard Replacement D Deficiency supports new CIP project
Snapfinger Elementary School 2 Building 2012 Electrical Panelboard Replacement D Deficiency supports new CIP project
Snapfinger Elementary School 2 Building 2010 Electrical Switchgear Replacement D Deficiency supports new CIP project
Snapfinger Elementary School 2 Building 2013 Roofing Modified Roof Covering Replacement D Deficiency supports new CIP project
Snapfinger Elementary School 3 Site Asphalt Driveway Replacement All Driveways Are Damaged And Aged. D Deficiency supports new CIP project
Snapfinger Elementary School 3 Site Concrete Walks Replacement Damaged, Front Of Building D Deficiency supports new CIP project
Southwest DeKalb High School 3 Building 5060 Electrical Mounted Building Lighting Installation Building Mounted Lights Needed D Deficiency supports new CIP project
Southwest DeKalb High School 3 Building 5070 Electrical Mounted Building Lighting Installation Ext. Lights Needed. D Deficiency supports new CIP project
Southwest DeKalb High School 2 Building 5012 Mechanical Ductless Split System AC Replacement Beyond Useful Life - Room 6357 D Deficiency supports new CIP project
Southwest DeKalb High School 2 Building 5030 Plumbing Water Heater Replacement Beyond Useful Life - Custodial Closet D Deficiency supports new CIP project
Cracking And Uneven And Lot Outside
Southwest DeKalb High School 3 Site Asphalt Driveway Replacement D Deficiency supports new CIP project
Building 5020
Cracked And South Of Building 5010 And
Southwest DeKalb High School 3 Site Concrete Walks Replacement D Deficiency supports new CIP project
5011
Stephenson High School 2 Building 5050 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
Stephenson High School 2 Building 5020 Electrical Panelboard Replacement D Deficiency supports new CIP project
Stephenson High School 2 Building 5050 Electrical Panelboard Replacement D Deficiency supports new CIP project
Stephenson High School 2 Building 5050 Electrical Panelboard Replacement D Deficiency supports new CIP project
Stephenson High School 3 Building 5010 Plumbing Toilet Replacement D Deficiency supports new CIP project
Stephenson High School 3 Building 5010 Plumbing Urinal Replacement D Deficiency supports new CIP project
Stor. 105.5, Cust 112.3. Has Bad Pressure
Stephenson High School 2 Building 5010 Plumbing Water Heater Replacement D Deficiency supports new CIP project
Relief Value
Stephenson High School 3 Building 5010 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing D Deficiency supports new CIP project
Stephenson High School 3 Building 5011 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Near Gutters D Deficiency supports new CIP project
Stephenson High School 3 Site Asphalt Driveway Replacement Repave D Deficiency supports new CIP project
Stephenson High School 3 Site Concrete Walks Replacement Cracked And Damaged D Deficiency supports new CIP project
Stephenson Middle School 2 Building 4010 Electrical Generator Replacement D Deficiency supports new CIP project
Stephenson Middle School 2 Building 4010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Stephenson Middle School 3 Building 4010 Electrical Transfer Switch Replacement D Deficiency supports new CIP project
Stone Mill Elementary School 2 Building 2010 Roofing Modified Roof Covering Replacement D Deficiency supports new CIP project
Stone Mill Elementary School 2 Building 2012 Roofing Modified Roof Covering Replacement Beyond Useful Life - Many Bubbles D Deficiency supports new CIP project
88 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Stone Mill Elementary School 3 Site Concrete Walks Replacement Cracked Sidewalk D Deficiency supports new CIP project
Stone Mountain Elementary School 2 Building 2013 Electrical Distribution Panel Replacement Beyond Useful Life D Deficiency supports new CIP project
Stone Mountain Elementary School 2 Building 2012 Electrical Electrical Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
Stone Mountain Elementary School 2 Building 2013 Electrical Electrical Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
Stone Mountain Elementary School 2 Building 2013 Electrical Electrical Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
Stone Mountain Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life 120 And 208 200A D Deficiency supports new CIP project
Stone Mountain Elementary School 2 Building 2013 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Stone Mountain Elementary School 2 Building 2013 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Stone Mountain Elementary School 2 Building 2013 Electrical Panelboard Replacement Beyond Useful Life 277 And 480 50A D Deficiency supports new CIP project
Stone Mountain Elementary School 2 Building 2013 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Stone Mountain Elementary School 2 Building 2013 Electrical Panelboard Replacement Beyond Useful Life 120 And 208 600A, D Deficiency supports new CIP project
Stone Mountain Elementary School 2 Building 2013 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Stone Mountain Elementary School 2 Building 2013 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Stone Mountain Elementary School 2 Building 2011 Mechanical Exterior Metal Cooling Tower Replacement Beyond Useful Life 125 Tons, D Deficiency supports new CIP project
Stone Mountain Elementary School 2 Building 2011 Mechanical Heat Exchanger Replacement Beyond Useful Life 375 Gpm D Deficiency supports new CIP project
Stone Mountain High School 3 Exterior Handrail Replacement Site Stair Hand Rail; Damaged D Deficiency supports new CIP project
Stone Mountain High School 3 Building 5010 Exterior Metal Panel Exterior Repair Broken Seals And Fasteners D Deficiency supports new CIP project
Stone Mountain High School 3 Building 5010 Plumbing Shower Replacement D Deficiency supports new CIP project
Ladder To High Roof Is Loose And Has Missing
Stone Mountain High School 3 Building 5010 Roofing Roof Access Ladder Replacement D Deficiency supports new CIP project
Bracket On Top
Estimated Quantity - Principal Indicated Some
Stone Mountain Middle School 2 Building 4010 Site Bleacher Repair D Deficiency supports new CIP project
Bleacher Sections Do Not Pull Out.
Stone Mountain Middle School 3 Site Concrete Walks Replacement Cracked D Deficiency supports new CIP project
Towers High School 2 Building 5010 Mechanical Ductless Split System AC Replacement Beyond Useful Life D Deficiency supports new CIP project
All Gas Piping On Roof Corroded And Beyond
Towers High School 2 Building 5010 Mechanical Gas Piping Replacement (SF Basis) D Deficiency supports new CIP project
Useful Life
Towers High School 2 Building 5013 Mechanical Gas Piping Replacement (SF Basis) Referring To Building 2010 D Deficiency supports new CIP project
Towers High School 2 Building 5010 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life D Deficiency supports new CIP project
Towers High School 3 Building 5010 Mechanical Large Diameter Exhausts/Hoods Replacement All Beyond Useful Life Or In Need Of Repair D Deficiency supports new CIP project
Beyond Useful Life - Staff Reported Units Are
Towers High School 2 Building 5010 Mechanical Package Roof Top Unit Replacement Failing And Have Issues When Seasons D Deficiency supports new CIP project
Change
Beyond Useful Life - Staff Reported Units Are
Towers High School 2 Building 5010 Mechanical Package Roof Top Unit Replacement Failing And Have Issues When Seasons D Deficiency supports new CIP project
Change
Beyond Useful Life - Staff Have Reported
Towers High School 2 Building 5010 Mechanical Package Roof Top Unit Replacement Units Are Failing And Have Issues When D Deficiency supports new CIP project
Seasons Change
All Heat Pumps And Rooftop Need To Be
Towers High School 3 Building 5010 Mechanical Testing And Balancing D Deficiency supports new CIP project
Replaced And Balanced
Towers High School 2 Building 5013 Roofing Modified Roof Covering Replacement D Deficiency supports new CIP project
Towers High School 3 Building 5013 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
No Recent Rain, Yet Soft Spots From Ponding D Deficiency supports new CIP project
Towers High School 3 Site Concrete Walks Replacement Cracking And Chipping D Deficiency supports new CIP project
Brick Joint Too Large Because Of Slab
Tucker High School 3 Building 5010 Exterior Brick Exterior Repointing D Deficiency supports new CIP project
Settlement
Tucker High School 3 Building 5010 Mechanical Testing And Balancing D Deficiency supports new CIP project
Tucker High School 3 Building 5020 Mechanical Testing And Balancing D Deficiency supports new CIP project
Repair Bubbles Over Gym, Band And
Tucker High School 3 Building 5010 Roofing Modified Covering Has Blisters That Should Be Repaired D Deficiency supports new CIP project
Orchestra Wings
Replace Wings A And B Roofs, Very Bad With
Tucker High School 2 Building 5010 Roofing Modified Roof Covering Replacement D Deficiency supports new CIP project
Many Bubbles
Vanderlyn Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
Vanderlyn Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
Vanderlyn Elementary School 2 Building 2010 Electrical Generator Replacement Generator Is Not Working D Deficiency supports new CIP project
Vanderlyn Elementary School 2 Building 2010 Electrical Panelboard Replacement Old D Deficiency supports new CIP project
Old Panelboard Should Be Replaced In Room
Vanderlyn Elementary School 2 Building 2010 Electrical Panelboard Replacement D Deficiency supports new CIP project
11.3
89 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Old Panelboards In Rooms 14 And 15 Should
Vanderlyn Elementary School 2 Building 2010 Electrical Panelboard Replacement D Deficiency supports new CIP project
Be Replaced
Old Panelboard Should Be Replaced In Room
Vanderlyn Elementary School 2 Building 2010 Electrical Panelboard Replacement D Deficiency supports new CIP project
19
Old Panelboard Should Be Replaced In Room
Vanderlyn Elementary School 2 Building 2010 Electrical Panelboard Replacement D Deficiency supports new CIP project
11.3
Vanderlyn Elementary School 3 Site Concrete Walks Replacement Broken Sidewalks D Deficiency supports new CIP project
Wadsworth Magnet School 2 Building 2010 Electrical Distribution Panel Replacement Mech Room D Deficiency supports new CIP project
Wadsworth Magnet School 2 Building 2010 Electrical Electrical Transformer Replacement Roof Top D Deficiency supports new CIP project
Wadsworth Magnet School 2 Building 2020 Electrical Electrical Transformer Replacement Outside Gym D Deficiency supports new CIP project
Voltage Fluctuations Persist In The Main
Office, Principal And Front Desk And
Wadsworth Magnet School 3 Building 2010 Electrical Interior Power Wiring Replacement Reception Areas. Replace Existing Power D Deficiency supports new CIP project
Wiring And Install Power Conditioner And
Voltage Stabilizer.
Wadsworth Magnet School 2 Building 2010 Electrical Panelboard Replacement Hallway 2010 Old D Deficiency supports new CIP project
Wadsworth Magnet School 2 Building 2010 Electrical Panelboard Replacement Media Center, Old D Deficiency supports new CIP project
Wadsworth Magnet School 2 Building 2010 Electrical Panelboard Replacement Media Center, Needs Front Cover D Deficiency supports new CIP project
Wadsworth Magnet School 2 Building 2010 Electrical Panelboard Replacement Old Panel. Cafeteria Stage D Deficiency supports new CIP project
Wadsworth Magnet School 2 Building 2010 Electrical Panelboard Replacement Old Panel - 2010 Hallway D Deficiency supports new CIP project
Wadsworth Magnet School 2 Building 2011 Electrical Panelboard Replacement 2011 Hallway D Deficiency supports new CIP project
Wadsworth Magnet School 2 Building 2011 Electrical Panelboard Replacement 2011 Hallway D Deficiency supports new CIP project
Wadsworth Magnet School 2 Building 2010 Electrical Switchgear Replacement Mech Room D Deficiency supports new CIP project
Wadsworth Magnet School 2 Building 2010 Mechanical Electric Unit Heater Replacement Broken, 112.1 D Deficiency supports new CIP project
Wadsworth Magnet School 3 Building 2010 Plumbing Gas Water Heater Replacement Beyond Useful Life - Room 112.1 D Deficiency supports new CIP project
Wadsworth Magnet School 3 Building 2010 Plumbing Gas Water Heater Replacement Beyond Useful Life - Room 112.1 D Deficiency supports new CIP project
Wadsworth Magnet School 2 Building 2010 Roofing Built-up Roofing Replacement Extensive Damage D Deficiency supports new CIP project
Wadsworth Magnet School 2 Building 2011 Roofing Built-up Roofing Replacement Extensive Damage D Deficiency supports new CIP project
Wadsworth Magnet School 3 Building 2011 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing D Deficiency supports new CIP project
Warren Technical Chamblee 3 Building 4020 Electrical Interior Power Wiring Replacement Old D Deficiency supports new CIP project
Warren Technical Chamblee 2 Building 4010 Electrical Panelboard Replacement Old, Corridor And Boiler D Deficiency supports new CIP project
Warren Technical Chamblee 2 Building 4010 Electrical Panelboard Replacement Old, Corridor D Deficiency supports new CIP project
Warren Technical Chamblee 2 Building 4010 Electrical Panelboard Replacement Old, Boiler Room D Deficiency supports new CIP project
Warren Technical Chamblee 2 Building 4010 Electrical Panelboard Replacement Old, Corridor And Boiler D Deficiency supports new CIP project
Warren Technical Chamblee 2 Building 4011 Electrical Panelboard Replacement Old - Utility D Deficiency supports new CIP project
Warren Technical Chamblee 2 Building 4011 Electrical Panelboard Replacement Old, Utility, Auto D Deficiency supports new CIP project
Warren Technical Chamblee 2 Building 4020 Electrical Panelboard Replacement Old D Deficiency supports new CIP project
William Bradley Bryant Technology Center 2 Building 8010 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
William Bradley Bryant Technology Center 2 Building 8010 Electrical Generator Replacement D Deficiency supports new CIP project
William Bradley Bryant Technology Center 2 Building 8010 Electrical Panelboard Replacement Old Panel D D Deficiency supports new CIP project
William Bradley Bryant Technology Center 2 Building 8010 Electrical Panelboard Replacement Old Panel D Deficiency supports new CIP project
William Bradley Bryant Technology Center 2 Building 8011 Electrical Panelboard Replacement Old D Deficiency supports new CIP project
William Bradley Bryant Technology Center 3 Building 8010 Electrical Transfer Switch Replacement D Deficiency supports new CIP project
William Bradley Bryant Technology Center 2 Building 8010 Mechanical Exterior Metal Cooling Tower Replacement Beyond Useful Life - Leaking D Deficiency supports new CIP project
William Bradley Bryant Technology Center 2 Building 8011 Mechanical Heat Pump HVAC Component Replacement D Deficiency supports new CIP project
William Bradley Bryant Technology Center 3 Building 8010 Mechanical Testing And Balancing D Deficiency supports new CIP project
William Bradley Bryant Technology Center 3 Building 8011 Plumbing Toilet Replacement D Deficiency supports new CIP project
William Buck Godfrey Stadium 2 Building 8010 Electrical Electrical Transformer Replacement D Deficiency supports new CIP project
William Buck Godfrey Stadium 3 Building 8010 Electrical Interior Power Wiring Replacement D Deficiency supports new CIP project
William Buck Godfrey Stadium 2 Building 8010 Electrical Panelboard Replacement D Deficiency supports new CIP project
William Buck Godfrey Stadium 2 Building 8010 Electrical Panelboard Replacement D Deficiency supports new CIP project
William Buck Godfrey Stadium 2 Building 8010 Electrical Panelboard Replacement D Deficiency supports new CIP project
William Buck Godfrey Stadium 2 Building 8010 Electrical Panelboard Replacement D Deficiency supports new CIP project
William Buck Godfrey Stadium 2 Building 8010 Electrical Switchgear Replacement D Deficiency supports new CIP project
William Buck Godfrey Stadium 2 Building 8010 Mechanical Boiler Replacement D Deficiency supports new CIP project
William Buck Godfrey Stadium 2 Building 8010 Mechanical Electric Unit Heater Replacement D Deficiency supports new CIP project
William Buck Godfrey Stadium 2 Building 8010 Mechanical Gas Piping Replacement (SF Basis) D Deficiency supports new CIP project
William Buck Godfrey Stadium 2 Building 8010 Mechanical Infrared Electric Radiant Heater Replacement D Deficiency supports new CIP project
William Buck Godfrey Stadium 2 Building 8010 Mechanical Infrared Electric Radiant Heater Replacement D Deficiency supports new CIP project
William Buck Godfrey Stadium 2 Building 8010 Mechanical Unit Ventilator Replacement D Deficiency supports new CIP project
William Buck Godfrey Stadium 3 Building 8010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life D Deficiency supports new CIP project
90 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
William Buck Godfrey Stadium 3 Building 8010 Plumbing Sanitary Sewer Piping Replacement D Deficiency supports new CIP project
William Buck Godfrey Stadium 3 Building 8010 Plumbing Water Storage Tank Replacement D Deficiency supports new CIP project
William Buck Godfrey Stadium 3 Site Asphalt Driveway Replacement Beyond Useful Life D Deficiency supports new CIP project
William Buck Godfrey Stadium 3 Site Concrete Walks Replacement Cracked D Deficiency supports new CIP project
Woodward Elementary School 2 Building 2010 Electrical Exterior Dry Type Transformer Replacement Beyond Useful Life D Deficiency supports new CIP project
Woodward Elementary School 3 Building 2011 Electrical Interior Power Wiring Replacement Beyond Useful Life D Deficiency supports new CIP project
Woodward Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Woodward Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life D Deficiency supports new CIP project
Woodward Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life - Federal Pacific D Deficiency supports new CIP project
Woodward Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life - Federal Pacific D Deficiency supports new CIP project
Woodward Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life - Federal Pacific D Deficiency supports new CIP project
Woodward Elementary School 2 Building 2011 Electrical Panelboard Replacement Beyond Useful Life - Federal Pacific D Deficiency supports new CIP project
Water Is Under Roofing At Concrete Covered
Walkway At Front Entrance. Water Needs To
Woodward Elementary School 2 Building 2010 Roofing Modified Roof Covering Replacement D Deficiency supports new CIP project
Be Removed. Roofing Seems To Be Ok But
Need To Remove Because Water Underneath.
Woodward Elementary School 2 Building 2012 Roofing Modified Roof Covering Replacement Old, Bubbler And All Locations D Deficiency supports new CIP project
Woodward Elementary School 3 Site Asphalt Walks Replacement Cracked And Front Portables D Deficiency supports new CIP project
Woodward Elementary School 3 Site Concrete Walks Replacement Broken And Cracked And Various D Deficiency supports new CIP project
Wynbrooke Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement Unit Has R22 D Deficiency supports new CIP project
Wynbrooke Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement R22 - 20 Ton D Deficiency supports new CIP project
Wynbrooke Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement Unit Has R22 D Deficiency supports new CIP project
Wynbrooke Elementary School 2 Building 2010 Mechanical Package Roof Top Unit Replacement R-22 D Deficiency supports new CIP project
Wynbrooke Elementary School 2 Building 2010 Mechanical Package Roof Top Unit Replacement R-22 D Deficiency supports new CIP project
Wynbrooke Elementary School 3 Building 2010 Mechanical Testing And Balancing D Deficiency supports new CIP project
Adams Stadium 3 Building 8010 Electrical Lighting Fixtures Replacement Beyond Useful Life - Stadium E Item assessed & not considered a priority deficiency
Adams Stadium 3 Building 8010 Electrical Lightning Protection System Installation Missing And Stadium E Item assessed & not considered a priority deficiency
Administrative and Instructional Complex (AIC) 3 Building 9030 Electrical Canopy Lighting Replacement All Canopy Lights Need To Be Replaced E Item assessed & not considered a priority deficiency
Administrative and Instructional Complex (AIC) 2 Building 9012 Electrical Distribution Panel Replacement Old E Item assessed & not considered a priority deficiency
Administrative and Instructional Complex (AIC) 2 Building 9012 Electrical Distribution Panel Replacement Old E Item assessed & not considered a priority deficiency
Administrative and Instructional Complex (AIC) 2 Building 9012 Electrical Distribution Panel Replacement Old E Item assessed & not considered a priority deficiency
Administrative and Instructional Complex (AIC) 2 Building 9012 Electrical Electrical Transformer Replacement Old E Item assessed & not considered a priority deficiency
Administrative and Instructional Complex (AIC) 2 Building 9012 Electrical Electrical Transformer Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Administrative and Instructional Complex (AIC) 2 Building 9012 Electrical Electrical Transformer Replacement Old E Item assessed & not considered a priority deficiency
Upstairs Corner Thru The Wall. Needs
Administrative and Instructional Complex (AIC) 2 Building 9030 Mechanical Fan Coil Unit Replacement E Item assessed & not considered a priority deficiency
Replacing
Administrative and Instructional Complex (AIC) 3 Building 9010 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Administrative and Instructional Complex (AIC) 3 Building 9011 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Administrative and Instructional Complex (AIC) 3 Building 9012 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Administrative and Instructional Complex (AIC) 2 Building 9010 Exterior Metal Exterior Door Replacement East Side E Item assessed & not considered a priority deficiency
Administrative and Instructional Complex (AIC) 2 Building 9012 Exterior Metal Exterior Door Replacement Major Rust And Back Of Building E Item assessed & not considered a priority deficiency
Administrative and Instructional Complex (AIC) 3 Building 9011 Roofing Modified Covering Has Blisters That Should Be Repaired E Item assessed & not considered a priority deficiency
Administrative and Instructional Complex (AIC) 2 Building 9011 Mechanical Package Roof Top Unit Replacement E Item assessed & not considered a priority deficiency
Administrative and Instructional Complex (AIC) 2 Building 9012 Electrical Panelboard Replacement Old E Item assessed & not considered a priority deficiency
Administrative and Instructional Complex (AIC) 2 Building 9012 Electrical Panelboard Replacement Old E Item assessed & not considered a priority deficiency
Administrative and Instructional Complex (AIC) 2 Building 9012 Electrical Panelboard Replacement E Item assessed & not considered a priority deficiency
Administrative and Instructional Complex (AIC) 2 Building 9012 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Administrative and Instructional Complex (AIC) 2 Building 9012 Electrical Panelboard Replacement Old E Item assessed & not considered a priority deficiency
Administrative and Instructional Complex (AIC) 2 Building 9012 Electrical Switchgear Replacement Old E Item assessed & not considered a priority deficiency
Balance Office Only. Duct Work Only In
Administrative and Instructional Complex (AIC) 3 Building 9020 Mechanical Testing And Balancing E Item assessed & not considered a priority deficiency
Office.
Allgood Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Old And Damaged E Item assessed & not considered a priority deficiency
Allgood Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Old And Damaged E Item assessed & not considered a priority deficiency
Allgood Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Old And Damaged E Item assessed & not considered a priority deficiency
Allgood Elementary School 2 Building 2013 Exterior Aluminum Window Replacement Old And Damaged E Item assessed & not considered a priority deficiency
Allgood Elementary School 2 Building 2013 Exterior Aluminum Window Replacement Old And Damaged E Item assessed & not considered a priority deficiency
Allgood Elementary School 2 Building 2013 Exterior Aluminum Window Replacement Old And Damaged E Item assessed & not considered a priority deficiency
Allgood Elementary School 2 Building 2013 Exterior Aluminum Window Replacement Old And Damaged E Item assessed & not considered a priority deficiency
Allgood Elementary School 2 Building 2013 Exterior Aluminum Window Replacement Old And Damaged E Item assessed & not considered a priority deficiency
Allgood Elementary School 2 Building 2014 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
91 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Allgood Elementary School 3 Building 2010 Plumbing Backflow Preventer Replacement Prv Station E Item assessed & not considered a priority deficiency
Allgood Elementary School 2 Building 2012 Exterior Brick Exterior Replacement (Bldg SF) E Item assessed & not considered a priority deficiency
Allgood Elementary School 3 Building 2012 Exterior Brick Exterior Repointing E Item assessed & not considered a priority deficiency
Allgood Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Allgood Elementary School 3 Building 2011 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Allgood Elementary School 3 Building 2013 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Allgood Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Allgood Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Allgood Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Allgood Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Allgood Elementary School 3 Building 2013 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Allgood Elementary School 3 Building 2014 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Allgood Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Arabia Mountain High School 3 Building 5010 Interior Interior Door Replacement Damaged E Item assessed & not considered a priority deficiency
Arabia Mountain High School 3 Building 5010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Avondale Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Beyond Useful Life - Not Insulated E Item assessed & not considered a priority deficiency
All Classroom Windows Are Not Insulated
Avondale Elementary School 2 Building 2011 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
And Beyond Useful Life
Avondale Elementary School 2 Building 2012 Exterior Aluminum Window Replacement Beyond Useful Life - Not Insulated E Item assessed & not considered a priority deficiency
Avondale Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Avondale Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Avondale Elementary School 3 Building 2013 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Avondale Elementary School 3 Building 2014 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Avondale Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Avondale Elementary School 3 Building 2011 Electrical Lightning Protection Terminal Replacement Not Existing E Item assessed & not considered a priority deficiency
Avondale Elementary School 2 Building 2010 Exterior Wood Exterior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 2 Building 5020 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5010 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5011 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5023 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5030 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5010 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5011 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5020 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5023 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5030 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5020 Interior Interior Door Hardware Replacement Not ADA Compliant E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5020 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5010 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5011 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5020 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5021 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5022 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5023 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5011 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5020 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5021 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5022 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5023 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5030 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5011 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5020 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5021 Electrical Public Address System Replacement, Non-main Building Intercom Is Served From Building 5020 E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5022 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Avondale High DSA 3 Building 5023 Electrical Public Address System Replacement, Non-main Building Building Is Serviced From Building 5020 E Item assessed & not considered a priority deficiency
Intercom System Is Serviced From Building
Avondale High DSA 3 Building 5030 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
5020
Avondale High DSA 2 Building 5010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
92 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Avondale High DSA 2 Building 5010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 2 Building 5010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 2 Building 5010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 2 Building 5011 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 2 Building 5011 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 2 Building 5011 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 2 Building 5011 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 2 Building 5011 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 2 Building 5011 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 2 Building 5011 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 2 Building 5021 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 2 Building 5010 Exterior Wood Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale High DSA 2 Building 5010 Exterior Wood Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale Stadium 2 Building 8010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale Stadium 2 Building 8010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Avondale Stadium 3 Building 8010 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Avondale Stadium 3 Building 8010 Interior Interior Door Hardware Replacement All Interior Office E Item assessed & not considered a priority deficiency
Avondale Stadium 3 Building 8010 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Avondale Stadium 3 Building 8010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Barack H. Obama Elementary 3 Building 2010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 2 Building 2010 Exterior Aluminum Storefront Exterior Door Replacement Old, Deficient. Replace E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 2 Building 2010 Electrical Distribution Panel Replacement Old, Book Storage E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 2 Building 2010 Electrical Distribution Panel Replacement Old, Mech Room E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 2 Building 2010 Electrical Distribution Panel Replacement Old, Lib Storage E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 3 Building 2010 Electrical Electrical Receptacle Replacement Multiple Locations E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 3 Building 2011 Electrical Electrical Receptacle Replacement Multiple Locations E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement 37.5 Kva - Old, Mech Room E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Old, Book Storage, Elec Room E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Old, Stage And Cafe E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Old, Lib Storage E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Old, Mech Room E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement Replace Light Outside Music Room E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement Non-ADA Compliant (Knobs) - Replace. E Item assessed & not considered a priority deficiency
Wood Doors Old, Deficient And Highly
Bob Mathis Elementary School 3 Building 2010 Interior Interior Door Replacement Inconsistent Access School. Replace All To E Item assessed & not considered a priority deficiency
Match. Single Type And Finish.
Bob Mathis Elementary School 3 Building 2010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 3 Building 2011 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 3 Building 2020 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 2 Building 2010 Exterior Metal Exterior Door Replacement Old, Deficient. Replace E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 2 Building 2010 Electrical Panelboard Replacement Elec Room Next To Back Storage E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 2 Building 2010 Electrical Panelboard Replacement Old, Mech Room E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 2 Building 2010 Electrical Panelboard Replacement Lib Storage E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 2 Building 2010 Electrical Panelboard Replacement Old, Kitchen E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 2 Building 2010 Electrical Panelboard Replacement Lib Storage E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 2 Building 2010 Electrical Panelboard Replacement Old, Stage E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 2 Building 2010 Electrical Panelboard Replacement Old, Elec Room Next To Storage E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 2 Building 2010 Electrical Panelboard Replacement Old Lib Storage E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 2 Building 2010 Electrical Switchgear Replacement Old. Replace. Mech Room E Item assessed & not considered a priority deficiency
Bob Mathis Elementary School 2 Building 2010 Exterior Wood Exterior Door Replacement Old, Replace E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement Old E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 3 Building 2011 Electrical Canopy Lighting Replacement Old E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 3 Building 2012 Electrical Canopy Lighting Replacement Old E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement Old E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement Old E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 3 Building 2011 Electrical Exterior Mounted Building Lighting Replacement Old E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 3 Building 2012 Electrical Exterior Mounted Building Lighting Replacement Old E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement Old E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 3 Building 2011 Electrical Interior Power Wiring Replacement Old E Item assessed & not considered a priority deficiency
93 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Briar Vista Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Old E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement Old E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 3 Building 2012 Electrical Lighting Fixtures Replacement Old E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement Old E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Briar Vista Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Existing Large Openings With Steel Framed
Windows Calculated As Storefront And
Briar Vista Elementary School 2 Building 2010 Exterior Storefront/Curtain Wall Replacement (Bldg SF) E Item assessed & not considered a priority deficiency
Curtain Wall. All Is Beyond Useful Life And
Needs To Be Replaced
Grouping Of Steel Windows Are Recorded As
Briar Vista Elementary School 2 Building 2011 Exterior Storefront/Curtain Wall Replacement (Bldg SF) Storefront. All Windows On This Building Are E Item assessed & not considered a priority deficiency
Beyond Useful Life And Should Be Replaced.
Briarlake Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Briarlake Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Briarlake Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Briarlake Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Briarlake Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Briarlake Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Briarlake Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Briarlake Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Briarlake Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Brockett Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement Old, Canopy E Item assessed & not considered a priority deficiency
Brockett Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Brockett Elementary School 3 Building 2011 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Brockett Elementary School 3 Building 2012 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Brockett Elementary School 3 Building 2010 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Brockett Elementary School 3 Building 2011 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Brockett Elementary School 3 Building 2012 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Brockett Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement Old Gym E Item assessed & not considered a priority deficiency
Brockett Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Brockett Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Brockett Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Brockett Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Brockett Elementary School 2 Building 2010 Exterior Metal Exterior Door Replacement Corroded E Item assessed & not considered a priority deficiency
Brockett Elementary School 3 Electrical Pole Lighting Replacement Beyond Useful Life - Damaged E Item assessed & not considered a priority deficiency
Brockett Elementary School 2 Building 2010 Exterior Storefront/Curtain Wall Replacement (Bldg SF) Beyond Useful Life E Item assessed & not considered a priority deficiency
Brockett Elementary School 2 Building 2011 Exterior Storefront/Curtain Wall Replacement (Bldg SF) Beyond Useful Life E Item assessed & not considered a priority deficiency
Brockett Elementary School 2 Building 2012 Exterior Storefront/Curtain Wall Replacement (Bldg SF) Beyond Useful Life E Item assessed & not considered a priority deficiency
Browns Mill Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Old, Leaky E Item assessed & not considered a priority deficiency
Browns Mill Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Old, Leaky E Item assessed & not considered a priority deficiency
Browns Mill Elementary School 2 Building 2010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Browns Mill Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Browns Mill Elementary School 3 Building 2010 Interior Interior Door Replacement Doors Old, Deficient E Item assessed & not considered a priority deficiency
Browns Mill Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement All Fl E Item assessed & not considered a priority deficiency
Browns Mill Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement Entire Cfl Lighting E Item assessed & not considered a priority deficiency
Browns Mill Elementary School 3 Building 2020 Electrical Lightning Protection Terminal Replacement E Item assessed & not considered a priority deficiency
Browns Mill Elementary School 2 Building 2010 Exterior Metal Exterior Door Replacement Old, Deficient E Item assessed & not considered a priority deficiency
94 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Browns Mill Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Browns Mill Elementary School 2 Building 2010 Exterior Storefront/Curtain Wall Replacement (Bldg SF) Old, Moisture, Water Damage E Item assessed & not considered a priority deficiency
Canby Lane Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Canby Lane Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Canby Lane Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Canby Lane Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Canby Lane Elementary School 3 Building 2030 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Canby Lane Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Canby Lane Elementary School 3 Building 2011 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Canby Lane Elementary School 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Canby Lane Elementary School 3 Building 2030 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Canby Lane Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Canby Lane Elementary School 3 Building 2010 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Canby Lane Elementary School 3 Building 2030 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Canby Lane Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Canby Lane Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Canby Lane Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Canby Lane Elementary School 3 Building 2030 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Canby Lane Elementary School 2 Building 2010 Exterior Metal Exterior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Canby Lane Elementary School 2 Building 2011 Exterior Metal Exterior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Cary Reynolds Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Single Pane And Cracked Caulk E Item assessed & not considered a priority deficiency
Cary Reynolds Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Single Pane And Cracked Caulk E Item assessed & not considered a priority deficiency
Cary Reynolds Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Single Pane And Cracked Caulk E Item assessed & not considered a priority deficiency
Cary Reynolds Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Single Pane And Cracked Screens E Item assessed & not considered a priority deficiency
Cary Reynolds Elementary School 2 Building 2012 Exterior Aluminum Window Replacement Cracked Seams, Single Pane E Item assessed & not considered a priority deficiency
Cedar Grove Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Cedar Grove Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Cedar Grove Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Cedar Grove Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Cedar Grove Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement Old E Item assessed & not considered a priority deficiency
Cedar Grove Elementary School 3 Building 2011 Electrical Canopy Lighting Replacement Old E Item assessed & not considered a priority deficiency
Cedar Grove Elementary School 3 Building 2012 Electrical Canopy Lighting Replacement Old E Item assessed & not considered a priority deficiency
Cedar Grove Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement Old E Item assessed & not considered a priority deficiency
Cedar Grove Elementary School 3 Building 2012 Electrical Exterior Mounted Building Lighting Replacement Old E Item assessed & not considered a priority deficiency
Cedar Grove Elementary School 3 Building 2010 Interior Interior Door Replacement Damaged And Corroded Frame E Item assessed & not considered a priority deficiency
Cedar Grove Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Cedar Grove Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Cedar Grove Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Cedar Grove Elementary School 2 Building 2010 Exterior Metal Exterior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Cedar Grove Elementary School 2 Building 2010 Exterior Metal Exterior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Cedar Grove Elementary School 2 Building 2011 Exterior Metal Exterior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Cedar Grove Elementary School 3 Building 2010 Electrical Public Address System Head-End Requires Replacement E Item assessed & not considered a priority deficiency
Cedar Grove Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Cedar Grove Elementary School 3 Building 2011 Electrical Public Address System Replacement, Non-main Building Old E Item assessed & not considered a priority deficiency
Cedar Grove Elementary School 3 Building 2012 Electrical Public Address System Replacement, Non-main Building Old E Item assessed & not considered a priority deficiency
Cedar Grove Elementary School 2 Building 2010 Exterior Storefront/Curtain Wall Replacement (Bldg SF) Beyond Useful Life - Leaks E Item assessed & not considered a priority deficiency
Exterior Windows Are Aged And Beyond
Cedar Grove High School 2 Building 5010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Useful Life. Replace
Exterior Windows Are Aged And Beyond
Cedar Grove High School 2 Building 5010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Useful Life. Replace
Cedar Grove High School 2 Building 5011 Exterior Aluminum Window Replacement Aged And Obsolete. Replace E Item assessed & not considered a priority deficiency
Cedar Grove High School 2 Building 5012 Exterior Aluminum Window Replacement Aged And Obsolete. Replace E Item assessed & not considered a priority deficiency
Cedar Grove High School 2 Building 5012 Exterior Aluminum Window Replacement Aged And Obsolete. Replace E Item assessed & not considered a priority deficiency
Cedar Grove High School 2 Building 5012 Exterior Aluminum Window Replacement Aged And Obsolete. Replace E Item assessed & not considered a priority deficiency
Cedar Grove High School 3 Building 5010 Electrical Exterior Mounted Building Lighting Replacement Aged And Obsolete E Item assessed & not considered a priority deficiency
Cedar Grove High School 3 Building 5011 Electrical Exterior Mounted Building Lighting Replacement Aged And Obsolete E Item assessed & not considered a priority deficiency
Cedar Grove High School 3 Building 5012 Electrical Exterior Mounted Building Lighting Replacement Aged And Obsolete E Item assessed & not considered a priority deficiency
Cedar Grove High School 3 Building 5010 Electrical Lighting Fixtures Replacement Replace Lighting In Corridors And Cafeteria E Item assessed & not considered a priority deficiency
Cedar Grove High School 3 Building 5012 Electrical Lighting Fixtures Replacement Aged And Obsolete E Item assessed & not considered a priority deficiency
Cedar Grove Middle School 3 Building 4010 Electrical Canopy Lighting Replacement Old E Item assessed & not considered a priority deficiency
95 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Cedar Grove Middle School 3 Building 4010 Electrical Exterior Mounted Building Lighting Replacement Old E Item assessed & not considered a priority deficiency
Cedar Grove Middle School 3 Building 4010 Interior Interior Door Replacement Damaged E Item assessed & not considered a priority deficiency
Lighting Throughout Building Is Old And
Cedar Grove Middle School 3 Building 4010 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Should Be Replaced.
Cedar Grove Middle School 3 Building 4010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Cedar Grove Middle School 2 Building 4010 Exterior Metal Exterior Door Replacement Damaged E Item assessed & not considered a priority deficiency
Replace Gaskets And Sealant: Gaskets Are
Cedar Grove Middle School 2 Building 4010 Exterior Storefront / Curtain Wall Repair Falling Out Of Place, Sealant Is Cracked And E Item assessed & not considered a priority deficiency
Could Be Leading To Roof Leaks
Chamblee High School 3 Building 5040 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Champion Middle Theme 3 Building 4010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Champion Middle Theme 3 Building 4011 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Champion Middle Theme 3 Building 4012 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Champion Middle Theme 3 Building 4013 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Old, Throughout Building E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement Old, Exterior E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 3 Building 2011 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement Old, Exterior E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Elec Room E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Elec Room E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 2 Building 2011 Electrical Electrical Transformer Replacement Old, Elec Room E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 2 Building 2010 Mechanical Gas Piping Replacement (SF Basis) Throughout E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 2 Building 2011 Mechanical Gas Piping Replacement (SF Basis) Throughout E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 2 Building 2012 Mechanical Gas Piping Replacement (SF Basis) Throughout E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 2 Building 2013 Mechanical Gas Piping Replacement (SF Basis) Throughout E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
Original Doors Were Not Replaced With
Other Doors. 5 Door Frames Need To Be
Chapel Hill Elementary School 3 Building 2010 Interior Interior Door Replacement E Item assessed & not considered a priority deficiency
Replaced. Door Replacement Included With
12 Doors To Replace. Corroded And Kitchen
Chapel Hill Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement Old, Throughout Building E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 3 Building 2011 Electrical Interior Power Wiring Replacement Old, Throughout Building E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 3 Building 2012 Electrical Interior Power Wiring Replacement Throughout Building, Old E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 3 Building 2013 Electrical Interior Power Wiring Replacement Old, Throughout Building E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 2 Building 2010 Electrical Panelboard Replacement Elec Room E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 2 Building 2010 Electrical Panelboard Replacement Elec Room E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 2 Building 2010 Electrical Panelboard Replacement Elec Room E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 2 Building 2011 Electrical Panelboard Replacement Old, Elec Room E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 2 Building 2011 Electrical Panelboard Replacement Old, Elec Room E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 3 Building 2010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life
Throughout E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 3 Building 2011 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life
Throughout E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 3 Building 2012 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life
Throughout E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 3 Building 2013 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life
Throughout E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 3 Building 2010 Plumbing Sanitary Sewer Piping Replacement Throughout E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 3 Building 2011 Plumbing Sanitary Sewer Piping Replacement Throughout E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 3 Building 2012 Plumbing Sanitary Sewer Piping Replacement Throughout E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 3 Building 2013 Plumbing Sanitary Sewer Piping Replacement Throughout E Item assessed & not considered a priority deficiency
Chapel Hill Elementary School 2 Building 2010 Electrical Switchgear Replacement Old, Main Elec E Item assessed & not considered a priority deficiency
Chapel Hill Middle School 2 Building 4010 Exterior Aluminum Window Replacement Beyond Useful Life - Damaged E Item assessed & not considered a priority deficiency
Chapel Hill Middle School 3 Building 4010 Electrical Canopy Lighting Replacement Old Canopies E Item assessed & not considered a priority deficiency
Chapel Hill Middle School 2 Building 4010 Electrical Distribution Panel Replacement Old, Elec Room E Item assessed & not considered a priority deficiency
Chapel Hill Middle School 2 Building 4010 Electrical Electrical Transformer Replacement Old, Elec Room E Item assessed & not considered a priority deficiency
Chapel Hill Middle School 2 Building 4010 Electrical Electrical Transformer Replacement Old, Elec Room E Item assessed & not considered a priority deficiency
Chapel Hill Middle School 2 Building 4010 Electrical Electrical Transformer Replacement Old, Elec Room E Item assessed & not considered a priority deficiency
Chapel Hill Middle School 2 Building 4010 Electrical Electrical Transformer Replacement Old, Elec Room E Item assessed & not considered a priority deficiency
Chapel Hill Middle School 2 Building 4010 Electrical Generator Replacement Old, Exterior Building E Item assessed & not considered a priority deficiency
Chapel Hill Middle School 3 Building 4010 Interior Interior Door Replacement Damaged E Item assessed & not considered a priority deficiency
Chapel Hill Middle School 3 Building 4010 Electrical Interior Power Wiring Replacement Old, Throughout Building E Item assessed & not considered a priority deficiency
96 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Chapel Hill Middle School 2 Building 4010 Electrical Motor Control Center Replacement Old, Main Elec Room E Item assessed & not considered a priority deficiency
Chapel Hill Middle School 2 Building 4010 Electrical Panelboard Replacement Old, Elec Room E Item assessed & not considered a priority deficiency
Chapel Hill Middle School 2 Building 4010 Electrical Panelboard Replacement Old, Elec Room E Item assessed & not considered a priority deficiency
Chapel Hill Middle School 2 Building 4010 Electrical Panelboard Replacement Old, Elec Room E Item assessed & not considered a priority deficiency
Chapel Hill Middle School 2 Building 4010 Electrical Panelboard Replacement Old, Elec Room E Item assessed & not considered a priority deficiency
Chapel Hill Middle School 2 Building 4010 Electrical Panelboard Replacement Old, Elec Room E Item assessed & not considered a priority deficiency
Chapel Hill Middle School 2 Building 4010 Electrical Panelboard Replacement Old, Elec Room E Item assessed & not considered a priority deficiency
Chapel Hill Middle School 2 Building 4010 Electrical Switchgear Replacement Old, Main Elec. Room E Item assessed & not considered a priority deficiency
Chapel Hill Middle School 3 Building 4010 Electrical Transfer Switch Replacement Old, Main Elec Room E Item assessed & not considered a priority deficiency
Chesnut Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Chesnut Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Chesnut Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Chesnut Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Chesnut Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Chesnut Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Chesnut Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Chesnut Elementary School 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Chesnut Elementary School 3 Building 2010 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Chesnut Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Chesnut Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Chesnut Elementary School 2 Building 2010 Exterior Metal Exterior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5012 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5012 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 3 Building 5011 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5012 Mechanical Ductless Split System AC Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5010 Mechanical Electric Unit Heater Replacement Damaged E Item assessed & not considered a priority deficiency
Beyond Useful Life Gcfis And Regular
Clarkston High School 3 Building 5010 Electrical Electrical Receptacle Replacement E Item assessed & not considered a priority deficiency
Receptacles
Clarkston High School 3 Building 5011 Electrical Electrical Receptacle Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Beyond Useful Life - Gfci And Regular
Clarkston High School 3 Building 5012 Electrical Electrical Receptacle Replacement E Item assessed & not considered a priority deficiency
Receptacles Are Multiple Locations
Clarkston High School 2 Building 5010 Electrical Electrical Transformer Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5012 Electrical Electrical Transformer Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5012 Electrical Electrical Transformer Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5010 Electrical Exterior Dry Type Transformer Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 3 Building 5010 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 3 Building 5011 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 3 Building 5012 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 3 Building 5012 Electrical H.I.D. Lighting Replacement Beyond Useful Life - Fluorescent Lighting E Item assessed & not considered a priority deficiency
Clarkston High School 3 Building 5010 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 3 Building 5011 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 3 Building 5012 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 3 Building 5010 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Clarkston High School 3 Building 5011 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Clarkston High School 3 Building 5012 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Clarkston High School 3 Building 5013 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5010 Exterior Metal Exterior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5011 Exterior Metal Exterior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5012 Exterior Metal Exterior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5010 Roofing Modified Roof Covering Replacement E Item assessed & not considered a priority deficiency
800 Amps, 28 Loads, 1 Motor Controller
Clarkston High School 2 Building 5010 Electrical Motor Control Center Replacement E Item assessed & not considered a priority deficiency
Center
1 Mcc, 800 Amps, 15 Loads, Beyond Useful
Clarkston High School 2 Building 5012 Electrical Motor Control Center Replacement E Item assessed & not considered a priority deficiency
Life
1 Mcc, 800 Amps, 19 Loads, Beyond Useful
Clarkston High School 2 Building 5012 Electrical Motor Control Center Replacement E Item assessed & not considered a priority deficiency
Life
Clarkston High School 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
97 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Clarkston High School 2 Building 5010 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5011 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5011 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5011 Electrical Panelboard Replacement Beyond Useful Life 120 And 240 150A E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5011 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5011 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5012 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5012 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5012 Electrical Panelboard Replacement 120 And 208 200A, Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5012 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5012 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
2 Roof Drains Have No Grated Cap, 5 Roof
Clarkston High School 3 Building 5010 Roofing Roof Drain Cleaning E Item assessed & not considered a priority deficiency
Drains Clogged With Debris
Clarkston High School 2 Building 5010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5011 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5011 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Clarkston High School 2 Building 5010 Electrical Switchgear Replacement Beyond Useful Life 1000 Amps E Item assessed & not considered a priority deficiency
Clarkston High School 3 Building 5010 Plumbing Toilet Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2012 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2011 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2012 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2011 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2010 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2011 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2012 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Columbia Elementary School 2 Building 2010 Exterior Metal Exterior Door Replacement Issue With Locking E Item assessed & not considered a priority deficiency
Columbia Elementary School 2 Building 2011 Exterior Metal Exterior Door Replacement Issue With Locking E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2010 Electrical Public Address System Head-End Requires Replacement E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2011 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2012 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Columbia Elementary School 3 Building 2020 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Columbia Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia Elementary School 2 Building 2011 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5010 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5011 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5012 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5016 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5010 Electrical Exterior Mounted Building Lighting Replacement Damaged E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5011 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5016 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5011 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
98 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Columbia High School 3 Building 5015 Interior Interior Door Replacement E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5010 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5011 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5012 Electrical Lighting Fixtures Replacement Beyond Useful Life - Old T8 Lamps E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5013 Electrical Lighting Fixtures Replacement Beyond Useful Life - Old T8 Lamps E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5014 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5015 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5016 Electrical Lighting Fixtures Replacement Beyond Useful Life - Old T8 Lamps E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5020 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5011 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5012 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5013 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5014 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5016 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5020 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5010 Electrical Lightning Protection Terminal Replacement E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5015 Electrical Lightning Protection Terminal Replacement E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5011 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5012 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5013 Electrical Public Address System Replacement, Non-main Building Intercom Is Served From Building 5015 E Item assessed & not considered a priority deficiency
Columbia High School 3 Building 5014 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia Middle School 3 Building 4010 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia Middle School 3 Building 4010 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Columbia Middle School 3 Building 4010 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Columbia Middle School 3 Building 4010 Electrical Public Address System Head-End Requires Replacement E Item assessed & not considered a priority deficiency
Columbia Middle School 3 Building 4010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Coralwood Education 3 Building 2010 Electrical Lightning Protection System Installation Missing Building E Item assessed & not considered a priority deficiency
Coralwood Education 3 Building 2011 Electrical Lightning Protection System Installation Missing Building E Item assessed & not considered a priority deficiency
Coralwood Education 3 Building 2010 Electrical Public Address System Head-End Requires Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Coralwood Education 3 Building 2011 Electrical Public Address System Head-End Requires Replacement E Item assessed & not considered a priority deficiency
Coralwood Education 3 Building 2010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Coralwood Education 3 Building 2011 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
DeKalb Elementary School of the Arts 3 Building 4010 Electrical Lightning Protection System Installation Missing - Building E Item assessed & not considered a priority deficiency
DeKalb Elementary School of the Arts 3 Building 4010 Electrical Public Address System Head-End Requires Replacement E Item assessed & not considered a priority deficiency
DeKalb Elementary School of the Arts 3 Building 4010 Electrical Public Address System Head-End Requires Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
DeKalb Elementary School of the Arts 3 Building 4010 Electrical Public Address System Head-End Requires Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
DeKalb Elementary School of the Arts 3 Building 4010 Electrical Public Address System Head-End Requires Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
3X2 - Replace 5 Windows In Courtyard
DeKalb Elementary School of the Arts 2 Building 4010 Exterior Steel Window Replacement Storefronts Above Doors. Moisture Between E Item assessed & not considered a priority deficiency
Window Panes.
DeKalb High of Technology, South Campus 3 Building 5010 Electrical Canopy Lighting Replacement Old E Item assessed & not considered a priority deficiency
DeKalb High of Technology, South Campus 3 Building 5010 Electrical Exterior Mounted Building Lighting Replacement Old E Item assessed & not considered a priority deficiency
DeKalb High of Technology, South Campus 3 Building 5010 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
DeKalb High of Technology, South Campus 3 Building 5010 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
DeKalb High of Technology, South Campus 3 Building 5010 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
DeKalb High of Technology, South Campus 3 Building 5010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
DeKalb High of Technology, South Campus 2 Building 5010 Exterior Metal Exterior Door Replacement Corroded And Roof E Item assessed & not considered a priority deficiency
DeKalb High of Technology, South Campus 3 Electrical Pole Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
DeKalb High of Technology, South Campus 2 Building 5010 Exterior Storefront / Curtain Wall Repair Gaps E Item assessed & not considered a priority deficiency
Doraville Administrative 3 Building 8010 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Doraville Administrative 3 Building 8010 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Doraville Administrative 3 Building 8010 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Doraville Administrative 3 Building 8010 Electrical Lightning Protection Terminal Replacement Missing E Item assessed & not considered a priority deficiency
Dresden Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dresden Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Druid Hills High School 2 Building 5011 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Druid Hills High School 2 Building 5020 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Druid Hills High School 2 Building 5020 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Druid Hills High School 2 Building 5021 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Druid Hills High School 2 Building 5021 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
99 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Druid Hills High School 2 Building 5030 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Druid Hills High School 2 Building 5030 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Druid Hills High School 3 Building 5030 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Druid Hills High School 3 Building 5010 Interior Interior Door Hardware Replacement Worn Out E Item assessed & not considered a priority deficiency
Druid Hills High School 3 Building 5030 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Druid Hills High School 3 Building 5010 Interior Interior Door Replacement Worn Out E Item assessed & not considered a priority deficiency
Druid Hills High School 3 Building 5021 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Druid Hills High School 3 Building 5030 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Druid Hills High School 3 Building 5030 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Druid Hills High School 3 Building 5040 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Druid Hills High School 2 Building 5010 Exterior Metal Exterior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Druid Hills High School 2 Building 5020 Exterior Metal Exterior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Druid Hills High School 2 Building 5021 Exterior Metal Exterior Door Replacement Worn Out E Item assessed & not considered a priority deficiency
Druid Hills High School 3 Building 5030 Roofing Tapered Insulation Installation To Eliminate Ponding When Re-Roofing
Ponding E Item assessed & not considered a priority deficiency
Druid Hills High School 2 Building 5020 Exterior Wood Exterior Door Replacement Rotten E Item assessed & not considered a priority deficiency
Druid Hills Middle School 2 Building 4011 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Druid Hills Middle School 3 Building 4010 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Druid Hills Middle School 3 Building 4011 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Druid Hills Middle School 3 Building 4010 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Druid Hills Middle School 3 Building 4011 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Druid Hills Middle School 3 Building 4011 Interior Interior Door Hardware Replacement Damaged E Item assessed & not considered a priority deficiency
Druid Hills Middle School 3 Building 4010 Interior Interior Door Replacement E Item assessed & not considered a priority deficiency
Druid Hills Middle School 3 Building 4010 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Druid Hills Middle School 3 Building 4011 Electrical Lighting Fixtures Replacement Beyond Useful Life -Old T8 Lamps E Item assessed & not considered a priority deficiency
Druid Hills Middle School 3 Building 4010 Electrical Lightning Protection Terminal Replacement Not Installed E Item assessed & not considered a priority deficiency
Druid Hills Middle School 3 Building 4011 Electrical Lightning Protection Terminal Replacement Missing E Item assessed & not considered a priority deficiency
Druid Hills Middle School 3 Building 4010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Druid Hills Middle School 3 Building 4011 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2012 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2010 Exterior Brick Exterior Repointing Mortar Cracked E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2012 Exterior Brick Exterior Repointing Cracked And Weathered E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Mechanical Ductless Split System AC Replacement Beyond Useful Life - 4 Ton E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Mechanical Ductwork Replacement (SF Basis) Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2012 Mechanical Ductwork Replacement (SF Basis) Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2011 Electrical Electrical Transformer Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2012 Electrical Electrical Transformer Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Mechanical Gas Piping Replacement (SF Basis) Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2011 Mechanical Gas Piping Replacement (SF Basis) Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2012 Mechanical Gas Piping Replacement (SF Basis) Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Electrical Generator Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Electrical Generator Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Mechanical Heat Pump HVAC Component Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2010 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2010 Interior Interior Door Replacement Corroded E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2011 Electrical Interior Power Wiring Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2010 Mechanical Kitchen Exhaust Hood Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2012 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Beyond Useful Life E Item assessed & not considered a priority deficiency
100 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Dunaire Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Mechanical Package Roof Top Unit Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Mechanical Package Roof Top Unit Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Mechanical Package Roof Top Unit Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Mechanical Package Roof Top Unit Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Mechanical Package Roof Top Unit Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Electrical Panelboard Replacement E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2011 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2011 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2012 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2012 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2012 Electrical Panelboard Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2010 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Useful Life
Beyond E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2011 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Useful Life
Beyond E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2012 Plumbing Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Useful Life
Beyond E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2010 Electrical Public Address System Head-End Requires Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2011 Electrical Public Address System Head-End Requires Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2012 Electrical Public Address System Head-End Requires Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2020 Electrical Public Address System Head-End Requires Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2011 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2012 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2020 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 2 Building 2010 Mechanical Radiant Heater (Ceiling Panel) Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2010 Plumbing Sanitary Sewer Piping Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2012 Plumbing Sanitary Sewer Piping Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2010 Mechanical Testing And Balancing E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2011 Mechanical Testing And Balancing E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2012 Mechanical Testing And Balancing E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2010 Electrical Transfer Switch Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunaire Elementary School 3 Building 2010 Electrical Transfer Switch Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Dunwoody Elementary School 3 Building 2010 Electrical H.I.D. Lighting Replacement Fluorescent 20' - Gym E Item assessed & not considered a priority deficiency
Room 2337 (Restroom) Missing Lock
Dunwoody Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
Hardware
Various Classrooms Throughout And Media
Dunwoody Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Center And Cafeteria.
Dunwoody Elementary School 3 Building 2010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Dunwoody High School 3 Building 5012 Electrical Canopy Lighting Replacement Aged And Obsolete. E Item assessed & not considered a priority deficiency
Dunwoody High School 3 Building 5012 Electrical Exterior Mounted Building Lighting Replacement Aged And Obsolete. E Item assessed & not considered a priority deficiency
Dunwoody High School 3 Building 5012 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
Dunwoody High School 3 Building 5012 Interior Interior Door Replacement Replace Doors To Rooms 127 And 116 E Item assessed & not considered a priority deficiency
Replace Aged And Brittle Cfl Fixtures In
Dunwoody High School 3 Building 5011 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Office, Cafe And Hallways
Dunwoody High School 3 Building 5012 Electrical Lighting Fixtures Replacement Replace Cfl Fixtures Throughout E Item assessed & not considered a priority deficiency
Dunwoody High School 3 Building 5010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Dunwoody High School 3 Building 5011 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Dunwoody High School 3 Building 5013 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Dunwoody High School 3 Building 5012 Electrical Lightning Protection Terminal Replacement E Item assessed & not considered a priority deficiency
Eagle Woods Academy 3 Building 8010 Electrical 2 X 4 Interior Fluorescent Lighting Replacement Replace All Cfls Throughout 8010 E Item assessed & not considered a priority deficiency
Eagle Woods Academy 3 Building 8020 Electrical 2 X 4 Interior Fluorescent Lighting Replacement Replace All Cfls Throughout E Item assessed & not considered a priority deficiency
Eagle Woods Academy 2 Building 8020 Exterior Aluminum Window Replacement Old, Deficient. Replace Throughout E Item assessed & not considered a priority deficiency
Replace All. Bubbled Up, Old. Tripping
Eagle Woods Academy 3 Building 8020 Interior Athletic Sport Flooring Replacement E Item assessed & not considered a priority deficiency
Hazard.
Eagle Woods Academy 3 Building 8010 Electrical Canopy Lighting Replacement On Building Sides E Item assessed & not considered a priority deficiency
Eagle Woods Academy 2 Building 8010 Electrical Distribution Panel Replacement Basement, Old E Item assessed & not considered a priority deficiency
Eagle Woods Academy 2 Building 8020 Electrical Distribution Panel Replacement Basement Old E Item assessed & not considered a priority deficiency
101 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Eagle Woods Academy 3 Building 8010 Electrical Electrical Receptacle Replacement Multiple Locations E Item assessed & not considered a priority deficiency
Eagle Woods Academy 3 Building 8020 Electrical Electrical Receptacle Replacement Replace Old Receptables. Install Gfcl Receps. E Item assessed & not considered a priority deficiency
Eagle Woods Academy 2 Building 8020 Mechanical Gas Furnace HVAC Component Replacement Beyond Useful Life - Ne Corner Room 226 E Item assessed & not considered a priority deficiency
Eagle Woods Academy 3 Building 8020 Electrical H.I.D. Lighting Replacement Replace All Pendant Lighting In Gym E Item assessed & not considered a priority deficiency
Eagle Woods Academy 3 Building 8030 Interior Interior Door Hardware Replacement Hardware Old, Deficient E Item assessed & not considered a priority deficiency
Metal Doors At Room 226 (Idf) Old. Replace
Eagle Woods Academy 3 Building 8020 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
Doors And Hardware.
Door At Room 162 Has Plywood Boards As
Eagle Woods Academy 3 Building 8010 Interior Interior Door Replacement E Item assessed & not considered a priority deficiency
Temp Fix. Replace With New Door.
Eagle Woods Academy 3 Building 8030 Interior Interior Door Replacement Interior Closet Doors Old. E Item assessed & not considered a priority deficiency
Eagle Woods Academy 3 Building 8030 Electrical Lighting Fixtures Replacement Replace All Cfls E Item assessed & not considered a priority deficiency
Eagle Woods Academy 3 Building 8010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Eagle Woods Academy 3 Building 8030 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Eagle Woods Academy 3 Building 8020 Electrical Lightning Protection Terminal Replacement E Item assessed & not considered a priority deficiency
Eagle Woods Academy 2 Building 8010 Exterior Metal Exterior Door Replacement Old, Deficient Throughout. Replace. E Item assessed & not considered a priority deficiency
Eagle Woods Academy 2 Building 8030 Exterior Metal Exterior Door Replacement Old, Deficient, Replace. E Item assessed & not considered a priority deficiency
Eagle Woods Academy 2 Building 8020 Exterior Metal Exterior Door Replacement Old, Deficient. Replace All. E Item assessed & not considered a priority deficiency
Eagle Woods Academy 2 Building 8010 Electrical Panelboard Replacement Storage Room 111 E Item assessed & not considered a priority deficiency
Eagle Woods Academy 2 Building 8010 Electrical Panelboard Replacement Basement, Old E Item assessed & not considered a priority deficiency
Eagle Woods Academy 2 Building 8010 Electrical Panelboard Replacement Old, Room 143 E Item assessed & not considered a priority deficiency
Eagle Woods Academy 2 Building 8010 Electrical Panelboard Replacement Hallway, Old E Item assessed & not considered a priority deficiency
Eagle Woods Academy 2 Building 8020 Electrical Panelboard Replacement Gym, Main Lobby, Old E Item assessed & not considered a priority deficiency
Eagle Woods Academy 2 Building 8020 Electrical Panelboard Replacement Basement, Old E Item assessed & not considered a priority deficiency
Eagle Woods Academy 2 Building 8030 Electrical Panelboard Replacement 150A - Inside 8030 Old E Item assessed & not considered a priority deficiency
Eagle Woods Academy 3 Building 8010 Electrical Public Address System Replacement, Non-main Building Replace Entire System E Item assessed & not considered a priority deficiency
Eagle Woods Academy 3 Building 8020 Electrical Public Address System Replacement, Non-main Building Entire System To Be Replaced E Item assessed & not considered a priority deficiency
Eagle Woods Academy 3 Building 8030 Electrical Public Address System Replacement, Non-main Building Replace Throughout E Item assessed & not considered a priority deficiency
Eagle Woods Academy 2 Building 8030 Exterior Wood Window Replacement Old, Deficient, Boarded Up. E Item assessed & not considered a priority deficiency
Eagle Woods Academy 2 Building 8030 Exterior Wood Window Replacement Old, Deficient, Boarded Up. E Item assessed & not considered a priority deficiency
Early Learning Academy 3 Building 2010 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Early Learning Academy 3 Building 2011 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Early Learning Academy 3 Building 2012 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Early Learning Academy 3 Building 2020 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Early Learning Academy 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Early Learning Academy 3 Building 2011 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Early Learning Academy 3 Building 2012 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Early Learning Academy 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Early Learning Academy 3 Building 2010 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Early Learning Academy 3 Building 2011 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Early Learning Academy 3 Building 2020 Interior Interior Door Hardware Replacement Worn Out E Item assessed & not considered a priority deficiency
Early Learning Academy 3 Building 2011 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Early Learning Academy 3 Building 2010 Interior Interior Door Replacement Beyond Useful Life - Replace Door Frame E Item assessed & not considered a priority deficiency
Early Learning Academy 3 Building 2010 Electrical Lightning Protection System Installation Beyond Useful Life E Item assessed & not considered a priority deficiency
Early Learning Academy 3 Building 2011 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Early Learning Academy 3 Building 2012 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Early Learning Academy 3 Building 2020 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Early Learning Academy 3 Building 2010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Early Learning Academy 3 Building 2011 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Early Learning Academy 3 Building 2012 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Early Learning Academy 3 Building 2020 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
East Campus #1 DeKalb Alternative 2 Building 8010 Exterior Aluminum Window Replacement East Side Of Building E Item assessed & not considered a priority deficiency
East Campus #1 DeKalb Alternative 3 Building 8020 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
East Campus #1 DeKalb Alternative 2 Building 8010 Exterior Metal Exterior Door Replacement Replace Damaged On South Side E Item assessed & not considered a priority deficiency
East Campus #1 DeKalb Alternative 3 Electrical Pole Lighting Replacement E Item assessed & not considered a priority deficiency
East Campus #1 DeKalb Alternative 2 Building 8010 Exterior Steel Window Replacement Nw Of Building E Item assessed & not considered a priority deficiency
East Campus #2 Transportation 3 Building 8010 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
East Campus #2 Transportation 2 Building 8020 Exterior Wood Exterior Door Replacement E Item assessed & not considered a priority deficiency
East Campus #2 Transportation 2 Building 8020 Exterior Wood Window Replacement 3X4 E Item assessed & not considered a priority deficiency
102 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
East Campus #2 Transportation 2 Building 8020 Exterior Wood Window Replacement 3X6 E Item assessed & not considered a priority deficiency
Edward L. Bouie, Sr. Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement Multiple Locations E Item assessed & not considered a priority deficiency
Edward L. Bouie, Sr. Elementary School 3 Building 2010 Electrical Electrical Receptacle Replacement Multiple Locations. Burned Out And Broken. E Item assessed & not considered a priority deficiency
Edward L. Bouie, Sr. Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Room E128 - Old. E Item assessed & not considered a priority deficiency
Edward L. Bouie, Sr. Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Room E128 - Old. E Item assessed & not considered a priority deficiency
Edward L. Bouie, Sr. Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Room E173 - Old. E Item assessed & not considered a priority deficiency
Edward L. Bouie, Sr. Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Room E195 - Old. E Item assessed & not considered a priority deficiency
Edward L. Bouie, Sr. Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Room E213 - Old. E Item assessed & not considered a priority deficiency
Edward L. Bouie, Sr. Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Room E242 - Old. E Item assessed & not considered a priority deficiency
Edward L. Bouie, Sr. Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement Room E128 - Old. E Item assessed & not considered a priority deficiency
Edward L. Bouie, Sr. Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement Multiple Locations E Item assessed & not considered a priority deficiency
Old Lighting In Hallways, Classrooms, Kitchen,
Edward L. Bouie, Sr. Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Clinic, Offices, Gym Areas, Bathrooms, Media E Item assessed & not considered a priority deficiency
Center, Janitor Closets
Edward L. Bouie, Sr. Elementary School 3 Building 2010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Eldridge L. Miller Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Eldridge L. Miller Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Eldridge L. Miller Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Eldridge L. Miller Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Eldridge L. Miller Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Eldridge L. Miller Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Eldridge L. Miller Elementary School 3 Building 2010 Electrical Public Address System Head-End Requires Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Eldridge L. Miller Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Eldridge L. Miller Elementary School 3 Building 2011 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Eldridge L. Miller Elementary School 3 Building 2020 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Evansdale Elementary School 2 Building 2010 Exterior Aluminum Window Replacement 8X9(17Ea) 1X30(1Ea) 6X25(2Ea) E Item assessed & not considered a priority deficiency
Evansdale Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Evansdale Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Evansdale Elementary School 3 Building 2011 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Evansdale Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Evansdale Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Evansdale Elementary School 3 Building 2011 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Evansdale Elementary School 3 Building 2010 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Evansdale Elementary School 3 Building 2011 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Evansdale Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Beyond Useful Life - Old Fluorescent E Item assessed & not considered a priority deficiency
Evansdale Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement Beyond Useful Life - Old Fluorescent E Item assessed & not considered a priority deficiency
Evansdale Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement Beyond Useful Life - Old Fluorescent E Item assessed & not considered a priority deficiency
Evansdale Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Evansdale Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Evansdale Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Evansdale Elementary School 3 Building 2011 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Evansdale Elementary School 3 Building 2020 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Fairington Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Fairington Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Fairington Elementary School 2 Building 2010 Exterior EIFS Exterior Replacement (Bldg SF) Old, Stained. Replace E Item assessed & not considered a priority deficiency
Fairington Elementary School 3 Building 2010 Electrical Electrical Receptacle Replacement Multiple Locations E Item assessed & not considered a priority deficiency
Fairington Elementary School 3 Building 2011 Electrical Electrical Receptacle Replacement Multiple Locations E Item assessed & not considered a priority deficiency
Fairington Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement 2 Kva - Security Room, Old. E Item assessed & not considered a priority deficiency
Fairington Elementary School 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement Replace 3 Lights Not Working. E Item assessed & not considered a priority deficiency
Fairington Elementary School 3 Building 2020 Electrical H.I.D. Lighting Replacement Replace Old Cfls E Item assessed & not considered a priority deficiency
Old, Deficient. Some Not ADA Compliant.
Fairington Elementary School 3 Building 2011 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
Replace
Some ADA Non-Compliant (Knobs) - Replace
Fairington Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
All Door Hardware On Wood Doors.
Fairington Elementary School 3 Building 2011 Interior Interior Door Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Fairington Elementary School 3 Building 2010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Fairington Elementary School 3 Building 2011 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Fairington Elementary School 3 Building 2020 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
103 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Fairington Elementary School 2 Building 2010 Electrical Panelboard Replacement Kitchen, Old E Item assessed & not considered a priority deficiency
Fairington Elementary School 2 Building 2010 Electrical Panelboard Replacement Kitchen, Old E Item assessed & not considered a priority deficiency
Fernbank Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Fernbank Science Center 3 Building 8010 Interior Interior Door Hardware Replacement No ADA E Item assessed & not considered a priority deficiency
Flat Rock Elementary School 3 Building 2010 Electrical Public Address System Head-End Requires Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Flat Rock Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Flat Shoals Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Aged. E Item assessed & not considered a priority deficiency
Flat Shoals Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Aged E Item assessed & not considered a priority deficiency
Flat Shoals Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement Not ADA E Item assessed & not considered a priority deficiency
Flat Shoals Elementary School 3 Building 2011 Interior Interior Door Hardware Replacement Not ADA E Item assessed & not considered a priority deficiency
Flat Shoals Elementary School 3 Building 2020 Interior Interior Door Hardware Replacement Not ADA E Item assessed & not considered a priority deficiency
Flat Shoals Elementary School 3 Building 2030 Interior Interior Door Hardware Replacement Not ADA E Item assessed & not considered a priority deficiency
Flat Shoals Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Flat Shoals Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Flat Shoals Elementary School 3 Building 2030 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Flat Shoals Elementary School 3 Building 2040 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Flat Shoals Elementary School 3 Building 2010 Electrical Lightning Protection Terminal Replacement Missing E Item assessed & not considered a priority deficiency
Flat Shoals Elementary School 3 Building 2011 Electrical Lightning Protection Terminal Replacement Missing E Item assessed & not considered a priority deficiency
Flat Shoals Elementary School 3 Building 2020 Electrical Lightning Protection Terminal Replacement Missing E Item assessed & not considered a priority deficiency
Flat Shoals Elementary School 3 Building 2030 Electrical Lightning Protection Terminal Replacement Missing E Item assessed & not considered a priority deficiency
All Exterior Doors Do Not Work Correctly And
Flat Shoals Elementary School 2 Building 2010 Exterior Metal Exterior Door Replacement E Item assessed & not considered a priority deficiency
Are Beyond Useful Life
All Exterior Doors Do Not Work Correctly And
Flat Shoals Elementary School 2 Building 2011 Exterior Metal Exterior Door Replacement E Item assessed & not considered a priority deficiency
Are Beyond Useful Life
Flat Shoals Elementary School 3 Building 2010 Electrical Public Address System Head-End Requires Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Flat Shoals Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Flat Shoals Elementary School 3 Building 2020 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Flat Shoals Elementary School 3 Building 2030 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Freedom Middle School 2 Building 4010 Exterior Brick Exterior Replacement (Bldg SF) E Item assessed & not considered a priority deficiency
Freedom Middle School 3 Building 4010 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Freedom Middle School 3 Building 4010 Electrical Public Address System Head-End Requires Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Green Forrest Drive 2 Building 2010 Exterior Aluminum Window Replacement 14 Each 3' X 5' Windows E Item assessed & not considered a priority deficiency
Green Forrest Drive 2 Building 2010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Green Forrest Drive 2 Building 2011 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Green Forrest Drive 2 Building 2011 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Green Forrest Drive 2 Building 2012 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Some Internal Leaks Suggest Roof
Hallford, James R. Stadium 3 Building 8010 Roofing Built Up Roofing (Bur) Membrane Has Holes That Should Be Repaired E Item assessed & not considered a priority deficiency
Penetrations And Holes, Inspect And Repair.
Hallford, James R. Stadium 3 Building 8010 Electrical Canopy Lighting Replacement Replace Old Lights On Security E Item assessed & not considered a priority deficiency
Hallford, James R. Stadium 3 Building 8020 Electrical Canopy Lighting Replacement Old Canopy Lights Outside Building E Item assessed & not considered a priority deficiency
Hallford, James R. Stadium 2 Building 8010 Electrical Distribution Panel Replacement Old Concession Stands E Item assessed & not considered a priority deficiency
Hallford, James R. Stadium 3 Building 8010 Electrical Electrical Receptacle Replacement Multiple Locations E Item assessed & not considered a priority deficiency
Hallford, James R. Stadium 3 Building 8030 Electrical Electrical Receptacle Replacement Multiple Locations E Item assessed & not considered a priority deficiency
Hallford, James R. Stadium 2 Building 8010 Electrical Electrical Transformer Replacement Old, Concession Stands E Item assessed & not considered a priority deficiency
Hallford, James R. Stadium 2 Building 8010 Electrical Electrical Transformer Replacement 60 Kva Old Concession Stands E Item assessed & not considered a priority deficiency
Hallford, James R. Stadium 2 Building 8020 Electrical Electrical Transformer Replacement Old, Inside Field House E Item assessed & not considered a priority deficiency
Ext. Mtl Doors At Concession Stands And
Hallford, James R. Stadium 3 Building 8010 Exterior Exterior Metal Door Repainting E Item assessed & not considered a priority deficiency
Facilities Need Repainting.
Hallford, James R. Stadium 3 Building 8010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Hallford, James R. Stadium 3 Building 8020 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Hallford, James R. Stadium 3 Building 8030 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Hallford, James R. Stadium 2 Building 8020 Exterior Metal Exterior Door Replacement Old, Deficient. Replace All E Item assessed & not considered a priority deficiency
Hallford, James R. Stadium 2 Building 8010 Electrical Panelboard Replacement Old Concession Stands E Item assessed & not considered a priority deficiency
Hallford, James R. Stadium 2 Building 8010 Electrical Panelboard Replacement Old Concession Stands E Item assessed & not considered a priority deficiency
Hallford, James R. Stadium 2 Building 8010 Electrical Panelboard Replacement Old Concession Stands E Item assessed & not considered a priority deficiency
Hallford, James R. Stadium 2 Building 8010 Electrical Panelboard Replacement Old Concession Stands E Item assessed & not considered a priority deficiency
Hallford, James R. Stadium 2 Building 8010 Electrical Panelboard Replacement Old Concession Stands E Item assessed & not considered a priority deficiency
Hallford, James R. Stadium 2 Building 8020 Electrical Panelboard Replacement Inside Field House, Old E Item assessed & not considered a priority deficiency
Hallford, James R. Stadium 2 Building 8020 Electrical Panelboard Replacement 150A - Old, Inside Field House E Item assessed & not considered a priority deficiency
Hallford, James R. Stadium 2 Building 8010 Electrical Switchgear Replacement Old, Concession Stands E Item assessed & not considered a priority deficiency
104 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Beyond Useful Life - Blinds Beyond Useful Life
Hambrick Elementary School 2 Building 2010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
As Well
Hambrick Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Beyond Useful Life - Blinds Broken As Well E Item assessed & not considered a priority deficiency
Hambrick Elementary School 2 Building 2012 Exterior Aluminum Window Replacement Beyond Useful Life - Blinds Broken As Well E Item assessed & not considered a priority deficiency
Hambrick Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Hambrick Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Hambrick Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Hambrick Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Hambrick Elementary School 3 Building 2010 Mechanical Small Diameter Exhausts/Hoods Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Hambrick Elementary School 3 Building 2010 Mechanical Testing And Balancing Test E Item assessed & not considered a priority deficiency
Hambrick Elementary School 3 Building 2011 Mechanical Testing And Balancing Test E Item assessed & not considered a priority deficiency
Hambrick Elementary School 3 Building 2012 Mechanical Testing And Balancing Test E Item assessed & not considered a priority deficiency
Hambrick Elementary School 3 Building 2020 Mechanical Testing And Balancing Test E Item assessed & not considered a priority deficiency
Hatton Dr Warehouse 2 Building 8010 Exterior Aluminum Window Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Hatton Dr Warehouse 3 Building 8010 Electrical Canopy Lighting Replacement All Canopy Lights E Item assessed & not considered a priority deficiency
Hatton Dr Warehouse 3 Building 8010 Electrical Exterior Mounted Building Lighting Replacement All Building Mounted Lights E Item assessed & not considered a priority deficiency
Replace (2) Wood Doors In Mens And
Hatton Dr Warehouse 3 Building 8010 Interior Interior Door Replacement Womens Restrooms Closest To Warehouse E Item assessed & not considered a priority deficiency
Storage (South)
Hatton Dr Warehouse 3 Building 8010 Electrical Lighting Fixtures Replacement All Cfls Need Replacement E Item assessed & not considered a priority deficiency
Hatton Dr Warehouse 3 Building 8010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Hatton Dr Warehouse 2 Building 8010 Exterior Metal Exterior Door Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Hatton Dr Warehouse 2 Building 8010 Exterior Overhead Door Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Hatton Dr Warehouse 3 Building 8010 Electrical Public Address System Replacement, Non-main Building Needs Pa System E Item assessed & not considered a priority deficiency
Hawthorne Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Hawthorne Elementary School 3 Building 2011 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Hawthorne Elementary School 3 Building 2012 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Hawthorne Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Hawthorne Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Hawthorne Elementary School 3 Building 2011 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Hawthorne Elementary School 3 Building 2012 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Hawthorne Elementary School 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Hawthorne Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement Broken E Item assessed & not considered a priority deficiency
Hawthorne Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Hawthorne Elementary School 3 Building 2012 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Hawthorne Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Hawthorne Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Hawthorne Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Hawthorne Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Hawthorne Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Hawthorne Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Hawthorne Elementary School 3 Building 2011 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Hawthorne Elementary School 3 Building 2012 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Hawthorne Elementary School 3 Building 2020 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Henderson Middle School 3 Building 4012 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Henderson Middle School 3 Building 4013 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Henderson Middle School 3 Building 4014 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Henderson Middle School 3 Building 4010 Electrical Public Address System Head-End Requires Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Henderson Middle School 3 Building 4010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Henderson Mill Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Henderson Mill Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Henderson Mill Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Henderson Mill Elementary School 3 Building 2011 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Henderson Mill Elementary School 3 Building 2010 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Henderson Mill Elementary School 3 Building 2011 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Henderson Mill Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Henderson Mill Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Henderson Mill Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Henderson Mill Elementary School 3 Building 2010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
105 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Henderson Mill Elementary School 3 Building 2020 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Henderson Mill Elementary School 3 Building 2011 Electrical Lightning Protection Terminal Replacement E Item assessed & not considered a priority deficiency
Hightower Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Missing - Building E Item assessed & not considered a priority deficiency
Hightower Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Missing - Building E Item assessed & not considered a priority deficiency
Hightower Elementary School 3 Building 2013 Electrical Lightning Protection System Installation Missing - Building E Item assessed & not considered a priority deficiency
Hightower Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Missing - Building E Item assessed & not considered a priority deficiency
Hightower Elementary School 3 Building 2011 Electrical Lightning Protection Terminal Replacement Missing - Building E Item assessed & not considered a priority deficiency
Hightower Elementary School 3 Building 2010 Electrical Public Address System Head-End Requires Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Hightower Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Huntley Hills Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement Aged And Obsolete. E Item assessed & not considered a priority deficiency
Huntley Hills Elementary School 3 Building 2011 Electrical Canopy Lighting Replacement Aged And Obsolete. E Item assessed & not considered a priority deficiency
Huntley Hills Elementary School 3 Building 2012 Electrical Canopy Lighting Replacement Aged And Obsolete. E Item assessed & not considered a priority deficiency
Huntley Hills Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement Aged And Obsolete. E Item assessed & not considered a priority deficiency
Door Are Approaching Beyond Useful Life,
And Are Not Equipped With ADA Hardware.
Huntley Hills Elementary School 3 Building 2011 Interior Interior Door Replacement E Item assessed & not considered a priority deficiency
Room 113 Door Frame Is Particularly Rusted
And Damaged
Doors Are At Beyond Useful Life And Are Not
Huntley Hills Elementary School 3 Building 2012 Interior Interior Door Replacement E Item assessed & not considered a priority deficiency
Equipped With ADA Hardware.
Upgrade Lighting In Cafeteria, Corridors And
Huntley Hills Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Media Center
Huntley Hills Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement Aged And Obsolete. E Item assessed & not considered a priority deficiency
Huntley Hills Elementary School 3 Building 2012 Electrical Lighting Fixtures Replacement Aged And Obsolete. E Item assessed & not considered a priority deficiency
Huntley Hills Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement Aged And Obsolete. E Item assessed & not considered a priority deficiency
Huntley Hills Elementary School 3 Building 2011 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Huntley Hills Elementary School 3 Building 2012 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Idlewood Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Idlewood Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Idlewood Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Idlewood Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Jolly Elementary School 2 Building 2010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Jolly Elementary School 2 Building 2010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Jolly Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Jolly Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
Jolly Elementary School 3 Building 2011 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
Jolly Elementary School 3 Building 2010 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Jolly Elementary School 3 Building 2011 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Jolly Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Jolly Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Jolly Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Jolly Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Jolly Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Jolly Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Kelley Lake Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Kelley Lake Elementary School 3 Building 2012 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Kelley Lake Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Kelley Lake Elementary School 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Kelley Lake Elementary School 3 Building 2011 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Kelley Lake Elementary School 3 Building 2012 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Kelley Lake Elementary School 3 Building 2010 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Kelley Lake Elementary School 3 Building 2011 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Kelley Lake Elementary School 3 Building 2012 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Kelley Lake Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement Old Lights E Item assessed & not considered a priority deficiency
Kelley Lake Elementary School 3 Building 2012 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Kelley Lake Elementary School 3 Building 2020 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Kelley Lake Elementary School 3 Building 2010 Electrical Lightning Protection Terminal Replacement E Item assessed & not considered a priority deficiency
Kelley Lake Elementary School 3 Building 2011 Electrical Lightning Protection Terminal Replacement E Item assessed & not considered a priority deficiency
Kelley Lake Elementary School 2 Building 2020 Exterior Metal Exterior Door Replacement E Item assessed & not considered a priority deficiency
Kelley Lake Elementary School 2 Building 2011 Exterior Metal Exterior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Kingsley Elementary School 3 Building 2010 Electrical Lightning Protection Terminal Replacement Missing E Item assessed & not considered a priority deficiency
Kingsley Elementary School 3 Building 2011 Electrical Lightning Protection Terminal Replacement Missing E Item assessed & not considered a priority deficiency
106 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Kingsley Elementary School 3 Building 2020 Electrical Lightning Protection Terminal Replacement Missing E Item assessed & not considered a priority deficiency
Kittredge Magnet 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Kittredge Magnet 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Kittredge Magnet 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Kittredge Magnet 3 Building 2011 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Kittredge Magnet 3 Building 2012 Electrical Canopy Lighting Replacement Outside 215 E Item assessed & not considered a priority deficiency
Kittredge Magnet 3 Building 2020 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Kittredge Magnet 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Kittredge Magnet 3 Building 2011 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Kittredge Magnet 3 Building 2012 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Kittredge Magnet 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Kittredge Magnet 3 Building 2010 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Kittredge Magnet 3 Building 2011 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Kittredge Magnet 3 Building 2012 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Kittredge Magnet 3 Building 2010 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Kittredge Magnet 3 Building 2011 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Kittredge Magnet 3 Building 2012 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Kittredge Magnet 3 Building 2012 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Kittredge Magnet 3 Building 2020 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Kittredge Magnet 2 Building 2010 Exterior Storefront/Curtain Wall Replacement (Bldg SF) Beyond Useful Life E Item assessed & not considered a priority deficiency
Kittredge Magnet 2 Building 2011 Exterior Storefront/Curtain Wall Replacement (Bldg SF) Beyond Useful Life E Item assessed & not considered a priority deficiency
Kittredge Magnet 2 Building 2012 Exterior Storefront/Curtain Wall Replacement (Bldg SF) Beyond Useful Life E Item assessed & not considered a priority deficiency
Kittredge Magnet 2 Building 2010 Exterior Wood Exterior Door Replacement Rotten And Can Wash E Item assessed & not considered a priority deficiency
Lakeside High School 2 Building 5012 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5012 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5014 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5015 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5010 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5012 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5014 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5015 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5010 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5011 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5012 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5013 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5014 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5015 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5011 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5012 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5013 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5014 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5015 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5030 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5010 Electrical Lightning Protection Terminal Replacement Not Installed E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5010 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5011 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5012 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5013 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5014 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Lakeside High School 3 Building 5015 Electrical Public Address System Replacement, Non-main Building Building Is Served From Building 5010 E Item assessed & not considered a priority deficiency
Laurel Ridge Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Laurel Ridge Elementary School 3 Building 2010 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Laurel Ridge Elementary School 3 Building 2011 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Laurel Ridge Elementary School 3 Building 2012 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Laurel Ridge Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Laurel Ridge Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Laurel Ridge Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Laurel Ridge Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Laurel Ridge Elementary School 2 Building 2010 Exterior Metal Exterior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Laurel Ridge Elementary School 2 Building 2011 Exterior Metal Exterior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
107 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Laurel Ridge Elementary School 2 Building 2012 Exterior Metal Exterior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Laurel Ridge Elementary School 2 Building 2010 Exterior Wood Exterior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Old, Bad Shape; Assessor Also Mentions 14
Lithonia High School 3 Building 5010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Downlights In Canopies Need To Be Replaced
Lithonia High School 3 Building 5010 Electrical Exterior Mounted Building Lighting Replacement 32 Old Sconces E Item assessed & not considered a priority deficiency
Lithonia High School 3 Building 5010 Interior Interior Door Replacement E Item assessed & not considered a priority deficiency
Lithonia High School 3 Building 5010 Interior Interior Door Replacement Damaged E Item assessed & not considered a priority deficiency
Corridors, Media, And Admin Have New Led;
Lithonia High School 3 Building 5010 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
All Others Are Older Fl
Lithonia High School 3 Building 5020 Electrical Lighting Fixtures Replacement Bad Shape E Item assessed & not considered a priority deficiency
Lithonia High School 3 Building 5010 Electrical Lightning Protection Terminal Replacement Not Installed E Item assessed & not considered a priority deficiency
Lithonia High School 2 Building 5020 Exterior Metal Exterior Door Replacement Damaged E Item assessed & not considered a priority deficiency
Lithonia High School 2 Building 5010 Exterior Steel Window Replacement Boarded And Damaged; 20'X8' E Item assessed & not considered a priority deficiency
Lithonia High School 2 Building 5010 Exterior Steel Window Replacement E Item assessed & not considered a priority deficiency
Lithonia Middle School 2 Building 4010 Exterior Aluminum Window Replacement Kitchen 634 E Item assessed & not considered a priority deficiency
Lithonia Middle School 2 Building 4010 Exterior Aluminum Window Replacement Above Gym E Item assessed & not considered a priority deficiency
Lithonia Middle School 3 Building 4010 Interior Interior Door Hardware Replacement Gym Stairs E Item assessed & not considered a priority deficiency
Lithonia Middle School 3 Building 4010 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Lithonia Middle School 3 Building 4010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Lithonia Middle School 3 Building 4010 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Lithonia Middle School 2 Building 4010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Old And Room 14 - All Windows At School
Livsey Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Are Original Aluminum Non-Insulated. Fifty E Item assessed & not considered a priority deficiency
Years Old.
Old And Back Left Hall - They Work And Are In
Livsey Elementary School 2 Building 2010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Good Condition.
Old And All Rooms. Replace Kitchen Window
Livsey Elementary School 2 Building 2010 Exterior Aluminum Window Replacement At Back Of School That Is Boarded Up. See E Item assessed & not considered a priority deficiency
Picture.
Livsey Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Missing - Building E Item assessed & not considered a priority deficiency
Livsey Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Missing - Building E Item assessed & not considered a priority deficiency
Marbut Elementary School 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Marbut Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Marbut Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Marbut Elementary School 3 Building 2020 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Margaret Harris Comprehensive 3 Building 8010 Interior Interior Door Hardware Replacement Not ADA E Item assessed & not considered a priority deficiency
Margaret Harris Comprehensive 3 Building 8011 Interior Interior Door Hardware Replacement Not ADA E Item assessed & not considered a priority deficiency
Margaret Harris Comprehensive 3 Building 8010 Electrical Lightning Protection System Installation Missing And Building E Item assessed & not considered a priority deficiency
Margaret Harris Comprehensive 3 Building 8011 Electrical Lightning Protection System Installation Missing And Building E Item assessed & not considered a priority deficiency
Margaret Harris Comprehensive 3 Building 8012 Electrical Lightning Protection System Installation Missing And Building E Item assessed & not considered a priority deficiency
Margaret Harris Comprehensive 3 Building 8010 Electrical Public Address System Head-End Requires Replacement E Item assessed & not considered a priority deficiency
Margaret Harris Comprehensive 3 Building 8010 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Martin Luther King, Jr. High School 2 Building 5010 Exterior Aluminum Storefront Exterior Door Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Martin Luther King, Jr. High School 2 Building 5010 Exterior Aluminum Window Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Martin Luther King, Jr. High School 2 Building 5010 Exterior Aluminum Window Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Martin Luther King, Jr. High School 2 Building 5010 Exterior Aluminum Window Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Martin Luther King, Jr. High School 2 Building 5010 Exterior Aluminum Window Replacement 4'X2' Size. Old, Deficient E Item assessed & not considered a priority deficiency
Martin Luther King, Jr. High School 3 Building 5010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Martin Luther King, Jr. High School 3 Building 5011 Electrical Electrical Receptacle Replacement E Item assessed & not considered a priority deficiency
Martin Luther King, Jr. High School 3 Building 5010 Electrical Exterior Mounted Building Lighting Replacement Replace E Item assessed & not considered a priority deficiency
Martin Luther King, Jr. High School 3 Building 5010 Electrical H.I.D. Lighting Replacement Old Lights (Fluorescent) E Item assessed & not considered a priority deficiency
Martin Luther King, Jr. High School 3 Building 5010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Martin Luther King, Jr. High School 3 Building 5011 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Martin Luther King, Jr. High School 2 Building 5010 Exterior Metal Exterior Door Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Martin Luther King, Jr. High School 3 Building 5010 Electrical Public Address System Replacement, Non-main Building Replace Pa System E Item assessed & not considered a priority deficiency
Mary McLeod Bethune Middle School 3 Building 4010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Mary McLeod Bethune Middle School 3 Building 4010 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Mary McLeod Bethune Middle School 3 Building 4010 Electrical Lighting Fixtures Replacement Old Lighting Needs Replacement E Item assessed & not considered a priority deficiency
Mary McLeod Bethune Middle School 3 Building 4010 Electrical Lightning Protection Terminal Replacement E Item assessed & not considered a priority deficiency
Mary McLeod Bethune Middle School 3 Building 4010 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
108 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
McLendon Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement Aged And Obsolete. E Item assessed & not considered a priority deficiency
McLendon Elementary School 3 Building 2011 Electrical Canopy Lighting Replacement Aged And Obsolete. E Item assessed & not considered a priority deficiency
McLendon Elementary School 3 Building 2013 Electrical Canopy Lighting Replacement Aged And Obsolete. E Item assessed & not considered a priority deficiency
McLendon Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement Aged And Obsolete. E Item assessed & not considered a priority deficiency
McLendon Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement Aged And Obsolete. E Item assessed & not considered a priority deficiency
McLendon Elementary School 3 Building 2011 Electrical Exterior Mounted Building Lighting Replacement Aged And Obsolete. E Item assessed & not considered a priority deficiency
McLendon Elementary School 3 Building 2012 Electrical Exterior Mounted Building Lighting Replacement Aged And Obsolete. E Item assessed & not considered a priority deficiency
McLendon Elementary School 3 Building 2013 Electrical Exterior Mounted Building Lighting Replacement Aged And Obsolete. E Item assessed & not considered a priority deficiency
McLendon Elementary School 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement Aged And Obsolete. E Item assessed & not considered a priority deficiency
McLendon Elementary School 3 Building 2011 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
McLendon Elementary School 3 Building 2012 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
McLendon Elementary School 3 Building 2013 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
McLendon Elementary School 3 Building 2010 Interior Interior Door Replacement Aged And At Beyond Useful Life E Item assessed & not considered a priority deficiency
Aged And Beyond Useful Life With Non-ADA
McLendon Elementary School 3 Building 2011 Interior Interior Door Replacement E Item assessed & not considered a priority deficiency
Hardware.
Aged And Beyond Useful Life. Non-ADA
McLendon Elementary School 3 Building 2012 Interior Interior Door Replacement E Item assessed & not considered a priority deficiency
Hardware.
Aged Beyond Useful Life With Non-ADA
McLendon Elementary School 3 Building 2013 Interior Interior Door Replacement E Item assessed & not considered a priority deficiency
Hardware.
McLendon Elementary School 3 Building 2010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
McLendon Elementary School 3 Building 2011 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
McLendon Elementary School 3 Building 2012 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
McLendon Elementary School 3 Building 2013 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
McLendon Elementary School 3 Building 2020 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
McLendon Elementary School 2 Building 2010 Exterior Metal Exterior Door Replacement Deteriorated And Beyond Useful Life E Item assessed & not considered a priority deficiency
McLendon Elementary School 2 Building 2010 Electrical Public Address System Replacement, Main Bldg System Equipment
Aged And Obsolete E Item assessed & not considered a priority deficiency
McLendon Elementary School 2 Building 2011 Electrical Public Address System Replacement, Main Bldg System Equipment
Aged And Obsolete. E Item assessed & not considered a priority deficiency
McLendon Elementary School 2 Building 2012 Electrical Public Address System Replacement, Main Bldg System Equipment
Aged And Obsolete. E Item assessed & not considered a priority deficiency
McLendon Elementary School 2 Building 2013 Electrical Public Address System Replacement, Main Bldg System Equipment
Aged And Obsolete. E Item assessed & not considered a priority deficiency
McLendon Elementary School 2 Building 2020 Electrical Public Address System Replacement, Main Bldg System Equipment
Aged And Obsolete. E Item assessed & not considered a priority deficiency
McNair Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
McNair Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
McNair Elementary School 2 Building 2010 Exterior Metal Exterior Door Replacement Corroded E Item assessed & not considered a priority deficiency
McNair High School 2 Building 5020 Exterior Aluminum Window Replacement Cracked E Item assessed & not considered a priority deficiency
McNair High School 3 Building 5010 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
McNair High School 3 Building 5020 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
McNair High School 3 Building 5010 Interior Interior Door Hardware Replacement Damaged E Item assessed & not considered a priority deficiency
McNair High School 3 Building 5012 Interior Interior Door Replacement E Item assessed & not considered a priority deficiency
McNair High School 3 Building 5020 Interior Interior Door Replacement E Item assessed & not considered a priority deficiency
McNair High School 3 Building 5030 Interior Interior Door Replacement E Item assessed & not considered a priority deficiency
McNair High School 3 Building 5013 Interior Interior Door Replacement Damaged E Item assessed & not considered a priority deficiency
McNair High School 3 Building 5030 Interior Interior Overhead Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
McNair High School 3 Building 5010 Electrical Lighting Fixtures Replacement Beyond Useful Life - Old T8 Lamps E Item assessed & not considered a priority deficiency
McNair High School 3 Building 5011 Electrical Lighting Fixtures Replacement Beyond Useful Life - Old T8 Lamps E Item assessed & not considered a priority deficiency
McNair High School 3 Building 5012 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
McNair High School 3 Building 5013 Electrical Lighting Fixtures Replacement Beyond Useful Life - Old T8 Lamps E Item assessed & not considered a priority deficiency
McNair High School 3 Building 5020 Electrical Lighting Fixtures Replacement Beyond Useful Life - Old T8 Lamps E Item assessed & not considered a priority deficiency
McNair High School 3 Building 5030 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
McNair High School 3 Building 5011 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
McNair High School 3 Building 5012 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
McNair High School 3 Building 5013 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
McNair High School 3 Building 5030 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
McNair High School 3 Building 5020 Electrical Lightning Protection Terminal Replacement Missing E Item assessed & not considered a priority deficiency
McNair High School 3 Building 5010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
McNair High School 3 Building 5011 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Beyond Useful Life - Intercom System Is
McNair High School 3 Building 5012 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Served From Building 5010
McNair High School 3 Building 5013 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Beyond Useful Life - Intercom System Is
McNair High School 3 Building 5020 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Served From Building 5010
McNair High School 3 Building 5030 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
109 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
McNair Middle School 3 Building 01 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Replace All Windows. Old And Deficient.
Midvale Elementary School 2 Building 2010 Exterior Aluminum Window Replacement School Staff Mentioned Glass Panes Have E Item assessed & not considered a priority deficiency
Fallen Out. Hazard.
Replace All Windows. Old And Deficient.
Midvale Elementary School 2 Building 2010 Exterior Aluminum Window Replacement School Staff Mentioned Glass Panes Have E Item assessed & not considered a priority deficiency
Fallen Out. Hazard.
Midvale Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Old, Damaged. Replace E Item assessed & not considered a priority deficiency
Midvale Elementary School 2 Building 2011 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Midvale Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement Multiple Locations E Item assessed & not considered a priority deficiency
Midvale Elementary School 3 Building 2011 Electrical Canopy Lighting Replacement Outside Room 125 Hallway E Item assessed & not considered a priority deficiency
Midvale Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement Multiple Locations E Item assessed & not considered a priority deficiency
Midvale Elementary School 3 Building 2020 Electrical H.I.D. Lighting Replacement E Item assessed & not considered a priority deficiency
Midvale Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement Old, Damaged - Non-ADA Compliant. Replace E Item assessed & not considered a priority deficiency
Midvale Elementary School 3 Building 2011 Interior Interior Door Hardware Replacement Old, Deficient. Replace All. E Item assessed & not considered a priority deficiency
Midvale Elementary School 3 Building 2010 Interior Interior Door Replacement Old, Damaged - Replace E Item assessed & not considered a priority deficiency
Midvale Elementary School 3 Building 2011 Interior Interior Door Replacement Old, Deficient. Replace All. E Item assessed & not considered a priority deficiency
All Of The Cel Lighting Fixtures Need
Midvale Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Replacement.
Midvale Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement Interior Lighting E Item assessed & not considered a priority deficiency
Replace Fluorescent Lighting Fixtures Inside
Midvale Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
The Gym.
Midvale Elementary School 3 Building 2010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Midvale Elementary School 3 Building 2011 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Midvale Elementary School 3 Building 2020 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Midvale Elementary School 2 Building 2020 Exterior Metal Exterior Door Replacement East Door, Bad Condition E Item assessed & not considered a priority deficiency
Midvale Elementary School 2 Building 2011 Exterior Metal Exterior Door Replacement Old, Damaged. Replace E Item assessed & not considered a priority deficiency
Replace All Metal Doors. Old And Damaged
Midvale Elementary School 2 Building 2010 Exterior Metal Exterior Door Replacement E Item assessed & not considered a priority deficiency
Hardware.
Miller Grove High School 3 Building 5010 Mechanical Kitchen Exhaust Hood Replacement E Item assessed & not considered a priority deficiency
Miller Grove High School 3 Building 5011 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Miller Grove High School 3 Building 5020 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Miller Grove High School 3 Building 5010 Electrical Lightning Protection Terminal Replacement Missing E Item assessed & not considered a priority deficiency
Miller Grove High School 3 Building 5011 Mechanical Testing And Balancing E Item assessed & not considered a priority deficiency
Miller Grove Middle School 2 Building 4010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Miller Grove Middle School 2 Building 4010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Miller Grove Middle School 2 Building 4010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Miller Grove Middle School 2 Building 4010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Miller Grove Middle School 2 Building 4010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Miller Grove Middle School 2 Building 4010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Miller Grove Middle School 2 Building 4011 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Miller Grove Middle School 3 Building 4010 Electrical Canopy Lighting Replacement Old E Item assessed & not considered a priority deficiency
Miller Grove Middle School 3 Building 4011 Electrical Canopy Lighting Replacement Old E Item assessed & not considered a priority deficiency
Miller Grove Middle School 3 Building 4010 Electrical Exterior Mounted Building Lighting Replacement Old E Item assessed & not considered a priority deficiency
Miller Grove Middle School 3 Building 4011 Electrical Exterior Mounted Building Lighting Replacement Old E Item assessed & not considered a priority deficiency
Miller Grove Middle School 3 Building 4011 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Miller Grove Middle School 3 Building 4010 Interior Interior Door Hardware Replacement Beyond Useful Life - Damaged E Item assessed & not considered a priority deficiency
Miller Grove Middle School 3 Building 4010 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Miller Grove Middle School 3 Building 4011 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Miller Grove Middle School 3 Building 4010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Miller Grove Middle School 3 Building 4011 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Miller Grove Middle School 2 Building 4010 Exterior Metal Exterior Door Replacement Beyond Useful Life - Corroded E Item assessed & not considered a priority deficiency
Miller Grove Middle School 2 Building 4011 Exterior Metal Exterior Door Replacement Corroded E Item assessed & not considered a priority deficiency
Montclair Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Montclair Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Montclair Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Montclair Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Montclair Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Montclair Elementary School 3 Building 2011 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Montclair Elementary School 3 Building 2012 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
110 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Montclair Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Montclair Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Montclair Elementary School 3 Building 2011 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Montclair Elementary School 3 Building 2012 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Montclair Elementary School 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Montclair Elementary School 3 Building 2011 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
Montclair Elementary School 3 Building 2011 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Montclair Elementary School 3 Building 2010 Interior Interior Door Replacement Beyond Useful Life -Replace E Item assessed & not considered a priority deficiency
Montclair Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Montclair Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement Beyond Useful Life - T8 Lamps E Item assessed & not considered a priority deficiency
Montclair Elementary School 3 Building 2012 Electrical Lighting Fixtures Replacement Beyond Useful Life - T8 Lamps E Item assessed & not considered a priority deficiency
Montclair Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Montclair Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Montclair Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Montclair Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Montclair Elementary School 3 Building 2012 Electrical Lightning Protection Terminal Replacement Not Installed E Item assessed & not considered a priority deficiency
Montclair Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Montclair Elementary School 3 Building 2011 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Montclair Elementary School 3 Building 2012 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Montclair Elementary School 3 Building 2020 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Montgomery Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Montgomery Elementary School 3 Building 2011 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Montgomery Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Montgomery Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Montgomery Elementary School 3 Building 2011 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Montgomery Elementary School 3 Building 2012 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Montgomery Elementary School 3 Building 2013 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Montgomery Elementary School 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Montgomery Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Montgomery Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Montgomery Elementary School 3 Building 2012 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Montgomery Elementary School 3 Building 2013 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Montgomery Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Montgomery Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Montgomery Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Montgomery Elementary School 3 Building 2013 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Montgomery Elementary School 3 Building 2020 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Montgomery Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Montgomery Elementary School 3 Building 2011 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Montgomery Elementary School 3 Building 2012 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Intercom System Is Served From Building
Montgomery Elementary School 3 Building 2013 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
2010
Montgomery Elementary School 3 Building 2020 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Montgomery Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Montgomery Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Montgomery Elementary School 2 Building 2011 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Montgomery Elementary School 2 Building 2012 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Montgomery Elementary School 2 Building 2013 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Murphey Candler Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Murphey Candler Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Murphey Candler Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Murphey Candler Elementary School 3 Building 2013 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Murphey Candler Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Nancy Creek Facility 3 Building 2010 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Nancy Creek Facility 3 Building 2010 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Nancy Creek Facility 3 Building 2020 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Nancy Creek Facility 3 Building 2010 Electrical Public Address System Head-End Requires Replacement E Item assessed & not considered a priority deficiency
Nancy Creek Facility 3 Building 2010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Nancy Creek Facility 3 Building 2020 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Narvie Harris Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement Room 210, Plan East Exterior Doors (4) E Item assessed & not considered a priority deficiency
North DeKalb Stadium 2 Building 8010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
111 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
North DeKalb Stadium 2 Building 8010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
North DeKalb Stadium 2 Building 8010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
North DeKalb Stadium 2 Building 8010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
North DeKalb Stadium 2 Building 8020 Exterior Aluminum Window Replacement Beyond Useful Life - Damaged E Item assessed & not considered a priority deficiency
North DeKalb Stadium 3 Building 8010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
North DeKalb Stadium 3 Building 8020 Interior Interior Door Hardware Replacement Ext Door E Item assessed & not considered a priority deficiency
North DeKalb Stadium 3 Building 8010 Electrical Lighting Fixtures Replacement Old Inc Lamps T12 And T8 Lamps E Item assessed & not considered a priority deficiency
North DeKalb Stadium 3 Building 8010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
North DeKalb Stadium 3 Building 8020 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
North DeKalb Stadium 2 Building 8020 Exterior Metal Exterior Door Replacement Beyond Useful Life - Damaged E Item assessed & not considered a priority deficiency
Oak Grove Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement Not ADA E Item assessed & not considered a priority deficiency
Oak Grove Elementary School 3 Building 2011 Interior Interior Door Hardware Replacement Not ADA E Item assessed & not considered a priority deficiency
Oak Grove Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Oak Grove Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Oak Grove Elementary School 3 Building 2012 Electrical Lightning Protection Terminal Replacement Missing E Item assessed & not considered a priority deficiency
Oak Grove Elementary School 3 Building 2020 Electrical Lightning Protection Terminal Replacement Missing E Item assessed & not considered a priority deficiency
Oak Grove Elementary School 3 Building 2010 Electrical Public Address System Head-End Requires Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Oak Grove Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Oak Grove Elementary School 2 Building 2010 Exterior Steel Window Replacement Aged E Item assessed & not considered a priority deficiency
Oak Grove Elementary School 2 Building 2011 Exterior Steel Window Replacement Aged E Item assessed & not considered a priority deficiency
Oak View Elementary School 2 Building 2010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Oak View Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Oak View Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Oak View Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
Oak View Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Oak View Elementary School 3 Building 2010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Oak View Elementary School 3 Building 2010 Electrical Public Address System Head-End Requires Replacement E Item assessed & not considered a priority deficiency
Oak View Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Oakcliff Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Oakcliff Elementary School 2 Building 2012 Exterior Aluminum Window Replacement Single Pane And Cracking E Item assessed & not considered a priority deficiency
Oakcliff Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
Oakcliff Elementary School 3 Building 2012 Interior Interior Door Hardware Replacement Non ADA Compliant E Item assessed & not considered a priority deficiency
Oakcliff Elementary School 3 Building 2020 Interior Interior Door Replacement Faded Finish E Item assessed & not considered a priority deficiency
Old Rock Gym 3 Building 8010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Old Rock Gym 3 Building 8010 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Old Rock Gym 3 Building 8010 Interior Interior Door Hardware Replacement Damaged And Missing E Item assessed & not considered a priority deficiency
Old Rock Gym 3 Building 8010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Old Rock Gym 2 Building 8010 Exterior Metal Exterior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Old Rock Gym 3 Building 8010 Exterior Replace Steel Windows with Impact Glazing Historic And Weathered E Item assessed & not considered a priority deficiency
Old Rock Gym 2 Building 8010 Exterior Steel Window Replacement Historic And Weathered E Item assessed & not considered a priority deficiency
Panola Way Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Panola Way Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Exposed Wiring At Exterior Electrical
Panola Way Elementary School 3 Building 2011 Electrical Electrical Receptacle Replacement E Item assessed & not considered a priority deficiency
Receptacles.
Panola Way Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement E Item assessed & not considered a priority deficiency
Panola Way Elementary School 2 Building 2010 Electrical Electrical Transformer Replacement E Item assessed & not considered a priority deficiency
Panola Way Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Panola Way Elementary School 3 Building 2011 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Panola Way Elementary School 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Panola Way Elementary School 3 Building 2010 Electrical Interior Power Wiring Replacement E Item assessed & not considered a priority deficiency
Panola Way Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Panola Way Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Panola Way Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Panola Way Elementary School 3 Building 2010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Panola Way Elementary School 3 Building 2011 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Panola Way Elementary School 3 Building 2020 Electrical Lightning Protection Terminal Replacement E Item assessed & not considered a priority deficiency
Panola Way Elementary School 2 Building 2010 Electrical Panelboard Replacement E Item assessed & not considered a priority deficiency
Panola Way Elementary School 2 Building 2010 Electrical Panelboard Replacement E Item assessed & not considered a priority deficiency
Panola Way Elementary School 2 Building 2010 Electrical Panelboard Replacement E Item assessed & not considered a priority deficiency
Panola Way Elementary School 2 Building 2010 Electrical Panelboard Replacement E Item assessed & not considered a priority deficiency
Panola Way Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
112 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Panola Way Elementary School 3 Building 2011 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Panola Way Elementary School 3 Building 2020 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Panola Way Elementary School 2 Building 2010 Electrical Switchgear Replacement E Item assessed & not considered a priority deficiency
Panthersville Administrative 2 Building 8020 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Panthersville Administrative 2 Building 8020 Exterior Aluminum Window Replacement No Lift Left E Item assessed & not considered a priority deficiency
Panthersville Administrative 3 Building 8010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Panthersville Administrative 3 Building 8040 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Panthersville Administrative 3 Building 8010 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Panthersville Administrative 3 Building 8020 Electrical Exterior Mounted Building Lighting Replacement Damaged And Old E Item assessed & not considered a priority deficiency
Panthersville Administrative 3 Building 8040 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Panthersville Administrative 3 Building 8010 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Panthersville Administrative 3 Building 8020 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Panthersville Administrative 3 Building 8030 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Panthersville Administrative 3 Building 8040 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Panthersville Administrative 3 Building 8010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Panthersville Administrative 3 Building 8030 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Panthersville Administrative 2 Building 8010 Exterior Metal Exterior Door Replacement Weathered E Item assessed & not considered a priority deficiency
Panthersville Administrative 2 Building 8020 Exterior Wood Exterior Door Replacement No Lift Left E Item assessed & not considered a priority deficiency
Peachtree Middle School 3 Building 4010 Electrical 2 X 4 Interior Fluorescent Lighting Replacement Multiple Locations E Item assessed & not considered a priority deficiency
Peachtree Middle School 3 Building 4010 Electrical Exterior Mounted Building Lighting Replacement Multiple Locations E Item assessed & not considered a priority deficiency
Grounding And Lighting Protection Rod Is
Peachtree Middle School 3 Building 4010 Electrical Lightning Protection Terminal Replacement E Item assessed & not considered a priority deficiency
Installed On The Rooftop.
Pine Ridge Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Pine Ridge Elementary School 3 Building 2011 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Pine Ridge Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Pine Ridge Elementary School 3 Building 2011 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Pine Ridge Elementary School 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Pine Ridge Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
Pine Ridge Elementary School 3 Building 2010 Interior Interior Door Replacement E Item assessed & not considered a priority deficiency
Pine Ridge Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Pine Ridge Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Pine Ridge Elementary School 3 Building 2011 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Pine Ridge Elementary School 3 Building 2010 Electrical Lightning Protection Terminal Replacement E Item assessed & not considered a priority deficiency
Pine Ridge Elementary School 2 Building 2010 Exterior Metal Exterior Door Replacement E Item assessed & not considered a priority deficiency
Pine Ridge Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Pine Ridge Elementary School 3 Building 2011 Electrical Public Address System Replacement, Non-main Building System Is Served From Building 2010 E Item assessed & not considered a priority deficiency
Pine Ridge Elementary School 3 Building 2020 Electrical Public Address System Replacement, Non-main Building System Served From Building 2010 E Item assessed & not considered a priority deficiency
Pleasantdale (New) Elementary School 3 Building 8010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Princeton Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement Yellowed Lens E Item assessed & not considered a priority deficiency
Princeton Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Princeton Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Rainbow Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life - Replace Blinds As Well E Item assessed & not considered a priority deficiency
Rainbow Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life - Replace Blinds As Well E Item assessed & not considered a priority deficiency
Rainbow Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Beyond Useful Life - Replace Blinds As Well E Item assessed & not considered a priority deficiency
Rainbow Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Rainbow Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Rainbow Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Rainbow Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Redan Elementary School 2 Building 2020 Exterior Aluminum Window Replacement Aging And Original E Item assessed & not considered a priority deficiency
Redan Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Redan Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Redan Elementary School 3 Building 2022 Electrical Canopy Lighting Replacement Old E Item assessed & not considered a priority deficiency
Redan Elementary School 3 Building 2030 Electrical Canopy Lighting Replacement Old E Item assessed & not considered a priority deficiency
Redan Elementary School 3 Building 2040 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Redan Elementary School 3 Building 2040 Electrical H.I.D. Lighting Replacement Fluorescent E Item assessed & not considered a priority deficiency
Redan Elementary School 3 Building 2020 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
Redan Elementary School 3 Building 2022 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
Redan Elementary School 3 Building 2011 Interior Interior Door Replacement Doors Cracked E Item assessed & not considered a priority deficiency
113 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Redan Elementary School 3 Building 2020 Interior Interior Door Replacement Originals E Item assessed & not considered a priority deficiency
Redan Elementary School 3 Building 2022 Interior Interior Door Replacement Originals E Item assessed & not considered a priority deficiency
Redan Elementary School 3 Building 2022 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Redan Elementary School 3 Building 2010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Redan Elementary School 3 Building 2011 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Redan Elementary School 3 Building 2020 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Redan Elementary School 3 Building 2021 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Redan Elementary School 3 Building 2022 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Redan Elementary School 3 Building 2030 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Redan Elementary School 3 Building 2040 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Redan Elementary School 2 Building 2020 Exterior Metal Exterior Door Replacement E Item assessed & not considered a priority deficiency
Redan Elementary School 2 Building 2010 Exterior Metal Exterior Door Replacement Age E Item assessed & not considered a priority deficiency
Redan Elementary School 2 Building 2022 Exterior Metal Exterior Door Replacement Originals E Item assessed & not considered a priority deficiency
Redan Elementary School 3 Building 2040 Electrical Public Address System Replacement, Non-main Building Install System E Item assessed & not considered a priority deficiency
Redan Elementary School 2 Building 2022 Exterior Steel Window Replacement E Item assessed & not considered a priority deficiency
Redan High School 3 Building 5010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Redan High School 3 Building 5010 Electrical Exterior Mounted Building Lighting Replacement Old, Building Exterior E Item assessed & not considered a priority deficiency
Redan Middle School 2 Building 4010 Exterior Aluminum Window Replacement Fogging Up E Item assessed & not considered a priority deficiency
Redan Middle School 3 Building 4010 Specialties Auditorium Seating Replacement Broken E Item assessed & not considered a priority deficiency
Most Building Mounted Lights Are
Redan Middle School 3 Building 4010 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Operational
Redan Middle School 3 Building 4010 Interior Interior Door Replacement E Item assessed & not considered a priority deficiency
Almost All Is Fluorescent; Many Fixtures Are
Redan Middle School 3 Building 4010 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Blown Out And Fused
Redan Middle School 3 Building 4010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Robert Shaw Theme 3 Building 2010 Electrical 2 X 4 Interior Fluorescent Lighting Replacement Multiple Locations. Old Cfl E Item assessed & not considered a priority deficiency
Robert Shaw Theme 3 Building 2020 Electrical 2 X 4 Interior Fluorescent Lighting Replacement Old Cfls Inside Gym E Item assessed & not considered a priority deficiency
Windows Original (Old) Deficient, Cracked.
Robert Shaw Theme 2 Building 2010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Replace.
Windows Original (Old) Deficient, Cracked.
Robert Shaw Theme 2 Building 2010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Replace.
Windows Original (Old) Deficient, Cracked.
Robert Shaw Theme 2 Building 2010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Replace.
Windows Original (Old) Deficient, Cracked.
Robert Shaw Theme 2 Building 2010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Replace.
Windows Original (Old) Deficient, Cracked.
Robert Shaw Theme 2 Building 2010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Replace.
Windows Original (Old) Deficient, Cracked.
Robert Shaw Theme 2 Building 2010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Replace.
Robert Shaw Theme 2 Building 2011 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Robert Shaw Theme 2 Building 2011 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Robert Shaw Theme 2 Building 2011 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Old, Deficient Adjacent To Entry Double
Robert Shaw Theme 2 Building 2020 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Doors.
Robert Shaw Theme 3 Building 2010 Electrical Canopy Lighting Replacement Multiple Locations E Item assessed & not considered a priority deficiency
Robert Shaw Theme 3 Building 2011 Electrical Canopy Lighting Replacement Behind 403 E Item assessed & not considered a priority deficiency
Robert Shaw Theme 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement Behind 312 E Item assessed & not considered a priority deficiency
Robert Shaw Theme 3 Building 2020 Electrical H.I.D. Lighting Replacement Replace Old Cfls E Item assessed & not considered a priority deficiency
Robert Shaw Theme 3 Building 2010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Robert Shaw Theme 3 Building 2011 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Robert Shaw Theme 3 Building 2020 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Robert Shaw Theme 2 Building 2010 Exterior Metal Exterior Door Replacement Metal Doors Old, Deficient. E Item assessed & not considered a priority deficiency
Robert Shaw Theme 2 Building 2020 Exterior Metal Exterior Door Replacement Old, Deficient. Replace E Item assessed & not considered a priority deficiency
Robert Shaw Theme 2 Building 2011 Exterior Metal Exterior Door Replacement Old, Deficient. Replace. Throughout (All) E Item assessed & not considered a priority deficiency
Robert Shaw Theme 3 Building 2020 Electrical Public Address System Replacement, Non-main Building Old, Replace E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2011 Electrical Canopy Lighting Replacement Old Fixtures E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2012 Electrical Canopy Lighting Replacement Old Fixtures E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2013 Electrical Canopy Lighting Replacement Old Fixtures E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement Old Fixtures E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
114 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Rock Chapel Elementary School 3 Building 2011 Electrical Exterior Mounted Building Lighting Replacement Old Fixtures E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2012 Electrical Exterior Mounted Building Lighting Replacement Old Fixtures E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2013 Electrical Exterior Mounted Building Lighting Replacement Old Fixtures E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement Old Fixtures E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2013 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2020 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement Non-ADA E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2012 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2013 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement Old Light Fixtures E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2013 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Intercom System Is Served From Building
Rock Chapel Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
2011
Rock Chapel Elementary School 3 Building 2011 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2012 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2013 Electrical Public Address System Replacement, Non-main Building Intercom System Served From Building 2011 E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 3 Building 2020 Electrical Public Address System Replacement, Non-main Building Intercom System Served From Building 2011 E Item assessed & not considered a priority deficiency
Rock Chapel Elementary School 2 Building 2010 Exterior Wood Exterior Door Replacement Rotted - Room 6.3 E Item assessed & not considered a priority deficiency
Rockbridge Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Rockbridge Elementary School 3 Building 2010 Mechanical Testing And Balancing E Item assessed & not considered a priority deficiency
Rowland Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Rowland Elementary School 3 Building 2011 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Rowland Elementary School 3 Building 2012 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Rowland Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Rowland Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Rowland Elementary School 3 Building 2011 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Rowland Elementary School 3 Building 2012 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Rowland Elementary School 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Rowland Elementary School 3 Building 2012 Interior Interior Door Hardware Replacement Damaged E Item assessed & not considered a priority deficiency
Rowland Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Old T8 Lamp Fixtures E Item assessed & not considered a priority deficiency
Rowland Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement Old T8 Lamp Fixtures E Item assessed & not considered a priority deficiency
Rowland Elementary School 3 Building 2012 Electrical Lighting Fixtures Replacement Old T8 Lamp Fixtures E Item assessed & not considered a priority deficiency
Rowland Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement Old T8 Lamp Fixtures E Item assessed & not considered a priority deficiency
Rowland Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Rowland Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Rowland Elementary School 2 Building 2010 Exterior Metal Exterior Door Replacement Damaged E Item assessed & not considered a priority deficiency
Rowland Elementary School 3 Building 2010 Electrical Public Address System Head-End Requires Replacement E Item assessed & not considered a priority deficiency
Rowland Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Beyond Useful Life - Intercom System Is
Rowland Elementary School 3 Building 2011 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Served From Building 2010
Rowland Elementary School 3 Building 2012 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Rowland Elementary School 3 Building 2020 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Sagamore Hills Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Sagamore Hills Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Sagamore Hills Elementary School 3 Building 2020 Electrical Lightning Protection Terminal Replacement Not Existing E Item assessed & not considered a priority deficiency
Sagamore Hills Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Sagamore Hills Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Sagamore Hills Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Sagamore Hills Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Sagamore Hills Elementary School 2 Building 2010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Sagamore Hills Elementary School 2 Building 2011 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Salem Middle School 2 Building 4011 Exterior Aluminum Storefront Exterior Door Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Salem Middle School 2 Building 4010 Exterior Aluminum Window Replacement Old, Deficient E Item assessed & not considered a priority deficiency
115 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Salem Middle School 2 Building 4010 Exterior Aluminum Window Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Salem Middle School 2 Building 4011 Exterior Aluminum Window Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Salem Middle School 2 Building 4011 Exterior Aluminum Window Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Salem Middle School 2 Building 4011 Exterior Aluminum Window Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Salem Middle School 3 Building 4010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Salem Middle School 3 Building 4010 Electrical Electrical Receptacle Replacement E Item assessed & not considered a priority deficiency
Salem Middle School 3 Building 4011 Electrical Electrical Receptacle Replacement Multiple Locations E Item assessed & not considered a priority deficiency
Salem Middle School 2 Building 4010 Electrical Generator Replacement E Item assessed & not considered a priority deficiency
Salem Middle School 3 Building 4011 Interior Interior Door Hardware Replacement Old, Damaged, Replace E Item assessed & not considered a priority deficiency
Salem Middle School 3 Building 4010 Interior Interior Door Hardware Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Salem Middle School 3 Building 4011 Interior Interior Door Replacement Old, Damaged, Replace E Item assessed & not considered a priority deficiency
Salem Middle School 3 Building 4010 Interior Interior Door Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Salem Middle School 3 Building 4010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Salem Middle School 3 Building 4011 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Salem Middle School 2 Building 4010 Exterior Metal Exterior Door Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Salem Middle School 2 Building 4011 Exterior Metal Exterior Door Replacement Old, Deficient E Item assessed & not considered a priority deficiency
Salem Middle School 2 Building 4010 Electrical Panelboard Replacement Old E Item assessed & not considered a priority deficiency
Salem Middle School 2 Building 4010 Electrical Panelboard Replacement Old E Item assessed & not considered a priority deficiency
Salem Middle School 3 Building 4010 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Salem Middle School 3 Building 4011 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Salem Middle School 2 Building 4010 Electrical Switchgear Replacement E Item assessed & not considered a priority deficiency
Sam Moss Service Center 2 Building 8050 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Sam Moss Service Center 3 Building 8010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Sam Moss Service Center 3 Building 8030 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Sam Moss Service Center 3 Building 8040 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Sam Moss Service Center 3 Building 8050 Exterior Exterior Metal Door Repainting E Item assessed & not considered a priority deficiency
Sam Moss Service Center 3 Building 8010 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Sam Moss Service Center 3 Building 8020 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Sam Moss Service Center 3 Building 8040 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Sam Moss Service Center 3 Building 8010 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Sam Moss Service Center 3 Building 8010 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Sam Moss Service Center 3 Building 8010 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Sam Moss Service Center 3 Building 8020 Electrical Lighting Fixtures Replacement Beyond Useful Life - Old T8 Lamps E Item assessed & not considered a priority deficiency
Sam Moss Service Center 3 Building 8030 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Sam Moss Service Center 3 Building 8040 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Sam Moss Service Center 3 Building 8040 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Sam Moss Service Center 3 Building 8050 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Sam Moss Service Center 3 Building 8010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Sam Moss Service Center 2 Building 8010 Exterior Metal Exterior Door Replacement E Item assessed & not considered a priority deficiency
Sam Moss Service Center 2 Building 8010 Exterior Metal Exterior Door Replacement E Item assessed & not considered a priority deficiency
Sam Moss Service Center 2 Building 8040 Exterior Metal Exterior Door Replacement E Item assessed & not considered a priority deficiency
Sam Moss Service Center 2 Building 8010 Exterior Overhead Door Replacement E Item assessed & not considered a priority deficiency
Overhead Doors Are Significant Issues At This
Building Because The Service Bays Are Too
Narrow And The Buses Are Interfering With
Sam Moss Service Center 2 Building 8040 Exterior Overhead Door Replacement E Item assessed & not considered a priority deficiency
Overhead Doors. After Discussing With The
Building Fm, He Indicated The Doors Have
Significant Issues With Servicing The Buses
Sam Moss Service Center 2 Building 8010 Exterior Wood Exterior Door Replacement E Item assessed & not considered a priority deficiency
Sam Moss Service Center 2 Building 8060 Exterior Wood Exterior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Shadow Rock Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Shadow Rock Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Shadow Rock Elementary School 2 Building 2010 Exterior Metal Exterior Door Replacement Rusted E Item assessed & not considered a priority deficiency
Silver Hill Facility 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Silver Hill Facility 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Silver Hill Facility 2 Building 2011 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Silver Hill Facility 3 Building 2010 Electrical Canopy Lighting Replacement Old Canopies E Item assessed & not considered a priority deficiency
Silver Hill Facility 3 Building 2011 Electrical Canopy Lighting Replacement Old, Exterior E Item assessed & not considered a priority deficiency
Silver Hill Facility 3 Building 2011 Electrical Exterior Mounted Building Lighting Replacement Old, Exterior E Item assessed & not considered a priority deficiency
Silver Hill Facility 3 Building 2010 Interior Interior Door Hardware Replacement Worn Out E Item assessed & not considered a priority deficiency
116 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Silver Hill Facility 3 Building 2011 Interior Interior Door Hardware Replacement Worn Out E Item assessed & not considered a priority deficiency
Silver Hill Facility 3 Building 2010 Interior Interior Door Replacement Worn Out E Item assessed & not considered a priority deficiency
Silver Hill Facility 3 Building 2011 Interior Interior Door Replacement Worn Out E Item assessed & not considered a priority deficiency
Silver Hill Facility 3 Building 2010 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Silver Hill Facility 3 Building 2011 Electrical Lighting Fixtures Replacement New Fl Corridors, Classroom Lts Old. E Item assessed & not considered a priority deficiency
Silver Hill Facility 3 Building 2020 Electrical Lighting Fixtures Replacement Old, Gym E Item assessed & not considered a priority deficiency
Silver Hill Facility 3 Building 2010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Silver Hill Facility 3 Building 2011 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Silver Hill Facility 3 Building 2020 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Silver Hill Facility 2 Building 2010 Exterior Metal Exterior Door Replacement Damaged E Item assessed & not considered a priority deficiency
Snapfinger Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Age, Damage, Efficiency E Item assessed & not considered a priority deficiency
Snapfinger Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Age, Damage, Efficiency E Item assessed & not considered a priority deficiency
Snapfinger Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Age, Damage E Item assessed & not considered a priority deficiency
Snapfinger Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Age, Damage E Item assessed & not considered a priority deficiency
Snapfinger Elementary School 2 Building 2012 Exterior Aluminum Window Replacement Age, Damage, Efficiency E Item assessed & not considered a priority deficiency
Snapfinger Elementary School 2 Building 2012 Exterior Aluminum Window Replacement Age, Damage, Efficiency E Item assessed & not considered a priority deficiency
Snapfinger Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Snapfinger Elementary School 3 Building 2012 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Snapfinger Elementary School 3 Building 2012 Interior Interior Door Hardware Replacement Classroom Not ADA Compliant E Item assessed & not considered a priority deficiency
Snapfinger Elementary School 3 Building 2010 Interior Interior Door Replacement Age, Damage E Item assessed & not considered a priority deficiency
Snapfinger Elementary School 3 Building 2011 Interior Interior Door Replacement Age, Damage E Item assessed & not considered a priority deficiency
Snapfinger Elementary School 3 Building 2012 Interior Interior Door Replacement Age, Damage E Item assessed & not considered a priority deficiency
Snapfinger Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Snapfinger Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Snapfinger Elementary School 3 Building 2010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Snapfinger Elementary School 3 Building 2011 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Snapfinger Elementary School 3 Building 2012 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Snapfinger Elementary School 3 Building 2013 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Snapfinger Elementary School 3 Building 2020 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Snapfinger Elementary School 2 Building 2010 Exterior Metal Exterior Door Replacement Damage And Age, Room 151.2 E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 2 Building 5010 Mechanical Boiler Replacement Beyond Useful Life - Room 4200.1 E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5010 Electrical Canopy Lighting Replacement Multiple Locations - Old E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5011 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5040 Electrical Canopy Lighting Replacement Replace Broken Light E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5010 Mechanical Circulation Pump Replacement Beyond Useful Life - Room 4200.1 E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 2 Building 5011 Electrical Distribution Panel Repair Repair Locks In Hallway Panels 51 And 52 E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5010 Electrical Electrical Receptacle Replacement E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5011 Electrical Electrical Receptacle Replacement Broken Receptacles In 5201 And 5210 E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5012 Electrical Electrical Receptacle Replacement E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5013 Electrical Electrical Receptacle Replacement Broken Receptacle In 1148 E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5060 Electrical Electrical Receptacle Replacement Gfci Receptacles On The Outside E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 2 Building 5011 Electrical Electrical Transformer Repair Humming Noise. Repair E Item assessed & not considered a priority deficiency
Replace 2 Lights Outside 2193 And 2197
Southwest DeKalb High School 3 Building 5010 Electrical Exterior Mounted Building Lighting Replacement Rooms And In The Open Area Between Media E Item assessed & not considered a priority deficiency
Center And Computer Lab.
Southwest DeKalb High School 3 Building 5011 Electrical Exterior Mounted Building Lighting Replacement Gym Side Backside E Item assessed & not considered a priority deficiency
Replace 2 Building Lights Behind 101A And
Southwest DeKalb High School 3 Building 5020 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
106A
Southwest DeKalb High School 3 Building 5030 Electrical Exterior Mounted Building Lighting Replacement Replace All Lights E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5040 Electrical Exterior Mounted Building Lighting Replacement Each Side Of The Building E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5060 Electrical Interior Power Wiring Replacement Replace Wiring E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5070 Electrical Interior Power Wiring Replacement Replace Wiring E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5010 Electrical Lighting Fixtures Replacement Old, Inconsistent Light Fixtures. E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5011 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5012 Electrical Lighting Fixtures Replacement Old Lighting And Broken E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5040 Electrical Lighting Fixtures Replacement Replace In The Offices, Restrooms And Lobby. E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5011 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5012 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
117 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Southwest DeKalb High School 3 Building 5013 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5020 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5030 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5040 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5050 Electrical Lightning Protection System Installation Install System E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5060 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5070 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 2 Building 5020 Exterior Metal Exterior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 2 Building 5040 Exterior Metal Exterior Door Replacement Damaged And East Side Of Building E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 2 Building 5010 Electrical Motor Control Center Replacement Replace Old Mcc In 4273 E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5050 Electrical Mounted Building Lighting Installation Exterior Building Lights Needed. E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5060 Electrical Panel Spacing Cover Plate Is Missing E Item assessed & not considered a priority deficiency
Unnamed (From Lcs2) (Assumed) - Panel
Southwest DeKalb High School 2 Building 5010 Electrical Panelboard Replacement E Item assessed & not considered a priority deficiency
Missing Front
Southwest DeKalb High School 2 Building 5010 Electrical Panelboard Replacement Old - Teachers Lounge E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 2 Building 5010 Electrical Panelboard Replacement Old - 3230 Room E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 2 Building 5010 Electrical Panelboard Replacement Replace Room 4270 E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 2 Building 5010 Electrical Panelboard Replacement Replace Room 2197 E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 2 Building 5010 Electrical Panelboard Replacement 2114 Electrical Room E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 2 Building 5010 Electrical Panelboard Replacement Replace - Kitchen E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 2 Building 5010 Electrical Panelboard Replacement Replace - Kitchen E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 2 Building 5010 Electrical Panelboard Replacement Replace Outside Lockers And 2189 Area E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 2 Building 5010 Electrical Panelboard Replacement Girls And Boys Lockers E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 2 Building 5010 Electrical Panelboard Replacement Old - Replace 4270 E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 2 Building 5011 Electrical Panelboard Replacement E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 2 Building 5011 Electrical Panelboard Replacement E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 2 Building 5011 Electrical Panelboard Replacement E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 2 Building 5011 Electrical Panelboard Replacement Old 5103 E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 2 Building 5011 Electrical Panelboard Replacement Old 5011 Data Center E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 2 Building 5011 Electrical Panelboard Replacement Old 5011 Data Center E Item assessed & not considered a priority deficiency
Southwest DeKalb High School 3 Building 5010 Plumbing Toilet Replacement Beyond Useful Life - Room 2118B E Item assessed & not considered a priority deficiency
Stephenson High School 3 Building 5010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Stephenson High School 3 Building 5011 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Stephenson High School 3 Building 5050 Exterior Exterior Door Hardware Replacement E Item assessed & not considered a priority deficiency
Stephenson High School 3 Building 5010 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Stephenson High School 3 Building 5011 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Stephenson High School 3 Building 5050 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Stephenson High School 3 Building 5010 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Stephenson High School 3 Building 5011 Electrical Lighting Fixtures Replacement Old T8 Fl Lamps E Item assessed & not considered a priority deficiency
Stephenson High School 3 Building 5040 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Stephenson High School 3 Building 5050 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Stephenson High School 3 Building 5010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Stephenson High School 3 Building 5011 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Stephenson High School 3 Building 5020 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Stephenson High School 3 Building 5040 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Stephenson High School 3 Building 5050 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Stephenson High School 3 Building 5050 Exterior Metal Exterior Door Repair Reinstall Doors E Item assessed & not considered a priority deficiency
Stephenson High School 3 Building 5010 Electrical Public Address System Head-End Requires Replacement E Item assessed & not considered a priority deficiency
Stephenson High School 3 Building 5010 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Stephenson High School 3 Building 5011 Electrical Public Address System Replacement, Non-main Building Intercom System Served From Building 5010 E Item assessed & not considered a priority deficiency
Stephenson Middle School 3 Building 4010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Stephenson Middle School 3 Building 4011 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Stephenson Middle School 3 Building 4010 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Stephenson Middle School 3 Building 4011 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Stephenson Middle School 3 Building 4010 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
Stephenson Middle School 3 Building 4011 Interior Interior Door Hardware Replacement Exterior Metal Door E Item assessed & not considered a priority deficiency
Stephenson Middle School 3 Building 4010 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Stephenson Middle School 3 Building 4011 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Stephenson Middle School 3 Building 4010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Stephenson Middle School 3 Building 4011 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
118 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Stephenson Middle School 3 Building 4010 Electrical Public Address System Head-End Requires Replacement E Item assessed & not considered a priority deficiency
Stephenson Middle School 3 Building 4010 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Stephenson Middle School 3 Building 4011 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Stone Mill Elementary School 3 Building 2011 Mechanical Large Diameter Exhausts/Hoods Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Stone Mill Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Stone Mill Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Stone Mill Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Stone Mill Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Missing E Item assessed & not considered a priority deficiency
Stone Mill Elementary School 3 Building 2010 Electrical Public Address System Head-End Requires Replacement E Item assessed & not considered a priority deficiency
Stone Mill Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Stone Mill Elementary School 3 Building 2020 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Stone Mill Elementary School 3 Building 2010 Mechanical Testing And Balancing E Item assessed & not considered a priority deficiency
Stone Mill Elementary School 3 Building 2012 Mechanical Testing And Balancing E Item assessed & not considered a priority deficiency
Stone Mill Elementary School 3 Building 2020 Mechanical Testing And Balancing E Item assessed & not considered a priority deficiency
Stone Mountain Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Stone Mountain Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Stone Mountain Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Stone Mountain Elementary School 2 Building 2012 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Stone Mountain Elementary School 2 Building 2012 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Stone Mountain Elementary School 2 Building 2013 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Stone Mountain Elementary School 2 Building 2013 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Stone Mountain Elementary School 2 Building 2013 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Stone Mountain Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement Not Working E Item assessed & not considered a priority deficiency
Stone Mountain Elementary School 3 Building 2012 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Stone Mountain Elementary School 3 Building 2020 Electrical H.I.D. Lighting Replacement Beyond Useful Life Fluorescent Lighting E Item assessed & not considered a priority deficiency
Stone Mountain Elementary School 3 Building 2010 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Stone Mountain Elementary School 3 Building 2011 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Stone Mountain Elementary School 3 Building 2012 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Stone Mountain Elementary School 3 Building 2013 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Stone Mountain Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Stone Mountain Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Stone Mountain Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Stone Mountain Elementary School 3 Building 2013 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Stone Mountain Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Not Existing E Item assessed & not considered a priority deficiency
Stone Mountain High School 2 Building 5010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Stone Mountain High School 3 Electrical Area Lighting Installation Missing And Damaged E Item assessed & not considered a priority deficiency
Stone Mountain High School 2 Building 5010 Exterior Brick Exterior Replacement (Bldg SF) Weathered And Eroded E Item assessed & not considered a priority deficiency
Stone Mountain High School 3 Exterior Handrail Replacement Site Ramp Steel Hand Rail; Bent E Item assessed & not considered a priority deficiency
Stone Mountain High School 3 Building 5010 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Stone Mountain High School 3 Building 5010 Electrical Interior Power Wiring Replacement Original To Building E Item assessed & not considered a priority deficiency
Stone Mountain High School 3 Building 5010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Stone Mountain High School 2 Building 5010 Exterior Metal Exterior Door Replacement Broken E Item assessed & not considered a priority deficiency
Stone Mountain Middle School 3 Building 4010 Exterior Brick Exterior Repointing Repoint CMU, Not Brick; Cracked E Item assessed & not considered a priority deficiency
Stone Mountain Middle School 3 Building 4010 Electrical Lightning Protection System Installation Don't Exist E Item assessed & not considered a priority deficiency
Toney Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Toney Elementary School 3 Building 2011 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Toney Elementary School 3 Building 2012 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Toney Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Toney Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Toney Elementary School 3 Building 2011 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Toney Elementary School 3 Building 2012 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Toney Elementary School 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Toney Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Toney Elementary School 3 Building 2011 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Toney Elementary School 3 Building 2012 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Toney Elementary School 3 Building 2010 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Toney Elementary School 3 Building 2011 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Toney Elementary School 3 Building 2012 Interior Interior Door Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Toney Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Toney Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Toney Elementary School 3 Building 2012 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
119 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Toney Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement Old T8 Lamps E Item assessed & not considered a priority deficiency
Toney Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Installed. E Item assessed & not considered a priority deficiency
Toney Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Toney Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Toney Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Toney Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Intercom System Is Served From Building
Toney Elementary School 3 Building 2011 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
2010
Intercom System Is Served From Building
Toney Elementary School 3 Building 2012 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
2010
Beyond Useful Life - Intercom System Is
Toney Elementary School 3 Building 2020 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
Served From Building 2010
Toney Elementary School 2 Building 2010 Exterior Storefront/Curtain Wall Replacement (Bldg SF) Beyond Useful Life E Item assessed & not considered a priority deficiency
Toney Elementary School 2 Building 2011 Exterior Storefront/Curtain Wall Replacement (Bldg SF) Beyond Useful Life E Item assessed & not considered a priority deficiency
Toney Elementary School 2 Building 2012 Exterior Storefront/Curtain Wall Replacement (Bldg SF) Beyond Useful Life E Item assessed & not considered a priority deficiency
Towers High School 3 Building 5010 Electrical 2 X 4 Interior Fluorescent Lighting Replacement E Item assessed & not considered a priority deficiency
Towers High School 3 Building 5010 Electrical 2 X 4 Interior Fluorescent Lighting Replacement E Item assessed & not considered a priority deficiency
Towers High School 3 Building 5010 Electrical 2 X 4 Interior Fluorescent Lighting Replacement E Item assessed & not considered a priority deficiency
Towers High School 3 Building 5010 Electrical 2 X 4 Interior Fluorescent Lighting Replacement E Item assessed & not considered a priority deficiency
Towers High School 3 Building 5010 Electrical 2 X 4 Interior Fluorescent Lighting Replacement E Item assessed & not considered a priority deficiency
Towers High School 3 Building 5010 Electrical 2 X 4 Interior Fluorescent Lighting Replacement E Item assessed & not considered a priority deficiency
Towers High School 3 Building 5010 Interior Interior Door Hardware Replacement Broken E Item assessed & not considered a priority deficiency
Towers High School 3 Building 5010 Interior Interior Door Replacement Broken E Item assessed & not considered a priority deficiency
Towers High School 3 Building 5011 Interior Interior Door Replacement Broken E Item assessed & not considered a priority deficiency
Tucker High School 3 Building 5010 Electrical Lightning Protection System Installation Missing From Building E Item assessed & not considered a priority deficiency
Tucker High School 3 Building 5020 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Replace 30Sf Of Window Because Moisture Is
Tucker Middle School 2 Building 4010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Between Panes Of Glass. See Picture
Tucker Middle School 3 Building 4010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
6'6"X4' - Windows Have Spring Issues And
Vanderlyn Elementary School 2 Building 2010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Some Have Broken Glass
Vanderlyn Elementary School 2 Building 2011 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Vanderlyn Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement Old Lights Should Be Replaced E Item assessed & not considered a priority deficiency
Vanderlyn Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Vanderlyn Elementary School 3 Building 2011 Electrical Exterior Mounted Building Lighting Replacement Lights Not Working E Item assessed & not considered a priority deficiency
Vanderlyn Elementary School 3 Building 2011 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
Vanderlyn Elementary School 3 Building 2010 Interior Interior Door Replacement E Item assessed & not considered a priority deficiency
Lights In Rooms 22, 23, 25, 22.1, And 22.3
Vanderlyn Elementary School 3 Building 2010 Electrical Lighting Fixtures Replacement Need Replacement. Currently Have T8 And E Item assessed & not considered a priority deficiency
T12 Fixtures
Vanderlyn Elementary School 3 Building 2010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Vanderlyn Elementary School 3 Building 2011 Electrical Lightning Protection System Installation No Lightning Protection E Item assessed & not considered a priority deficiency
Vanderlyn Elementary School 3 Building 2020 Electrical Lightning Protection System Installation No Lightning Protection On Building E Item assessed & not considered a priority deficiency
Vanderlyn Elementary School 3 Building 2030 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Vanderlyn Elementary School 2 Building 2011 Exterior Metal Exterior Door Replacement E Item assessed & not considered a priority deficiency
Wadsworth Magnet School 3 Building 2010 Electrical Canopy Lighting Replacement Main Entrance Walkway E Item assessed & not considered a priority deficiency
Wadsworth Magnet School 3 Building 2010 Interior Interior Door Hardware Replacement Replace Knob Hardware E Item assessed & not considered a priority deficiency
Wadsworth Magnet School 3 Building 2010 Interior Interior Door Replacement Very Old, Damaged E Item assessed & not considered a priority deficiency
Wadsworth Magnet School 3 Building 2010 Electrical Lighting Fixtures Replacement Cfls In Area Need To Be Replaced E Item assessed & not considered a priority deficiency
Wadsworth Magnet School 3 Building 2011 Electrical Lighting Fixtures Replacement Interior Lighting Cfl Needs To Be Replaced E Item assessed & not considered a priority deficiency
Wadsworth Magnet School 3 Building 2020 Electrical Lighting Fixtures Replacement Replace All Interior Lights E Item assessed & not considered a priority deficiency
Wadsworth Magnet School 3 Building 2010 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Wadsworth Magnet School 3 Building 2011 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Wadsworth Magnet School 3 Building 2012 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Wadsworth Magnet School 3 Building 2020 Electrical Lightning Protection System Installation E Item assessed & not considered a priority deficiency
Wadsworth Magnet School 2 Building 2010 Exterior Metal Exterior Door Replacement Aged E Item assessed & not considered a priority deficiency
Wadsworth Magnet School 2 Building 2011 Exterior Metal Exterior Door Replacement Aged And Deficient, Replace E Item assessed & not considered a priority deficiency
Warren Technical Chamblee 2 Building 4010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Warren Technical Chamblee 2 Building 4010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
120 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Warren Technical Chamblee 2 Building 4010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Warren Technical Chamblee 2 Building 4010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Warren Technical Chamblee 2 Building 4010 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Warren Technical Chamblee 2 Building 4011 Exterior Aluminum Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Warren Technical Chamblee 3 Building 4010 Electrical Canopy Lighting Replacement Old E Item assessed & not considered a priority deficiency
Warren Technical Chamblee 3 Building 4011 Electrical Canopy Lighting Replacement Old E Item assessed & not considered a priority deficiency
Warren Technical Chamblee 3 Building 4010 Electrical Exterior Mounted Building Lighting Replacement Old E Item assessed & not considered a priority deficiency
Warren Technical Chamblee 3 Building 4011 Electrical Exterior Mounted Building Lighting Replacement Old E Item assessed & not considered a priority deficiency
Warren Technical Chamblee 3 Building 4010 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Warren Technical Chamblee 3 Building 4011 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
Warren Technical Chamblee 3 Building 4010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Warren Technical Chamblee 3 Building 4011 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Warren Technical Chamblee 2 Building 4010 Exterior Steel Window Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Windows Are Beyond Useful Life. Glazing Is
Warren Technical Chamblee 2 Building 4010 Exterior Storefront/Curtain Wall Replacement (Bldg SF) Single Pane, Warped Sealant Is Failing. Some E Item assessed & not considered a priority deficiency
Condensation Noted.
Windows Are Beyond Useful Life. Glazing Is
Warren Technical Chamblee 2 Building 4011 Exterior Storefront/Curtain Wall Replacement (Bldg SF) Single Pane, Some Are Warped. Sealant Is E Item assessed & not considered a priority deficiency
Failing.
William Bradley Bryant Technology Center 2 Building 8010 Exterior Aluminum Window Replacement 102 @ 8X4 - Non Operable E Item assessed & not considered a priority deficiency
William Bradley Bryant Technology Center 2 Building 8011 Exterior Aluminum Window Replacement Windows Show Aging E Item assessed & not considered a priority deficiency
William Bradley Bryant Technology Center 3 Building 8010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
William Bradley Bryant Technology Center 3 Building 8010 Electrical Install or Replace Rooftop Lightning Protection System E Item assessed & not considered a priority deficiency
William Bradley Bryant Technology Center 3 Building 8011 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
William Buck Godfrey Stadium 3 Building 8010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
William Buck Godfrey Stadium 3 Building 8010 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
William Buck Godfrey Stadium 3 Building 8010 Electrical Lighting Fixtures Replacement E Item assessed & not considered a priority deficiency
William Buck Godfrey Stadium 2 Building 8010 Exterior Metal Exterior Door Replacement Weathered E Item assessed & not considered a priority deficiency
Woodridge Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Woodridge Elementary School 3 Building 2011 Electrical Canopy Lighting Replacement Old Fixtures E Item assessed & not considered a priority deficiency
Woodridge Elementary School 3 Building 2020 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Woodridge Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Woodridge Elementary School 3 Building 2020 Electrical Exterior Mounted Building Lighting Replacement E Item assessed & not considered a priority deficiency
Woodridge Elementary School 3 Building 2011 Interior Interior Door Hardware Replacement E Item assessed & not considered a priority deficiency
Woodridge Elementary School 3 Building 2010 Interior Interior Door Hardware Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Woodridge Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Woodridge Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Woodridge Elementary School 3 Building 2010 Electrical Lightning Protection Terminal Replacement Not Installed E Item assessed & not considered a priority deficiency
Woodward Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Kitchen E Item assessed & not considered a priority deficiency
Woodward Elementary School 2 Building 2010 Exterior Aluminum Window Replacement Kitchen E Item assessed & not considered a priority deficiency
Replace Window Shades To All Windows In
Building Except Kitchen And Stairwells.
Woodward Elementary School 2 Building 2010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Existing Window Shades Are Old, Broken And
Bent.
Kitchen - Replace Window Shades To All
Windows In Building Except Kitchen And
Woodward Elementary School 2 Building 2010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Stairwells. Existing Window Shades Are Old,
Broken And Bent.
Woodward Elementary School 2 Building 2010 Exterior Aluminum Window Replacement In Stairwells, Replace 2 Windows. E Item assessed & not considered a priority deficiency
Replace Window Shades To All Windows In
Building Except Kitchen And Stairwells.
Woodward Elementary School 2 Building 2010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Existing Window Shades Are Old, Broken And
Bent.
Replace Window Shades To All Windows In
Building Except Kitchen And Stairwells.
Woodward Elementary School 2 Building 2010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Existing Window Shades Are Old, Broken And
Bent.
Replace Window Shades To All Windows In
Building Except Kitchen And Stairwells.
Woodward Elementary School 2 Building 2010 Exterior Aluminum Window Replacement E Item assessed & not considered a priority deficiency
Existing Window Shades Are Old, Broken And
Bent.
121 of 122 9/25/2024
Jacobs Priority 1-2-3 from Spring 2021, Sept. 2024 Update
Old, Not Insulated And All. Replace Window
Woodward Elementary School 2 Building 2011 Exterior Aluminum Window Replacement Shades To All 16 Windows. Existing Window E Item assessed & not considered a priority deficiency
Shades Are Old, Broken And Bent.
Woodward Elementary School 2 Building 2012 Exterior Aluminum Window Replacement Old, Non Insulated And All E Item assessed & not considered a priority deficiency
Woodward Elementary School 2 Building 2012 Exterior Aluminum Window Replacement Old, Non Insulated And All E Item assessed & not considered a priority deficiency
Woodward Elementary School 2 Building 2012 Exterior Aluminum Window Replacement Old, Non Insulated And All E Item assessed & not considered a priority deficiency
Woodward Elementary School 3 Building 2011 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Woodward Elementary School 3 Building 2012 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Woodward Elementary School 3 Building 2020 Electrical Lighting Fixtures Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Woodward Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Missing - Building E Item assessed & not considered a priority deficiency
Woodward Elementary School 3 Building 2011 Electrical Lightning Protection System Installation Missing - Building E Item assessed & not considered a priority deficiency
Woodward Elementary School 3 Building 2012 Electrical Lightning Protection System Installation Missing - Building E Item assessed & not considered a priority deficiency
Woodward Elementary School 3 Building 2020 Electrical Lightning Protection System Installation Missing - Building E Item assessed & not considered a priority deficiency
Woodward Elementary School 3 Building 2010 Electrical Public Address System Head-End Requires Replacement E Item assessed & not considered a priority deficiency
Woodward Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Woodward Elementary School 3 Building 2011 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Woodward Elementary School 3 Building 2012 Electrical Public Address System Replacement, Non-main Building Beyond Useful Life E Item assessed & not considered a priority deficiency
Replace T8 Strip Interior Lighting - Not
Wynbrooke Elementary School 3 Building 2010 Electrical Canopy Lighting Replacement E Item assessed & not considered a priority deficiency
Exterior Rated
Wynbrooke Elementary School 3 Building 2010 Electrical Exterior Mounted Building Lighting Replacement Beyond Useful Life E Item assessed & not considered a priority deficiency
Wynbrooke Elementary School 3 Building 2010 Electrical Lightning Protection System Installation Not Installed E Item assessed & not considered a priority deficiency
Wynbrooke Elementary School 3 Building 2010 Electrical Public Address System Head-End Requires Replacement E Item assessed & not considered a priority deficiency
Wynbrooke Elementary School 3 Building 2010 Electrical Public Address System Replacement, Non-main Building E Item assessed & not considered a priority deficiency
122 of 122 9/25/2024